Plan Number: S06-149
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: RECORD OF SURVEY REVIEW

Plan Number - S06-149
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/10/2006 JOE LINVILLE LANDSCAPE REVIEW Approved
07/12/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied July 12, 2006
ACTIVITY NUMBER: S06-149
PROJECT NAME: King Parcel
PROJECT ADDRESS: 207 W King Road
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Record of Survey; therefore a revised Record of Survey is required for resubmittal.

The following items must be revised or added to the Record of Survey.

1. Show and label as to size (i.e. 20x110) both existing and future SVTs (DS 2-02.2.1.A.10). If the existing and future SVTs are coincident, label it as both existing and future.

2. Locate driveways on adjacent properties to verify compliance with driveway spacing requirements of Tucson City Code Chapter 25. A minimum 12' offset needs to be provided between curb cuts.

If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
07/13/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* Four lot split for individual homes. Service approved for APC curbside service. APC's will be required to be placed and removed from the curbside collection area on the day of service.
07/17/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-149
KING PARCEL
07/18/2006 JIM EGAN COT NON-DSD FIRE Approved Fire Sprinklers to be provided for lots 2, 3, and 4.
07/18/2006 RICHARD WILLIAMSON TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved WATER SUPPLY
Tucson Water has been designated by the State of Arizona, Department of Water Resources, as having an assured water supply. This does not mean that water service is currently available to the proposed development. This development lies within the exterior boundary of Tucson Water's planned 50-year service area. Therefore, water supply is assured.

WATER SERVICE
The approval of water meter applications is subject to the availability of water service at the time an application is made. The developer shall be required to submit a water master plan identifying but not limited to:

Water Use
Fire Flow Requirements
Offsite / Onsite Water Facilities
Loops and Proposed Connection Points to Existing Water System
Easements / Common Areas

Any specific area plan fees, protected main / facility fees and / or other needed facilities' cost are to be paid by the developer.

If the existing water system is not capable of meeting the requirements of the proposed development, the developer shall be fiscally responsible for modifying/enhancing the existing water system to meet those needs.

This letter shall be null and void one year from the date of issuance.

Issuance of this letter is not to be construed as agency approval of a water plan or as containing construction review comments relative to conflicts with existing water lines and the proposed development.

If you have any questions, please call New Development at 791-4718.

Sincerely,



Richard S. Williamson, P.E.
Manager, New Development
RW:bjh
07/20/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved ESTIMATED DAILY TRIPS - 38
07/25/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: KING PARCEL RECORD OF SURVEY
REVIEW

S06-149





Tucson Electric Power Company has reviewed and approved the record of
survey review submitted July 7, 2006. It appears that there could
possibly be conflicts with the existing facilities within the boundaries
of this proposed development. Relocation costs are billable to the
customer.



Enclosed is a copy of a TEP facilities map showing the approximate
location of the existing facilities. Secondary and secondary/service
poles may be on property to the East, no way to tell without property
corners identified. Also, note underground service from pole 193 to
meter post.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Tucson
Electric Power Company

Attn:
Ms. Mary Boice

New
Business Project Manager

P. O.
Box 711 (DB-101)

Tucson,
AZ 85702


520-917-8732



Please call the area Designer Warren McElyea at (520) 918-8268, should
you have any questions.






Sincerely,








Kathy Clark for Denise Tellez


Scheduling Coordinator


Design/Build

kc

Enclosures

cc: P. Gehlen, City of Tucson

W. McElyea, Tucson Electric Power





Kathy Clark
Scheduling Coordinator
Design/Build
520-918-8271
kclark@tep.com
07/27/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-149 KING PARCEL/RECORD OF SURVEY
DATE: 7/26/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


Delete all street directions on Location Map.

Change 44/63 to 41/63 on Location Map.

Spell out all street suffixes except on Location Map.

Delete 207 W. King Rd everywhere.

Delete all tax codes and owner information on all adjacent parcels.



es
07/31/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: July 31, 2006

SUBJECT: Engineering review of the King Parcel, Record of Survey. The activity number is S06-149.

SUMMARY: The Record of Survey was received by Engineering on July 7th, 2006. Engineering has reviewed the received items and does not recommend approval of the Record of Survey.

