Plan Number: S06-125
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S06-125
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/21/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied May 18, 2007

To: Ron Peetz
AmericaBuilt Development, Inc.


Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Rincon Knolls
Lots 1-500 and Common Areas “A”-“E”
Tentative Plat – 3rd Submittal
S06-125

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The tentative plat for this project cannot be approved until a copy of this letter has been received by this office.
The letter in file is outdated.

Sheet 1: The existing sewer line and manhole are missing in the legend.

Sheet 3: Ex. MH #43625-23 does not point to a manhole.

Sheet 4: Sewer directional flow arrows are missing near MH 4 and MH 3.

Sheet 4: The manhole #’s appear to go in the wrong direction on Cienega Knolls Loop. Please revise.

Sheet 4: The force main pipe size is not called out.

Sheet 5: The sewer directional flow arrows on the force main are missing.

Sheet 6: Refer to the specific sewer plans for the proposed lift station and explain the rim elevation of MH WW4 being lower then the invert elevation.

Sheet 8: The manhole sequencing appears to be off because the numbers should be going down as the sewer moves downstream.

Sheet 9: The manhole sequencing along Quail Canyon is not correct.

Sheet 11: The manhole sequencing is not correct along Adam Camp Trail.

Sheet 13: The manholes and label information are missing on Tortoise Pointe Drive near the bottom of page. Also the manhole and sewer line segment tables are missing.

Sheet 14: Manholes on Rincon Knolls Loop near top of page are not labeled.

Sheet 14: The sewer directional flow arrows are missing.

Sheet 15: The sewer directional flow arrows are missing.

Sheet 17: Extend the sewer line to front Lot 399


This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

For the 3rd submittal only $78.00 was collected but 18 pages of wastewater plans were reviewed. Therefore, an additional $624.00 are due for the 3rd submittal. The next submittal of this project will be the (4th) submittal. A check for the review fee of this submittal in the amount of $1092.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. This amount will cover the combined amount due for the 3rd and 4th submittals. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me .
05/23/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-125 RINCON KNOLLS/REVISED TENTATIVE PLAT
DATE: 5/23/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: Approved with the following condition:

Add suffix of Way to Mary Ann Cleaveland on sheet 3 of Final Plat.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***


es
05/24/2007 JIM EGAN COT NON-DSD FIRE Approved
06/01/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond The Landscape Section approves the tentative plat subject to the following conditions:

1) The NUOS Boundaries are to be shown on the final plat.
LUC 3.8.6.4

2) The project is subject to the provisions of the Watercourse, Amenities, Safety, and Habitat Ordinance, a separate application and review and approval is required prior to tentative plat approval. TCC 23-12.

3) Incorporate plants proposed for revegetation on Exhibit 2 (WASH) into the landscape plans for the project.
06/06/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond S06-125 Rincon Knolls: Resubmittal - CDRC - Tentative Plat Review - Per Sht. 3 of 34, request clarification concerning the two drainage pipes and if the responsibility for maintenance will be public or private.
06/06/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Ref.: My 6/6/07 E-Mail, Same Subject

S06-125 Rincon Knolls: Resubmittal - CDRC - Tentative Plat Review - Per above reference, request previous comments "Per Sht. 3 of 34, request clarification concerning the two drainage pipes and if the responsibility for maintenance will be public or private" be changed to "Per Sht. 3 of 34, request an agreement for the maintenance of the two drainage pipes be established during the P.I.A. process ."

