Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: S06-205
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S06-205
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/27/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved April 26, 2007

TO: J. Lorenzo Ortiz
Indevco A&E, Inc.

THRU: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department
,
FROM: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Las Sendas (RCP)
Lots 1 – 77 and Common Areas ‘A’ –‘D’
Tentative Plat – 3nd Submittal
S06-205

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either department. The following comments are offered for your use.

The cross reference numbers, C12-86-7A, C9-85-18, and CD9-85-18, have not been added to sheet 5.

Sheet 3. The sewer line shown in Laporte Lane, crossing Pandora Avenue, is not labeled. Provide a new keynote of the future status of this lateral or, if it is to be abandoned, please label it with keynote #8.

A copy of the approved variance request for drops in manholes and the sewer slopes is required.

Please note that this project cannot be approved until the approval cited in comment no 3 is received.

If you have any questions regarding the above mentioned comments, please contact me.

Sincerely,



Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: RSE Job #0432.08.2
04/27/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved July 3, 2007

TO: J. Lorenzo Ortiz, P.E.
Indevco A & E, Inc.

FROM: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department

FROM: Tom Porter, Sr. CEA
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Las Sendas , Lots 1 Through 77 and Common Areas 'A' -'D'
Tentative Plat-4th Submittal, SO6-205

The drawings for the proposed Final Plat of the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative or preliminary plat as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.



If you have any questions regarding the above comments, please do not hesitate to contact me.


Sincerely,







Tom Porter
520-740-6579
04/30/2007 ANDY VERA ENV SVCS REVIEW Denied 1. Refuse enclosure detail on page 4 does not provide the 10ft inside clear between the rear wall protector (bollard) and the front gates. Per DS 6-01.4.1.B.
Detail states 10ft 8in overall measurement and inside measurement adds up to 9ft 5in.

2. Detail does not demonstrate clearly how the enclosure gate that is attached to the common wall of the double enclosure will work. It does not appear that the gate will be able to swing open fully. Clarify how this gate will be mounted and ensure that the 10ft inside clear area is not encroached upon.
Also, the gates are to be designed so that each can be secured in the open position. Per DS 6-01.4.2.4
Recommend design to include ''positive locking and (bayonet) anchors plus four - 1in diameter x 6in long galvanized pipe that are to be flush with concrete so they can be secured when open or closed.

Correct all items on resubmittal.
05/02/2007 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: May 2, 2007
SUBJECT: Las Sendas Tentative Plat- 3rd Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 1425 W Ajo Way, T14S R13E Sec34/35, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: S06-205


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised Tentative Plat, Landscape Plans, Drainage Report, and Geotechnical Report. The Drainage Report was reviewed for Tentative Plat purposes only. Engineering Division recommends conditional approval of the Tentative Plat at this time. Items # 1 and # 2 need to be clarified prior to Mylar approval:

TENTATIVE PLAT:

1) DS Sec.6-01.4.1.B: Revise the refuse enclosure detail on Sheet 4 to verify the 10-foot inside clear dimension between the rear wall bollard and the front gate of the enclosure. The detail shows and inside clearance of ~9.5-feet.

2) DS Sec.6-01.4.2.4: Revise the refuse enclosure detail to verify the unobstructed 10-foot inside clearance at the enclosure gate that is attached to the common wall. Refer to Environmental Services comment for further clarity.


GENERAL COMMENTS:

3) DS Sec.11-01.2.1: For future reference a grading permit will be required for this project.

4) Please ensure the grading plan is consistent with the Tentative Plat, Drainage Report, and Geotechnical Report. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf.

5) Arizona Pollutant Discharge Elimination System (AZPDES) requirements are applicable to this project. Stormwater Pollution Prevention Plans and text addressing stormwater controls for all areas affected by construction activities related to this development will be required with grading plan submittal. For further information, visit www.adeq.state.az.us/environ/water/permits/stormwater.html.


CCR COMMENTS:

6) Revise the Condition Covenants and Restrictions prior to Final Plat approval. Remove the reference to Common Elements and replace with Common Areas. Verify that all language within the CCR match the Title Block of the Final Plat and that the name references the RCP designation.

If you have any questions, I can be reached at 837-4929 (Note new phone number for your records).



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
05/03/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

May 3, 2007

J. Lorenzo Ortiz, P.E.
INDEVCO A&E, Inc.
5995 East Grant Road, Suite 111
Tucson, Arizona 85712

Subject: S06-205 La Sendas Subdivision Tentative Plat

Dear Lorenzo:

The above referenced plan has been CONDITIONALLY APPROVED by the Community Design Review Committee, subject to the revisions required on the mylars. Please submit the following documents for sign-off:

1 Reproducible Océ or Photo Mylar of the Plat, Landscape Plan and NPPO.

Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and three (3) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Please note that the final plat must be approved by Mayor and Council and recorded within one year of date of approval of the tentative plat per LUC 4.1.7.3.

PRIOR TO SUBMITTING THE MYLARS TO THE CITY OF TUCSON CDRC OFFICE, THEY MUST BE APPROVED BY PIMA COUNTY WASTEWATER. PIMA COUNTY WASTEWATER MUST PROVIDE WRITTEN DOCUMENTATION (E-MAIL IS OKAY) THAT MYLARS HAVE MET THE CONDITIONS OF APPROVAL. DSD ENGINEERING WILL VERIFY CONDITIONS OF APPROVAL FOR ENGINEERING AND ESD HAVE BEEN MET.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 545-0092