| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2006 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 07/10/2006 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 07/12/2006 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Denied | July 12, 2006 ACTIVITY NUMBER: S06-149 PROJECT NAME: King Parcel PROJECT ADDRESS: 207 W King Road PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer Resubmittal Required: Traffic Engineering does not recommend approval of the Record of Survey; therefore a revised Record of Survey is required for resubmittal. The following items must be revised or added to the Record of Survey. 1. Show and label as to size (i.e. 20x110) both existing and future SVTs (DS 2-02.2.1.A.10). If the existing and future SVTs are coincident, label it as both existing and future. 2. Locate driveways on adjacent properties to verify compliance with driveway spacing requirements of Tucson City Code Chapter 25. A minimum 12' offset needs to be provided between curb cuts. If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov |
| 07/13/2006 | JCLARK3 | ENV SVCS | REVIEW | Approved | * No known landfill with in 1000 feet of this development. * Four lot split for individual homes. Service approved for APC curbside service. APC's will be required to be placed and removed from the curbside collection area on the day of service. |
| 07/17/2006 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | NO COMMENT S06-149 KING PARCEL |
| 07/18/2006 | JIM EGAN | COT NON-DSD | FIRE | Approved | Fire Sprinklers to be provided for lots 2, 3, and 4. |
| 07/18/2006 | RICHARD WILLIAMSON | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | WATER SUPPLY Tucson Water has been designated by the State of Arizona, Department of Water Resources, as having an assured water supply. This does not mean that water service is currently available to the proposed development. This development lies within the exterior boundary of Tucson Water's planned 50-year service area. Therefore, water supply is assured. WATER SERVICE The approval of water meter applications is subject to the availability of water service at the time an application is made. The developer shall be required to submit a water master plan identifying but not limited to: Water Use Fire Flow Requirements Offsite / Onsite Water Facilities Loops and Proposed Connection Points to Existing Water System Easements / Common Areas Any specific area plan fees, protected main / facility fees and / or other needed facilities' cost are to be paid by the developer. If the existing water system is not capable of meeting the requirements of the proposed development, the developer shall be fiscally responsible for modifying/enhancing the existing water system to meet those needs. This letter shall be null and void one year from the date of issuance. Issuance of this letter is not to be construed as agency approval of a water plan or as containing construction review comments relative to conflicts with existing water lines and the proposed development. If you have any questions, please call New Development at 791-4718. Sincerely, Richard S. Williamson, P.E. Manager, New Development RW:bjh |
| 07/20/2006 | FRODRIG2 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | ESTIMATED DAILY TRIPS - 38 |
| 07/25/2006 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | SUBJECT: KING PARCEL RECORD OF SURVEY REVIEW S06-149 Tucson Electric Power Company has reviewed and approved the record of survey review submitted July 7, 2006. It appears that there could possibly be conflicts with the existing facilities within the boundaries of this proposed development. Relocation costs are billable to the customer. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Secondary and secondary/service poles may be on property to the East, no way to tell without property corners identified. Also, note underground service from pole 193 to meter post. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Ms. Mary Boice New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8732 Please call the area Designer Warren McElyea at (520) 918-8268, should you have any questions. Sincerely, Kathy Clark for Denise Tellez Scheduling Coordinator Design/Build kc Enclosures cc: P. Gehlen, City of Tucson W. McElyea, Tucson Electric Power Kathy Clark Scheduling Coordinator Design/Build 520-918-8271 kclark@tep.com |
| 07/27/2006 | KAY MARKS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S06-149 KING PARCEL/RECORD OF SURVEY DATE: 7/26/06 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: Delete all street directions on Location Map. Change 44/63 to 41/63 on Location Map. Spell out all street suffixes except on Location Map. Delete 207 W. King Rd everywhere. Delete all tax codes and owner information on all adjacent parcels. es |
| 07/31/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | TO: Patricia Gehlen; CDRC Coordinator DATE: July 31, 2006 SUBJECT: Engineering review of the King Parcel, Record of Survey. The activity number is S06-149. SUMMARY: The Record of Survey was received by Engineering on July 7th, 2006. Engineering has reviewed the received items and does not recommend approval of the Record of Survey. RESUBMITTAL REQUIRED: RECORD OF SURVEY RECORD OF SURVEY COMMENTS 1. Place the Record of Survey case number in the lower right hand corner of sheet one. DS 2-0311.8.B.1. 2. Under the "DEDICATION" section it is recommended to remove the fourth paragraph because it is redundant with the second paragraph. Revise appropriately. DS 2-03.11.9.B. 3. At least one (1) corner of the property will be tied by course and distance to a section corner, a quarter section corner, or an established City survey monument. The plan must include a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. Revise survey appropriately. DS 2-03.11.10.A. 4. Show easements of record on the plan, with recordation information, locations, widths, and purposes shall be included. DS 2-03.11.11A. 5. Provide the recordation data (book and page) for King Road. DS 2-03.11.11.B. 6. Dimension from the street centerline of King Road to the existing curb and the proposed sidewalk. DS 2-03.11.11.B. 7. Provide the sidewalk width located along King Road. 8. Provide a copy of the ROW permit for the proposed sidewalks. 9. |
