Plan Number: S06-247
Parcel: Unknown

Address:
3234 N TUCSON BL

Review Status: Completed

Review Details: RECORD OF SURVEY REVIEW

Plan Number - S06-247
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: January 3, 2007

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: S06-247 3234 N Tucson Bd Lot Split

Staff has no comments.
01/04/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: S06-247
3234 N. Tucson Blvd., one lot to two (prior split done 2000)
Record of Survey

TRANSMITTAL DATE: January 4, 2006

DUE DATE: December 26, 2006

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a record of survey. If, at the end of that time, the record of survey has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey is November 26, 2007.

2. This project was reviewed for content specifications outlined in DS 2-03.11.0, Record of Survey drafted specifications. This project was also reviewed for compliance with the Land Use Code (LUC) and Development Standards (DS).

3. Per DS 2-03.11.7.D, with regards to the project location map:
A) add a north arrow
B) reference nearby subdivisions with book and page

4. Per DS 2-03.11.7.E, place the words "Book_____" and "Page____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Recorders Office at time of recordation.

5. Per DS 2-03.2.11.7.F, with regards to the title block:
A) The first line of the title block must read "RECORD OF SURVEY" - correct and remove reference to a lot split.
B) To clarify, is project called "3234 N. Tucson. Blvd" if not, provide project name
C) Provide number of lots proposed

6. Per DS 2-03.2.11.7.I, provide a legend with all symbols used.

7. Per DS 2-03.2.11.8.A.1, list the primary owners of the site with contact info.

8. Per DS 2-03.2.11.8.B.1, place the case number "S06-247" near the title block.

9. Per DS 2-03.2.11.8.B.2, list as a general note "Existing zoning is R-1."

10. Per DS 2-03.2.11.8.B.3, Add the following note "The number of lots is 2."

11. Per DS 2-03.2.11.8.B.4, Add a note listing the gross area of the existing parcel.

12. Per DS 2-03.2.11.8.B.5, Add the following note, "There will be no further division of lots without the expressed approval of the City of Tucson."

13. Per DS 2-03.2.11.9.C, Include a 5" by 5" box for the County Recorder's stamp. The title over the box must read "RECORDING DATA".

14. Per DS 2-03.2.11.11.A, provide docket and page of all easements on plan.

15. Per DS 2-03.2.11.11.D, show adjacent zoning classifications on the plan.

16. Per DS 2-03.2.11.11.E, WILL THERE BE ANY RIGHT OF WAY DEDICATION FOR THE POTENTIAL WIDENING OF TUCSON BLVD.?

17. Per DS 2-03.2.11.12.B, provide a 1' wide No Vehicular Access Easement (NVAE) along the full 101.33' length of lot 2 - abutting parcel 122-03-358B. Parcel 358B was split off - under a lot split process in 2000 - from this subject site. I also see on the aerial photo where vehicular access can occur between parcel 358B and the driveway for these two lots, which would create problems for this split. Per code, there is a limit of no more than 2 units/lots allowed to have access off the same driveway. If parcel 358B uses the drive for these two lots, the entire entrance for these two lots would have to become a street, which would not allow the record of survey to proceed.

18. Please clarify who's fence is shown at the east, crossing into parcel 3530.

19. Per a 2005 aerial photo, I see a structure on what is to be lot 2. Has this structure been removed? I don't see a demolition permit in our system. Please provide a photo showing there is no structure near the entrance of the property. I do see that there is a house permit to be contained on lot 1.

20. Please note, depending upon responses provided, further review comments may be forthcoming. Should you have any questions on this review, contact me via email at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.


C:\planning\cdrc\record of survey\S06-247 3234 N Tucson.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised record of survey and additional requested documents.
01/09/2007 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Needs Review
01/09/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 9, 2007

Albert Durazo
A.O.E. Construction
4390 South Liberty Avenue
Tucson, Arizona 85714

Subject: S06-247 Tucson Boulevard Lot Split Record of Survey

Dear Albert:

Your submittal of November 27, 2006, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

7 Copies Revised Record of Survey (Traffic, Fire, Engineering, Real Estate, Zoning, Wastewater, DSD),

2 Copies Title Report (Real Estate, DSD)





Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 798-3428 Attention Albert
11/27/2006 MARILYN KALTHOFF START PLANS SUBMITTED Completed
12/01/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-247
A.O.E. CONSTRUCTION
3234 N TUCSON BLVD LOT SPLIT