RESUBMITTAL REQUIRED: RECORD OF SURVEY


RECORD OF SURVEY COMMENTS

1. Place the Record of Survey case number in the lower right hand corner of sheet one. DS 2-0311.8.B.1.

2. Under the "DEDICATION" section it is recommended to remove the fourth paragraph because it is redundant with the second paragraph. Revise appropriately. DS 2-03.11.9.B.

3. At least one (1) corner of the property will be tied by course and distance to a section corner, a quarter section corner, or an established City survey monument. The plan must include a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. Revise survey appropriately. DS 2-03.11.10.A.

4. Show easements of record on the plan, with recordation information, locations, widths, and purposes shall be included. DS 2-03.11.11A.

5. Provide the recordation data (book and page) for King Road. DS 2-03.11.11.B.

6. Dimension from the street centerline of King Road to the existing curb and the proposed sidewalk. DS 2-03.11.11.B.

7. Provide the sidewalk width located along King Road.

8. Provide a copy of the ROW permit for the proposed sidewalks.

9.
08/01/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S06-149 King Parcel: Record of Survey Review - No comment.
08/03/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied August 1, 2006

TO: Don Burke
Lee Moran Development, LLC

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: King Parcel
Tentative Plat – 1st Submittal
S06-149

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

ALL SHEETS. Add the project number, S06-149, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates.

SHEET 1. Add the following General Note

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.

SHEET 1. Add the following General Note

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

Show the length, size and slope for all newly proposed sewers.

Show the six-digit Pima County manhole number for all existing public manholes that may be located on W King Road.

Show the size and Pima County plan number for the existing public sewer(s) that may be located on W King Road.

Please be aware that if this project plans for the proposed sewers to be shared among the lots on this project, this project will require a Joint Use And Maintenance Agreement. Please contact Ilene Deckard (Pima County Wastewater Management Department) at (520) 740-6544 to coordinate this matter.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
08/14/2006 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: King Parcel - Record of Survey
S06-149
Record of Survey (1st Review)

TRANSMITTAL DATE: August 14, 2006

DUE DATE: August 03, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. D.S. 2-03.11.0, permits a maximum of one year from the date of application to obtain approval of a Record of Survey. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey is August 02, 2007.

2. Provide the proposed name for the Land Survey Exception. (D.S. 2-03.11.7.F.2)

3. This project has been assigned Land Survey Exception case number S06-149. Please note the subdivision case number in the lower right corner of each sheet of the record of survey. (D.S. 2-03.11.8.B.1)

4. List as a general note: "Existing zoning is R-2" (D.S. 2-03.11.8.B.2)

5. Revise the Certificate of Survey to match D.S. 2-03.11.9.A.

6. Revise the Dedication to match D.S. 2-03.11.9.B.

7. The following information regarding the existing public right-of-way will be provided: recordation data, type and dimensioned width of paving, curbs, curb cuts and sidewalks. (D.S. 2-03.11.11.B)

8. Provide information on existing utilities per D.S. 2-03.11.11.C

9. All proposed easement recordation information (docket and page) must be included on the plan prior to final approval. (D.S. 2-03.11.12.A)

10. Provide a 1'-0" No-Access easement between lots 2 & 3 starting at the east side of the Proposed 15'-0" Ingress, Egress & Utility easement heading east to the east property line.


If you have any questions about this transmittal, please call Steve Shields, (520) 791-5608 ext. 1180

C:\planning\cdrc\record of survey\S06-149ros.doc


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, tentative plat, final plat, CC&R's and additional requested documents.
08/14/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: August 14, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: S06-149 King Parcel: Record of Survey Review

Staff has no comments.
08/14/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-149 King Parcel 08/10/06

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: North Stone

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 08/03/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 07/17/06
08/23/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 23, 2006

Don Burke
Lee Moran Development LLC
698 East Wetmore Road, Suite 310
Tucson, Arizona 85705

Subject: S06-149 King Parcel Record of Survey

Dear Don:

Your submittal of July 7, 2006, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Record of Survey (Traffic, Addressing, Engineering, Zoning, Wastewater, DSD),







Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 382-0032
08/23/2006 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Needs Review