Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: S06-138
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S06-138
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approved TO: Patricia Gehlen; CDRC Coordinator
FOR: FSSB Engineering
SUBJECT: Wilmot/I-10 Commercial Center Tentative Plat re-submittal Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S06-138

SUMMARY: The revised Tentative Plat/Development Plan, Landscape documents, and rezoning conditions were reviewed. Development Services Department Engineering Division recommends approval of the Tentative Plat. The Drainage Report was reviewed for Tentative Plat purposes only. The grading plan review will show further information regarding how water harvesting is utilized, require further geometrics for weir outlet and sediment trap for basin, and provide Geotechnical Report additional percolation test results. If you have questions or would like to set up a meeting, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
01/17/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 17, 2007

Michael John Baker, P.E.
Floerchinger, Sadler, Steele, Baker Inc.
326 South Covent
Tucson, AZ 85701

Subject: S06-138 Wilmot & I-10 Commercial Center Tentative Plat

Dear Mike:

Your submittal of November 16, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

11 Copies Revised Tentative Plat (ESD, TEP, DUPD, Wastewater, Traffic, Real Estate, ADOT, Landscape, Zoning, OCSD, DSD)

5 Copies Revised Landscape Plan (Landscape, Zoning, DUPD, OCSD, DSD)

2 Copies Title Report (Real Estate, DSD)

3 Copies Traffic Impact Analysis (ADOT, Traffic, DSD)

THE ABOVE LISTED RESUBMITTAL REQUIREMENTS ARE FOR CONTINUATION OF THIS TENTATIVE PLAT. IF A BLOCK PLAT IS SUBMITTED, IT WILL BE CONSIDERED A NEW SUBMITTAL AND MUST GO TO ALL REVIEW AGENCIES. A FULL SUBMITTAL WILL BE REQUIRED. THE OFFICE OF CONSERVATION AND SUSTAINABLE DEVELOPMENT (OCSD) HAS BEEN ADDED TO THIS REVIEW DUE TO LANDSCAPE COMMENTS. IF A BLOCK PLAT IS SUBMITTED, PLEASE INCLUDE AN EXTRA COPY OF THE PLAT AND LANDSCAPE PLAN FOR OCSD.


Should you have any questions, please call me at 791-5608 ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 628-1375
11/16/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/28/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Denied Here's a few comments From Regional Traffic;



* need to show access control on plat, if not added the plan
will be incomplete

* any sound walls along I-10 frontage road will be installed by
the developer

* a copy of the TIA will be needed and with proper mitigation,
before any approval from ADOT

* does the sight distance triangle, on the frontage road, meet
current ADOT standards

* because of the distance from the frontage road to the
entrance/dedicated street, the only movement SB will be right in & right
out

* a raised median will be installed along the frontage of the
project on Wilmot



Thank you. TM.
12/04/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied December 4, 2006

TO: Michael John Baker, P.E.
Floerchinger Sadler Steel Baker, Inc.

THRU: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department

FROM: Chandubhai C. Patel, P.E.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Wilmot & I-10 Commercial Center
Tentative Plat – 2nd Submittal
S06-138

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 2. A 330 feet long 8-inch private sewer is proposed in a public street. This is not permissible. This sewer should be changed to public sewer and labeled accordingly.

2. SHEET 1. In light of the above comment, add THE following to the General Note # 10:

THE ONSITE PUBLIC SEWER WILL BE DESIGNED AND CONSTRUCTED TO PIMA COUNTY WMD STANDARDS AND MUST BE ACCEPTED AND RELEASED FOR SERVICE BY PCWMD PRIOR TO THE ISSUANCE OF SEWER CONNECTION PERMITS.

SHEET 2. Label the two new manholes in the public street as PUBLIC manholes.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

5. SHEET 2. The new manholes shown on this sheet need to be numbered. They should be numbered sequentially.

The next submittal of this project will be the 3RD submittal. A check for the review fee of this submittal in the amount of $78.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above comments, please do not hesitate to contact me.

Sincerely,



Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: Project File
12/05/2006 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S06-138
Wilmot & I-10 Commercial Center
Tentative Plat/Development Resubmittal

TRANSMITTAL DATE: November 30, 2006

DUE DATE: December 15, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Previous Comment not addressed - Based on rezoning condition #1, the title block should indicate that this is a "tentative plat/development plan".
DS 2-03.2.4.U

2. If it is anticipated that the proposed building for lot 3 is to be no greater than eighteen feet per your response, add proposed maximum height for that lot that would meet the required MS&R setback on the building footprint. This will limit height of proposed structures on future development plan.

3. The areas proposed on the tentative plat for development may only use walls no greater than thirty (30) inches but proposed projects for block 1-3 will most likely utilize walls that are higher than thirty inches abutting the SH zones. Future development plan will be required to provide details of walls that meet the rezoning condition 14

4. Previous Comment - Provide exterior elevation drawings for the proposed buildings to demonstrate compliance with rezoning condition 15. DS 2-05.2.4.U

Please add note on tentative plat/development plan that dimensioned color exterior elevations will be provided at time of individual development plan submittal for each lot.