| 08/01/2006 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Approved | S06-149 King Parcel: Record of Survey Review - No comment. |
| 08/03/2006 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | August 1, 2006 TO: Don Burke Lee Moran Development, LLC THRU: Patricia Gehlen City of Tucson, Development Services Department FROM: Dickie Fernández, E.I.T. Pima County Development Services Department Development Review Division (Wastewater) SUBJECT: King Parcel Tentative Plat – 1st Submittal S06-149 The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf. ALL SHEETS. Add the project number, S06-149, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers. Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates. SHEET 1. Add the following General Note ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS. SHEET 1. Add the following General Note A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT. Show the length, size and slope for all newly proposed sewers. Show the six-digit Pima County manhole number for all existing public manholes that may be located on W King Road. Show the size and Pima County plan number for the existing public sewer(s) that may be located on W King Road. Please be aware that if this project plans for the proposed sewers to be shared among the lots on this project, this project will require a Joint Use And Maintenance Agreement. Please contact Ilene Deckard (Pima County Wastewater Management Department) at (520) 740-6544 to coordinate this matter. We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents. The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter. For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above mentioned comments, please contact me. Sincerely, Dickie Fernández, E.I.T. Telephone: (520) 740-6947 Copy: Project |
| 08/14/2006 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: King Parcel - Record of Survey S06-149 Record of Survey (1st Review) TRANSMITTAL DATE: August 14, 2006 DUE DATE: August 03, 2006 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. D.S. 2-03.11.0, permits a maximum of one year from the date of application to obtain approval of a Record of Survey. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey is August 02, 2007. 2. Provide the proposed name for the Land Survey Exception. (D.S. 2-03.11.7.F.2) 3. This project has been assigned Land Survey Exception case number S06-149. Please note the subdivision case number in the lower right corner of each sheet of the record of survey. (D.S. 2-03.11.8.B.1) 4. List as a general note: "Existing zoning is R-2" (D.S. 2-03.11.8.B.2) 5. Revise the Certificate of Survey to match D.S. 2-03.11.9.A. 6. Revise the Dedication to match D.S. 2-03.11.9.B. 7. The following information regarding the existing public right-of-way will be provided: recordation data, type and dimensioned width of paving, curbs, curb cuts and sidewalks. (D.S. 2-03.11.11.B) 8. Provide information on existing utilities per D.S. 2-03.11.11.C 9. All proposed easement recordation information (docket and page) must be included on the plan prior to final approval. (D.S. 2-03.11.12.A) 10. Provide a 1'-0" No-Access easement between lots 2 & 3 starting at the east side of the Proposed 15'-0" Ingress, Egress & Utility easement heading east to the east property line. If you have any questions about this transmittal, please call Steve Shields, (520) 791-5608 ext. 1180 C:\planning\cdrc\record of survey\S06-149ros.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, tentative plat, final plat, CC&R's and additional requested documents. |
| 08/14/2006 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: August 14, 2006 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov CC: SUBJECT: S06-149 King Parcel: Record of Survey Review Staff has no comments. |
| 08/14/2006 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF URBAN PLANNING & DESIGN Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S06-149 King Parcel 08/10/06 () Tentative Plat () Development Plan () Landscape Plan () Revised Plan/Plat () Board of Adjustment (XXXX) Other – Record of Survey CROSS REFERENCE: NEIGHBORHOOD PLAN: North Stone GATEWAY/SCENIC ROUTE: COMMENTS DUE BY: 08/03/06 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: () No Annexation or Rezoning Conditions, Not an RCP - No Comment (XXXX) Proposal Complies with Annexation or Rezoning Conditions () RCP Proposal Complies With Plan Policies () See Additional Comments Attached () No Additional Comments - Complies With Planning Comments Submitted on: () Resubmittal Required: () Tentative Plat () Development Plan () Landscape Plan () Other REVIEWER: D. Estolano 791-4505 DATE: 07/17/06 |
| 08/23/2006 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES August 23, 2006 Don Burke Lee Moran Development LLC 698 East Wetmore Road, Suite 310 Tucson, Arizona 85705 Subject: S06-149 King Parcel Record of Survey Dear Don: Your submittal of July 7, 2006, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLUELINES MUST BE FOLDED 6 Copies Revised Record of Survey (Traffic, Addressing, Engineering, Zoning, Wastewater, DSD), Should you have any questions, please call me at 791-5608, ext 1179. Sincerely, Patricia Y. Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 382-0032 |
| 08/23/2006 | PATRICIA GEHLEN | ZONING-RECORDATION | REVIEW | Needs Review |