Plan Number: S06-097
Parcel: Unknown

Address:
3808 N 1ST AV

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S06-097
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/27/2006 JIM EGAN COT NON-DSD FIRE Approved Fire sprinklers will be required.
05/02/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-097
TandT ENGINEERING LLC.
THE LOFTS AT VILLA SAVONNA

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by e-mail, and delete or destroy all copies plus attachments.
05/05/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: THE LOFTS AT VILLA SAVONNA
S06-097

Tucson Electric Power Company has reviewed and approved the development
plan submitted April 26, 2006.

Enclosed is a copy of a TEP facilities map showing the approximate
location of the existing facilities. There may be a conflict with the
overhead service from pole #119 to building and secondary/service pole
#125 with overhead services. Any relocation of TEP facilities will be
billable to the developer.

In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:

Ms. Mary Boice, Project Manager
Design/Build - DB 101
Tucson Electric Power Company
P. O. Box 711
Tucson, AZ 85702
(520) 917-8732

Please call the area Designer, Warren McElyea at 918-8268, should you
have any technical questions. My telephone number is 918-8297.


Sincerely,



Denise Tellez
Scheduling Coordinator
Design/Build
dt
Enclosures
cc: P. Gehlen/F. Rodriguez, City of Tucson (by e-mail)


Denise Tellez
918-8297 DB102
05/10/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* All lots have street side frontage. Approved for APC curbside service off PAAL.
05/11/2006 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond May 10, 2006

TO: Tom Guido, P.E.
T and T Engineering, LLC

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: The Lofts at Villa Savonna
Tentative Plat – 1st Submittal
S06-097

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

ALL SHEETS. Add the project number, S06-097, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates.

Subject to the above required revisions, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative plat/final plat/development plan.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
05/19/2006 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1) The calculations for landscape border trees indicate that 5 trees are required, 6 provided along First Ave. (MS&R) but only 4 are shown on the drawing. Revise plan to meet required number of landscape border trees.
DS 2-06.3.4.D.1
LUC 3.7.2.4

2) Dimension the length and width of landscape borders on the landscape plan per DS 2-07.2.2.A.2.f.

3) Indicate square footage of all landscaped areas and provide a calculation of the percentage of vegetative coverage on the landscape plan per DS 2-07.2.2.2.g. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting.
LUC 3.7.2.4.A.5
DS 2-06.3.4.D.2

4) Identify on the plans the native plant preservation methodology (the Plant Inventory Methodology) used to comply with the regulations.
LUC 3.8.6.1

5) Identify and locate on the landscape and native plant preservation plans all utility easements and facilities. DS 2-07.2.2.E

6) Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Add a calculation of the required number of canopy trees per DS 2-07.2.2.A.2.c. Note: In areas where a required landscape border falls within the vehicular use area, up to 50% of the canopy trees may be counted towards both the minimum parking lot canopy tree requirement and the landscape border canopy tree requirement per LUC 3.7.2.3.b

7) Structures higher than thirty (30) inches must be located outside of the sight visibility triangles. The proposed 6-foot high screen wall may not extend into the sight visibility triangle (SVT). Revise plan to show the extent of the wall in relationship to the SVT.
DS 3-01.5.1.A.1

8) Add the subdivision case number (S06-097) to the lower right hand corner of all sheets of the Plat, Landscape Plan and NPP Plan.
DS 2-03.2.2.B.1

9) The required screen wall may not extend into the street landscape border. Provide a detail showing that the wall is constructed outside of required street landscape borders.

10) Show on the landscape plan the ultimate site location of all native plants to be transplanted on site.
DS 2-15.3.4.B.2
05/22/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: May 18, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: S06-097 The Lofts at Villa Savonna:: Tentative Plat Review(4-26-06)


Staff has no comments.
05/23/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-097 THE LOFTS AT VILLA SAVONNA/TENTATIVE PLAT
DATE: 5/22/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Change a resubdivision of lot 7 to a resubdivision of a portion of lot 7 on all Title Blocks.

Correct scale on Location Map.

Spell out all streets suffixes except on Location Map.

Add Court or Place to Villa Savonna.

Please provide Spanish Review for Villa Savonna.



es
05/24/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Estimated daily traffic in 24 hr period - 147
05/24/2006 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: May 23, 2006


RE: Assessor’s Review and Comments Regarding Tentative Plat
S06-097 The Lofts at Villa Savonna T131430 (113-03)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal. Please make the following additions/corrections in the final plat.
Remove shading and stippling.
Add interior bearings for the lot lines, the dimension and bearing for the street centerline.
Add the complete curve data.
Add road information for Pastime Road, Smoot Drive, First Avenue, Tyndall Avenue and Roger Road.
Add adjacent subdivision names or add UNSUBDIVIDED to adjacent areas.
Is the brass cap in HH the Northwest section corner? If so, please label it as such.
If there are any questions, please contact Susan King at 740-4391.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.