-
06/06/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
06/08/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN
AND THE OFFICE OF CONSERVATION AND SUSTAINABLE DEVELOPMENT
Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-125 Rincon Knolls Tent. Plat 06/07/07

(X) Tentative Plat
() Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-06-07 Wycozona – Mary Ann Cleveland Way

MASTER PLAN: Houghton Area Master Plan (H.A.M.P.)
GATEWAY ROUTE: No

COMMENTS DUE BY: June 6, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY BOTH COMMUNITY PLANNING & PRESERVATION, AND THE OFFICE OF CONSERVATION AND SUSTAINABLE DEVELOPMENT. STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(X) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(X) Resubmittal Required:
(X) Tentative Plat
() Development Plan
(X) Landscape Plan
(X) Other – Model Elevations and Color Palette
REVIEWER: msp 791-4505 DATE: June 1, 2007
REVIEWER: ap 791-4505 DATE: ____________

A. - Department of Urban Planning and Design (DUPD) Comments
S06-125 – Rincon Knolls – Tentative Plat
June 1, 2007


The applicant acknowledges that the following staff requirements/comments have carried over from the previous reviews and are not in compliance at the time of this review:


Prior to approval from staff, the applicant shall provide documentation to satisfy the following:
Provide documentation that the Pantano River Park corridor (Trail #5), has been approved either on-site, off-site on State Land, or an approval from the Department of Parks and Recreation that satisfies the Pantao River Park requiremens with in lieu fees.

Current submittal does not comply with rezoning condition # 20. Please revise landscape plan, sheet L-1, note 13 to read verbatim the language provided in rezoning condition # 20, which reads as following:

Provide a native canopy tree within ten feet of the front property line on every other lot, on every street within the development.

Landscape plan, sheet 1 of 11, note #9 provides instructions on how to install the required temporary fencing, based on development standards. However, as written note # 9 does not acknowledge rezoning requirements related to the installation of temporary fences. Please revise landscape plan, sheet 1 of 11, note # 9 to read verbatim the language provided on rezoning conditions # 11 & 12. Rezoning conditions # 11 and 12 read as following:

Rezoning Condition # 11
Temporary construction fences shall be installed on the NUOS boundary. Construction fencing shall be installed under the supervision of a registered land surveyor. Grading will not be permitted until the installation of the construction fencing in compliance with the tentative plat, grading plan, and final plat has been verified by a survey prepared by a registered land surveyor.

Rezoning Condition #12
Temporary construction fences and the required NUOS boundary fences shall be installed under the supervision of a registered land surveyor. Upon completion of all required fencing installation, the registered land surveyor shall certify by letter that the physical placement of all required temporary construction fencing has been installed as shown and identified on final plat and grading plan.

4. Prior to tentative plat approval, the Department of Urban Planning & Design (DUPD) requires documentation which establishes that the applicant is in contact with the Department of Development Services (DSD), Zoning Review Section to discuss an agreement on methods by which rezoning condition # 19, 21 and 22 will be tracked for compliance at the time of housing permit issuance.

This submittal indicates you spoke with Loren Makus from the Department of Development Services, Engineering Section. However, DUPD staff requires that you submit documentation, which satisfies DUPD staff comment #4 and verifies you are in contact with the Department of Development Services, Zoning Review Section Supervisor (David Rivera).
06/12/2007 FRODRIG2 COT NON-DSD OCSD Denied The following comments are provided by:
Ann Audrey, City of Tucson, Office of Conservation and Sustainable Development (OCSD)
Review of Submittal #3 for Rincon Knolls, Lots 1-502, COT#S06-125

Regarding sheet details, the following additions and corrections should be made:

All sheets with grading notes, Under note 103, add "per Sht 22"

Sheet 22, Note 1 under Mitigation Structures: Add the following language, based on 12-7-06 meeting between AmericaBuilt and OCSD: “If initial wall construction is not sufficient to keep tortoises from escaping the wildlife area, a 1.5- to 2. 5-foot fine-meshed fence with a lipped top or 6-inch wide overhang pointing in the direction of the tortoise side should be installed on the wildlife side of the rock wall.”

Sheet 22, Note 2 under Mitigation Structures: revise wording as follows: “A bridge shall be constructed on Arnold Ranch Road allowing tortoise and other wildlife free access under the bridge.”

Sheet 22, Detail 44: Revise the drawing to show vegetation planted on the non-tortoise side of this wall (rather then the currently shown tortoise side of the wall). Vegetation on the non-tortoise side of the wall will deter people from climbing over the wall into the tortoise area. On the tortoise side of the wall, do not place vegetation within 10 feet of the wall since as vegetation grows and branches out tortoise could potentially climb this vegetation to get over the wall.