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised tentative plat/development plan.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197.

KAA S:\zoning review\karol\planning\cdrc\tentativeplat\S06-138tpr.doc
12/06/2006 JCLARK3 ENV SVCS REVIEW Denied * Project was approved initially conditionally. ES stated that the enclosure required doors and sidewall protection. The review notes and the drawings did not address the request.
12/08/2006 JOE LINVILLE LANDSCAPE REVIEW Denied The Landscape Section does not recommend approval of the plans at this time due to inconsistencies with adopted codes and standards. The plan was reviewed for compliance with the Land Use Code (LUC), Development Standards (DS) and other applicable standards and guidelines referred to in the comments. Revise the plans as necessary to comply.

1) Provide documentation of coordination with the Office of Conservation and Sustainable Development related to the design of the open space and the detention basin. C9-01-05

2) Revise the development plan and landscape plan to clarify compliance with the screening requirements for loading areas. The loading zone at the restaurant location must screened from all adjacent streets per LUC Table 3.7.2.-I.

3) A vehicular use area must be provided with post barricades or wheel stop curbing designed to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings per DS 3-05.2.3.C.
Revise the plans as necessary to indicate appropriate barriers along the perimeter oif all paved areas. See the parking access lane at Blocks 2 & 3.

Resubmittal of the tentative plat/development plan and landscape plans is required.
12/11/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-138 WILMOT & I-10 COMMERCIAL CTR./REVISED TENTATIVE PLAT
DATE: 12/11/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***


ES
12/11/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied S06-138 Wilmot & I-10 Commercial Center: Resubmittal - CDRC - Tentative Plat Review - Request consideration for the following:

1. No title report provided.
2. Deny private sewers mains within the proposed Right-of-Way.
12/13/2006 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR# 164648 December 13, 2006

Dear : Mr. Baker
SUBJECT: Wilmot & I-10 Commercial Center
S06-138

Tucson Electric Power Company has reviewed and disapproved the development plan submitted November 16, 2006 It appears that there are conflicts with the existing facilities within the boundaries of this proposed development. Please show facilities on the plan. A facilities map is attached for reference. The pole on Wilmot Rd, located on the S/W corner of Wilmot and the new road appear to be in conflict with the new road. There is an additional pole that is not indicated on the plan. This pole is located approximately 185’ north of the previously discussed pole (This pole may be in conflct as well). There is also an underground service that is not indicated on the plan. The UG service goes from the missing pole, N/W to a sign located somewhere in lot 3, also not shown on the plan. There are also poles located on the north edge of this property along the frontage road that are not indicated on the plan. Please see the attached 100 scale map for reference.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Todd Stocksdale at (520) 917-8715, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: T. Stocksdale-TEP
P. Gehlen, City of Tucson (E-Mail)
12/15/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied December 15, 2006
ACTIVITY NUMBER: S06-138
PROJECT NAME: Wilmot & I-10 Commercial Ctr.
PROJECT ADDRESS: 7710 S Wilmot Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Tentative Plat; therefore a revised Tentative Plat

The following items must be revised or added to the plat.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Provide the Traffic Impact Analysis as required per Rezoning Condition C9-01-05 (note 6 on the Tentative Plat). If the Tentative Plat is re-platted as a Block Plat then this rezoning condition for a TIA will be postponed and noted as a condition for future Development Plan/Tentative Plats for these proposed lots.



If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
12/15/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-138 Wilmot & I-10 Comm. Ctr. 12/15/06

() Revised Tentative Plat
( ) Development Plan
() Revised Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-01-05; C9-06-26 - west of S06-138

NEIGHBORHOOD PLAN: Rincon Southeast Subreg. Plan

GATEWAY ROUTE: N/A

COMMENTS DUE BY: 12/15/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: J. Hershenhorn 791-4505 DATE: 12/15/06
Wilmot and I-10 Commercial Center
S06-138


Regarding rezoning condition 1.d and pedestrian crosswalks, the intent is to provide a continuous, safe, well-defined pedestrian system along the public street. Please provide crosswalks, aligned in an east-west direction, connecting the sidewalk segments on the northern side of the public street (to each other), so that they form a continuous walking path along the northern edge of the public street. Similarly, please provide crosswalks, aligned in an east-west direction, connecting the sidewalk segments on the southern side of the street, so that they form a continuous walking path along the southern side of the street. Please call if you would clarification on the location of these crosswalks.

Regarding rezoning condition 15, please provide a general note on the plat stating that colored building elevations will be provided with the development plan submittal for each lot or block.

To clearly define the edge of the phased project areas, please provide post barricades or wheel stop curbing at the edges of the paved areas adjacent to blocks 2 and 3.DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application