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
12/01/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information for
Rezoning, Subdivision, and
Development Requests
Delivered to:
Date Delivered:
Development Services - City of Tucson
11/30/2006
Case Number Project Name
Average number of daily trips
(ADT) forecasted as a result of the
proposed development
This information is provided for jurisdictional
planning departments to assess the impact of
the proposed residential or commercial
development on surrounding traffic patterns
and roads. If the forecasted daily traffic
exceeds 500 average daily trips, a more
detailed analysis is also provided.
S06-247 19 Albert Durazo
Pima Association of Governments
Sandra C. Holland, Data Services
177 N. Church Ave., Suite 405, Tucson, Arizona
85701-1127
(520) 792-1093 FAX (520) 620-6981
12/04/2006 JCLARK3 ENV SVCS REVIEW Approved * Catus landfill is over 1000 feet from this development. No special provisions required.
* Service for this lot split will be APC curbside service. APC's will be placed and removed from the designated curbside collection area on the day of service.
12/06/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#173884 December 5, 2006

A.O.E Construction
Attn: Albert Durazo
4390 S Liberty Ave
Tucson, Arizona 85714

Dear Mr. Durazo :

SUBJECT: 3234 N Tucson Blvd
S06-247

Tucson Electric Power Company has reviewed and approved the development plan submitted Novermber 27, 2006. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. TEP will need a full set of approved site, electrical load, paving off-site improvements and irrigation plans.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Warren McElyea at (520) 918-8268, should you have any questions.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: P. Gehlen and F. Rodriguez, City of Tucson (email)
W. McElyea, Tucson Electric Power
12/06/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied December 6, 2006
ACTIVITY NUMBER: S06-247
PROJECT NAME: 3234 N. Tucson Blvd Lot Split
PROJECT ADDRESS: 3234 N. Tucson Blvd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Record of Survey; therefore revised documentation is required for re-submittal.

The following items must be revised or added to the required documentation.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Tucson Blvd is a Major Street and Route therefore; illustrate on a site plan or separate exhibit that vehicles on the proposed lots 1 & 2 can maneuver on-site in a manner that allows the vehicles to exit lots 1 & 2 face forward and do not back into Tucson Blvd.

3. On the future site plan the following standard will be waved to prevent conflict with existing adjacent driveways

"The access points shall have 25' radius curb returns. (DS 3-01.0 figure 6)".

Rather then 25' radius returns provide a standard driveway apron at the time of development of lots 1 & 2.


If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
12/18/2006 JOE LINVILLE LANDSCAPE REVIEW Approved
12/19/2006 JIM EGAN COT NON-DSD FIRE Denied Please transfer the notes indicating "fire sprinklers are required" to the large set of plans.
12/19/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-247 3234 N Tucson Blvd Lot Split 12/18/06

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – Record of Survey & Site Plan

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Richland Heights

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 12/26/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D.R. Corral 791-4505 DATE: 12/07/06
12/20/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: December 20, 2006

SUBJECT: Engineering review of the 3234 North Tucson Blvd., Record of Survey. The activity number is S06-247.

SUMMARY: The Record of Survey was received by Engineering on November 27th, 2006. Engineering has reviewed the received items and does not recommend approval of the Record of Survey.

RESUBMITTAL REQUIRED: RECORD OF SURVEY


RECORD OF SURVEY COMMENTS


1. Place the words "Book ____ Page ____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation. DS 2-03.11.7.E.

2. Per DS 2-03.11.7.F. the following information must be provided in the title block with the following information in the lower right corner of the first page of the Record of Survey;

a. The first line of the title block must read, "RECORD OF SURVEY".

b. Provide the proposed name of the Land Survey Exception.

c. The number of proposed lots is to be noted.

3. Provide a legend which shows and describes all symbols used on the drawing will be placed on either the first sheet or the first sheet which contains all or part of the drawing.

4. The following general notes will appear on the record of survey;

a. List the names, addresses, and telephone numbers of the primary owners of the site.

b.List the name, address, and telephone number of the person, firm, or organization that prepared the record of survey and the applicable registration number, along with the seal and signature, of the land surveyor or professional engineer.

5. Provide the general note, "The number of lots is ____." DS 2-03.11.8.B.3.

6. Add a note listing the gross area of the existing parcel. DS 2-03.11.8.B.4.

7. Add the following note, "There will be no further division of lots without the expressed approval of the City of Tucson." DS 2-03.11.8.B.5.

8. On single family projects bounded or intersected by a Major Street or Route, list the following note: "Lots with frontage on a street designated a Major Street or Route shall have ingress-egress designed in a manner so that motor vehicles do not back out onto the Major Street or Route, through the use of circular drives, turnarounds, or other similar solutions." DS 2-03.11.B.6.

9. Provide the following note: "Any relocation or modification of existing utilities and/or public improvements necessitated by the proposed development will be at no expense to the public." DS 2-03.11.8.C.1.

10. Provide the required information found in DS 2-03.11.9.

11. At least one (1) corner of the property will be tied by course and distance to a section corner, a quarter section corner, or an established City survey monument. The plan must include a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. Tie down one of the corners of the proposed lots to the provided basis of bearing. DS 2-02.11.10.A.

