Plan Number: S06-260
Parcel: Unknown

Address:
1615 E ALLEN RD

Review Status: Completed

Review Details: RECORD OF SURVEY REVIEW

Plan Number - S06-260
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Compliance with City ordinances and regulations not reviewed as part of the land split review process will be determined at the time of application for building permits when more detailed information is provided on the proposed development of each lot. LUC 4.3.3.3.E

No protected plants may be removed from the property prior to review and approval of building permits.
01/04/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#174922 January 2, 2007

Architique Homes
Attn: Neil Snyder
2561-2 E Ft. Lowell Road
Tucson, Arizona 85716-1540

Dear Mr. Snyder :

SUBJECT: Allen Road Estates
S06-260

Tucson Electric Power Company has reviewed and approved the development plan submitted December 14, 2006. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. TEP will need a full set of approved site, electrical load, paving off-site improvements and irrigation plans.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Warren McElyea at (520) 918-8268, should you have any questions.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: P. Gehlen and F. Rodriguez, City of Tucson (email)
W. McElyea, Tucson Electric Power
01/05/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-260
ARCHITIQUE HOMES
ALLEN ROAD ESTATES

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
01/10/2007 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-260 ALLEN ROAD ESTATES/RECORD OF SURVEY REVIEW
DATE: 1/10/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct Location Plan scale.

Include legal description on Title Block.

Change 40-68 to 46-13 and change 2-76 to 12-76 on Location Plan.

Arrow 34-11 to the correct location on Location Map.

Shade in project on Location Plan.

Number lots (not letters).

Provide recorded deeds with legal descriptions in order to obtain addresses.
01/11/2007 FRODRIG2 COT NON-DSD REAL ESTATE Denied S06-260 Allen Road Estates: Record of Survey Review - Request legal description be placed on first page. Request dotted lines delineate the W. boundary of Parcel "C" & and E. boundary of parcel "D". No title report provided.
01/12/2007 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S06-260
Allen Road Estates
Record of Survey

TRANSMITTAL: 01/12/07

DUE DATE: 01/12/07

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a record of survey. If, at the end of that time, the record of survey plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey plat is January 11, 2008.

2. DS 2-03.11.8.B.1 The Land Survey Exception case number assigned to this project is S06-260. Place the Land Survey Exception case number in the lower right hand corner of the plan next to the title block.

3. DS 2-03.11.12.B Show no-vehicular use easements where applicable. A one (1) foot no-vehicular use easement will be required on parcels "C" and "D" along the east, west and north property lines of the excluded parcel. Recordation information (docket and page) for the no-vehicular use easement must be included on the plan prior to approval.

4. DS 2-03.11.12.A On the reference plan, clearly indicate the location of the utility lines to the proposed structures. (gas, water, sewer and electrical)

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.

TLS C:\planning\cdrc\record of survey\S06-260ros.doc
01/17/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
01/19/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond January 19, 2007

To: Neil Snyder, Architique Homes

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J.Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Allen Road Estates (Record of Survey)
Final Plat - 1st Submittal
S06-260

The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the South Rillito - West (Central Line) Interceptor. Per written guidance provided by the PCWMD Development Services Section, sufficient conveyance and treatment capacity exists in the downstream public sewerage system for this small project, and a formal capacity response letter from the PCWMD will not be required.

Sheet 1: Add a General Note that states:

A JOUINT USE AND SEWER MAINTENANCE AGREEMENT, APPROVED BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT, IS REQUIRED PRIOR TO CONNECTION TO THE PUBLIC SEWER FOR ANY SHARED PRIVATE SEWER CONNECTIONS.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
01/25/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied DATE: January 25, 2007

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Suzanne Bohnet, CFM
Engineering Division

SUBJECT: S06-260 Allen Road Estates: Record of Survey (First Review)
T13S, R14E, Section 30

RESUBMITTAL REQUIRED: Record of Survey

The Engineering Division has reviewed the Record of Survey and we do not recommend approval at this time. The following review comments must be addressed.

Record of Survey Comments:
1. Please provide documentation verifying the lot split that created the excluded parcel received City of Tucson approval.
2. Aerial photographs indicate that a right-of-way sidewalk is not pre-existing. Per DS 2-03.11.1.C, a land survey exception may be applied for when all street frontage has existing sidewalks and curbs. Please verify that a sidewalk has been installed.
3. The Record of Survey indicates the 5' right-of-way sidewalk abuts the curb. If possible, provide for a 2' space between the sidewalk and curb.
4. Please ensure that all lettering and dimensions are the equivalent of 12 (0.12) point or greater in size for legibility when reproduced or microfilmed (DS 2-03.11.7.C).
5. Please provide the right-of-way width, recordation data, type and dimensioned width of paving, curbs and sidewalks for the existing right-of-way (DS 2-03.11.11.B).

Submit a revised Record of Survey with a detailed response letter detailing how each comment has been addressed.

If you have any questions, I can be reached at 791-5550 x1188 or suzanne.bohnet@tucsonaz.gov.

Suzanne Bohnet, CFM
Engineering Associate
01/31/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved CITY PARKS & RECREATION


DATE: January 8, 2007

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: S06-260 Allen Road Estates: Record of Survey Review


Staff has no comments.
02/02/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied see decision letter under "recordation" folder.
02/02/2007 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Needs Review COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

February 2, 2007

Neil Snyder
Architique Homes
2561-2 East Fort Lowell Road
Tucson, Arizona 85716-1540

Subject: S06-260 Allen Road Estates Record of Survey

Dear Neil:

Your submittal of December 14, 2006, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Record of Survey (Traffic, Addressing, Real Estate, Engineering, Zoning, DSD),

2 Copies Title Report (Real Estate, DSD)








Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 795-2686
12/13/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/20/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied December 20, 2006
ACTIVITY NUMBER: S06-260
PROJECT NAME: Allen Road Estates
PROJECT ADDRESS: 1615 E Allen Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Record of Survey; therefore a revised Record of Survey is required for resubmittal.

The following items must be revised or added to the Record of Survey.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. On the schematic development plan illustrate and dimension the location(s) of the proposed and existing adjacent driveways per (DS 2-02.2.1.A.11).

3. Locate driveways on adjacent properties to verify compliance with driveway spacing requirements of Tucson City Code Chapter 25 and Access Management Guidelines. There should be 12' of separation between all proposed and existing driveways.

If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
12/22/2006 JIM EGAN COT NON-DSD FIRE Approved
12/27/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information for
Rezoning, Subdivision, and
Development Requests
Delivered to:
Date Delivered:
Development Services - City of Tucson
12/22/2006
Case Number Project Name
Average number of daily trips
(ADT) forecasted as a result of the
proposed development
This information is provided for jurisdictional
planning departments to assess the impact of
the proposed residential or commercial
development on surrounding traffic patterns
and roads. If the forecasted daily traffic
exceeds 500 average daily trips, a more
detailed analysis is also provided.
S06-260 38 Allen Road Estates
Pima Association of Governments
Sandra C. Holland, Data Services
177 N. Church Ave., Suite 405, Tucson, Arizona
85701-1127
(520) 792-1093 FAX (520) 620-6981
12/27/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill within 1000 feet of this development.
* Four single family lots created off Allen Road. Lots will have to bring the APC's to Allen Road for service.
12/29/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-260 Allen Road Estates 12/29/06

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
(XXXX) Other - Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Northside

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 01/12/7

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: D.R. Corral 791-4505 DATE: 12/26/06