Sheets 4, 8, 13, 14, 15, 16, Add numbered note under Streets heading as follows: “Tortoise Crossing Sign per detail 45 Sht 22” and show locations on the sheet where signs are to be installed

Sheet 5, 11, 12, 14, 15, 16, Add numbered note under Streets heading as follows: “Rock barrier wall per detail 44 Sht 22” and show locations on the sheets where rock barrier walls are to be installed

Sheet 13, Add numbered note under Drainage heading as follows: “Wildlife crossing box culvert per detains 41, 42, 43, Sht 22” and show location on the sheet where box culvert is to be installed

Per note 3 from the 12-7-06 meeting between AmericaBuilt and OCSD, “A wall-like obstruction……should be constructed along any location where tortoise could potentially stray from protected areas into adjacent areas.” In addition to those locations already noted of the plans for construction of rock barrier walls, add rock barrier walls or fine-meshed fencing for tortoise and other wildlife at all locations where existing barriers, retaining walls or residential walls are not sufficient to deter tortoise entry (minimum of 18-inch vertical face). Fine meshed fencing should have a small enough mesh to prevent snakes from partially going though the mesh and getting stuck (for example, chicken wire is not fine enough mesh). Based on review of the current plans, locations where tortoise appear to be able to access streets include the following locations:
Sheet 4, south side of Rincon Knolls Loop
Sheet 6, east side of Rocking Lazy A Ranch Place, and the west side of that cul de sac
Sheet 8, east side of Rincon Knolls Loop north of Page Canyon Lane
Sheet 9, outside curve where Paige Canyon Lane becomes Pantano View Drive
Sheet 10, Adam Camp Trail cul de sac
Sheet 12, portions of Alessi Peak Place cul de sac
Sheet 13, east and west side of Rincon Knolls Loop
Sheet 16, on the approach to the conarch bridge as needed
Sheet 17, Diane Ranch Road cul de sac and southeast side, and north side of Megan Ridge Lane
Sheet 18, Lauren Canyon Place cul de sac
06/21/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall Senior Planner

PROJECT: S06-125
Rincon Knolls Residential Cluster Project Subdivision
Tentative Plat, 3rd review

TRANSMITTAL DATE: June 21, 2007
DUE DATE: June 6, 2007

COMMENTS: This review is segmented in plat, RCP, rezoning, and overlay comments.

TENTATIVE PLAT REVIEW COMMENTS

1. Per DS 2-03.2.4.E, I see the phasing notes provided on sheets 31-34, thank you. Please provide a density per acre calculation for each phase - cumulatively. Please clarify what is included in the "total developed area" - roads, building footprints?

2. Per DS 2-03.2.4.J, I acknowledge the response that the access agreement from the State of Arizona, for the Mary Ann Cleveland Way area is being sought, thank you. This comment will remain to remind me to check for such documentation.

RCP REVIEW COMMENTS
3. with regards to building setbacks:
A) in detail 9, list 19' garage setback is MINIMUM measured from back of sidewalk
B) in detail 9, add note 18' garage setback must be provided on site (to property line).
C) In detail 10, I apologize for my mistake in referring to Rincon Knolls Loop as a Major Streets and Routes in my last review. Please remove the MSR note and instead, just indicate ADT is greater than 1000
D) In detail 10, the building setback from the Rincon Knolls Loop side is the greater of 21' or the height of the exterior building wall, measured from THE BACK OF THE FUTURE/CURRENT CURB (not travel lane as noted), AND NEVER LESS THAN 3' FROM PROPERTY LINE (the width of the right of way to property line from curb is greater than 21' in this case) Please provide such notes on the detail.
E) In detail 10, remove reference to the word "VARIES" - our rezoning condition note is suffice to address varying garage setbacks.
F) In detail 10, add note 18' garage setback must be provided on site (to property line)
G) In detail 11, show the SUBDIVISION BOUNDARY line (for reference to rear yard setback listed as the greater of 10' or ¾ of the height of the exterior building wall)
H) In detail 11, remove reference to word "VARIES" - our rezoning condition note is suffice to address varying garage setbacks
I) In detail 11, add note 18' garage setback must be provided on site (to property line)
J) In detail 12, remove reference to word "VARIES" - our rezoning condition note is suffice to address varying garage setbacks
K) In detail 12, add note 18' garage setback must be provided on site (to property line)
L) In detail 13, remove reference to word "VARIES" - our rezoning condition note is suffice to address varying garage setbacks
M) In detail 13, add note 18' garage setback must be provided on site (to property line)