12. Provide a bearing for the dimensions on the west boundary. DS 2-03.11.10.B.

13. The basis of bearings should be established from two (2) found, physically monumented points described and shown on the plan. If the monuments at each end of the reference line are fully described on the plan, they need not be described in the "Basis of Bearings" statement. Revise appropriately. DS 2-03.11.10.C.1.

14. All boundary monumentation must be labeled as "found" or "set." Revise appropriately.

15. Fully describe and show all markings on found monuments. DS 2-03.11.10C.3.a.

16. A one-half (½) inch iron rod tagged by a registered land surveyor will be set at all corners upon completion of construction. DS 2-03.11.10.C.3.b.

17. Indicate whether the distance and bearings between all monuments are measured or calculated. DS 2-03.11.10.C.4.

18. All existing easements of record will be drawn on the plan, and recordation information, locations, widths, and purposes shall be included. DS 2-03.11.11.A.

19. Any parcel that is not part of this project must be removed. Revise.

20. Remove any site plan information i.e . references to fences and walls. This document is for survey information only.

21. Show no-vehicular access easements where applicable. DS 2-03.11.12.B.

22. Provide the recordation data for Tucson Blvd and indicate if this is a public or private road. DS 2-03.11.B.

23. Dimension from the centerline of Tucson Blvd the width of paving, curb and sidewalk location. DS 2-03.11.B.

24. Projects bounded by streets having only a portion of the Major Streets and Routes (MS&R) right-of-way width will be required to dedicate right-of-way to the MS&R width. Right-of-way dedication is required prior to Land Survey Exception approval. Include right-of-way dedication recordation information on the plan. DS 2-03.11.E.

25. All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. Recordation information (docket and page) must be included on the plan prior to final approval. DS 2-03.12.

26. Maximum curb cut width is 30' for two adjoining properties. Revise the survey to meet this requirement.

27. Be advised that to construct the proposed curb cuts a Right of Way (ROW) permit is required.

28. Please note that subsequent comments may be necessary upon resubmittal, depending on the nature and extent of revisions that occur to the plans.
12/22/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-247 3234 N TUCSON BL LOT SPLIT/RECORD OF SURVEY REVIEW
DATE: 12/22/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: Provide copies of recorded deeds prior to request of Addresses.




es
12/22/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied S06-247 3234 N Tucson Blvd Lot split: Record of survey Review - No title report was provided. Request 2' along the W. boundary of Subject Property be dedicated for MS&R purposes. MS&R calls for a 64' width at this location. The W. boundary of the Subject Property is 30' of the centerline of Tucson Blvd.
12/27/2006 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
12/27/2006 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
12/28/2006 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Denied December 28, 2006

To: Albert Durazo, A. O. E. Construction

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J. Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Lot Split 3234 N. Tucson Blvd., Record of Survey
Record of Survey - 1st Submittal
S06-247

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. This project will be tributary to the Roger Road Wastewater Treatment Facility via the South Rillito - West ( South Line) Interceptor. Per written guidance provided by the PCWMD Development Services Section, sufficient conveyance and treatment capacity exists in the downstream public sewerage system for this small project, and a formal capacity response letter from the PCWMD will not be required for this project.

2. The site plan for this lot split is not sealed by an engineer, architect or surveyor and I believe it would unsuitable for recording as a Record of Survey. The plan shows the 6" sewer main, I-671, in the Tucson Boulevard right of way, directly in front of the parcel, when our records indicate that this sewer, the nearest public sewer, is across the street and approximately 45' north of the property frontage. The owners should hire a registered professional, to develop a plan that presents an accurate representation of existing public sewer assets and the proposed connections that will provide sewer service for these two lots, before making another submittal to PCDSD of this project. However, PCDSD will allow a site plan submittal that is acceptable to city staff.

3. Revise the site plan to include the neighboring properties, which are currently sharing the existing private sewer, which these two proposed lots will need to connect to. Show the existing buildings that are served by the existing private sewer. Show the existing 4" private sewer, from its point of connection to the public sewer, to the connections to the existing buildings.

4. Revise the site plan to show a private utility or sewer easement, across the neighboring property owned by Squire, through the subject property, to the Studwell property. And, provide the appropriate recording information for these easements.

5. Before this office will be able to approve this lot split (or Record of Survey), a Joint Use and Maintenance Agreement, between the owner of this project and the owners of the other two parcels that share the existing private sewer (Squire and Studwell properties), will need to be recorded for the shared private sewer line. Prior to signature or recordation of these documents, this agreement must be reviewed and approved by the staff of the Pima County Wastewater Management Division, Development Services Section. Please contact Ms. Ilene Deckard about this matter as soon as possible. She can be reached at 740-6544.

6. This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the record of survey. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File