4. Street cross sections 3 and 4 (p 19) appear to match, why listed for separate streets?

5. On sheet 8, please show the cross-section detail reference for Rincon Knolls Road.

6. Please see engineering for any references to the street requirements for existing Millicent Trail. call out sidewalks on both sides for Millicent Trail detail.

REZONING REVIEW COMMENTS:
Per Rezoning case C9-06-07, please address the following:

7. submit a separate response letter explaining how conditions of rezoning will be met.
RESPONSE: Rezoning condition received reviewed, thank you. Please address:
A) Please add common area F (desert park) information to sheet 31
B) Some of the print size in the Common Area column on page 31 is less than 12 pt and is to small for microfilming - enlarge at least to 12 point.
C) Conditions 23, 25 and 26 with regards to walls will be examined with the grading plans, understood.

GENERAL NOTES/DETAILS REVIEW COMMENTS

8. On sheet 2, please correct note 1 to say current zoning is RH, proposed zoning is R-1.

9. On the lots with fire easements, please specify if they have curbing, asphaltic surfacing and revise the site coverage calculation to include the fire lanes.

10. On the lots with fire easements, it is in question whether these lots are buildable. To ensure buildable lots are created - please provide the maximum square footage building footprint - dimensioned - on each lot, showing setbacks. In addition, access to the lots should be confirmed by Engineering and Fire.

11. Hillside Overlay zone comments are made on a separate submittal.

12. Depending upon responses provided, further review comments may be forthcoming.
Contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156 if you have questions.

C:\planning\cdrc\tentativeplat\S06-125 rincon knolls 3.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, CC&R's and additional requested documents.
07/09/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied DATE: July 06, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: S06-125 Rincon Knolls(5-8-07)

Denied. The plat must include a note addressing the in-lieu contribution for the Pantano Riverpark. The note must address the amount of the contribution and the timing of payment. The wording of the note must be approved by both the city and county parks departments.
07/19/2007 LOREN MAKUS ENGINEERING REVIEW Approv-Cond July 19, 2007
To: Patricia Gehlen, CDRC/Zoning Manager
From: Loren Makus, Senior Engineering Associate
Re: S06-125 Rincon Knolls, Tentative Plat (Third Review)

Resubmittal Required: None,

The Tentative Plat and Drainage Report have been reviewed by the Engineering Division. We recommend approval of the Tentatitive Plat be approved subject to the following condition:

Tentative Plat Approval Condition:
1. Clearly indicate the end of the Public Right-of-Way and the beginning of the Private street at the intersection of Millicent Trail and Rincon Knolls Loop.

I can be reached at loren.makus@tucsonaz.gov or at 520.837-4927.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
07/25/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 25, 2007

Ron Peetz.
America Built Development Inc.
5255 Williams Circle Suite 6000W
Tucson, AZ 85711

Subject: S06-125 Rincon Knolls Tentative Plat

Dear Ron:

Your submittal of May 8, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

8 Copies Revised Tentative Plat (OCSD, Engineering, DUPD, Wastewater, Landscape, Parks and Recreation, Zoning, DSD)

7 Copies Revised Landscape Plan (OSD, Landscape, DUPD, Parks and Recreation, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plans (Landscape, DSD)


PRIOR TO RESUBMITTAL OF THIS TENTATIVE PLAT, A WRITTEN REQUEST FOR A REVIEW EXTENSION MUST BE SUBMITTED TO AND APPROVED BY THE CDRC OFFICE.






Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 790-2399