Susan King
05/26/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this TP:

1. Show and label as to size (ie 20x110) both existing and future SVTs (DS 2-03.2.4.M). If the existing and future SVTs are coincident, label it as both existing and future. The SVTs at the project access are not labeled as to their size.

2. List the name, ROW width, recordation data, type and dimensioned with of paving, curbs, curb cuts and sidewalks. (DS 2-03.2.3.D) I can find no recordation data for any roadways.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
05/30/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: May 30th, 2006

SUBJECT: Engineering review of the Lofts at Villa Savonna Tentative Plat. The activity number is S06-097.

SUMMARY: The Tentative Plat and Drainage Report were received by Engineering on April 26th, 2006. Engineering has reviewed the received items and does not recommend approval of the Tentative Plat or the Drainage Report.

RESUBMITTAL REQUIRED: TENTATIVE PLAT, DRAINAGE REPORT

SUMBITTAL REQUIRED: GEOTECHINICAL REPORT (Soil's Report)


GENERAL COMMENTS

1. The Drainage Report was reviewed for Tentative Plat purposes only.

2. Please include the Assurance Package with the Final Plat submittal. This package must include the original Third Party Trust, the original Amendment to Trust, a copy of the Trust Agreement, a copy of the Deed, and a Title Report.

3. Include a copy of the CC&Rs with the Final Plat submittal. The specific maintenance notes specified in the Standards Manual for Drainage Design and Floodplain Management, SMDDFM, 14.3.2 must be included on the Final Plat or in the CC&Rs. The term "owner" in the maintenance notes is to be replaced with "Homeowners Association".

4. Please provide a copy of the boundary closure calculations with the Final Plat submittal.

5. A Grading Plan and Permit will be required. Proposed grading in excess of 5,000 yards is designated "engineered grading" and a soils engineering report is required with the Grading Plan submittal. Development Standard 11-01.4.C. The Soils Report must also address the requirements detailed in the Standards Manual for Drainage Design and Floodplain Management, SMDDFM, 14.2.6.

6. Proposed fills in excess of two feet above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property require the procedure outlined in Development Standard 11-01.8.0. This process must be complete prior to Grading Plan approval.

7. Proposed developments disturbing areas exceeding 1 acre are subject to AzDES requirements.

8. All proposed easements must be shown in a surveyable manner on the Final Plat.


The next submittal must address the following items:

TENTATIVE PLAT

1. Provide the subdivision case number S06-097 in the lower right hand corner of each sheet. DS 2-03.2.2.B.1.

2. The benchmark symbol shown on 1st Avenue and Roger Road is shown in the legend as a "new brass cap survey monument." Is this correct? Typically the bench mark locations in an arterial street/road are a found monument. Please clarify and revise the plat appropriately. DS 2-02.2.3.A.

3. It appears the symbols for the survey information in the legend are not consistent with what is shown on the plat view. For example the survey point located in the southwest corner is labeled on the plat view as "found ½ rebar affixed tag LS 36175." The symbol used is described in the legend as "set ½" rebar tagged LS 36715." Please correct the plat appropriately. DS 2-02.2.3.A.

4. Dimension from the street centerline of First Avenue to the existing curb and sidewalk location. DS 2-03.2.3.D.

5. All existing easements will be drawn on the plat, and recordation information, locations, widths, and purposes shall be included. If the easement is not in use and proposed for abandonment, so indicate. Blanket easements should be listed in the notes, together with recordation data and their proposed status. If this requirement is applicable, provide this information on the plat. D.S. 2-03. 2.2.3.C.

6. Conditions on adjacent land affecting the project must be shown on the plat. This includes item such as walls, fences, structures, etc. It appears after reviewing an aerial photo the project may be bound by a wall or fence on the south and/or east side of the project. Clarify in detail in the response letter and revise appropriately on the plat view. DS 2-03.2.3.H.

7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

8. Provide 5' sidewalks along the proposed roadwork for Smoot Drive. DS 3-01.4.0.

9. Show and label as to size (ie 20x110) both existing and future SVTs (DS 2-03.2.4.M). If the existing and future SVTs are coincident, label it as both existing and future. The SVTs at the project access are not labeled as to their size.

10. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. Revise appropriately.

11. The new lot lines for lots 1-25 are difficult to determine from the channels, sidewalks and driveways. It is acknowledged this is a small site where it can be a challenge to clearly provide the required information on the plat. The lot lines must be identifiable on the plat. Revise the plat to clearly indicate the lot lines on each plat. DS 2-03.2.4.A.

12. Provide the curve data for lots 11, 12 and 25. Revise the square footage of each lot appropriately. DS 2-03.2.4.A., DS 2-03.2.4.B.

13. Common area must be clearly defined. It is not clear if the 10' bufferyard 'D' is part of a common area. Each common area must be enclosed with a solid line and appropriately labeled with the correct letter designation. Clarify in the response letter and revise the plat as necessary. DS 2-03.2.4.C.

14. Are the sidewalks and the infrastructure in front of the lots part of common area 'B'? It must be clear on the plat what infrastructure is included in common area 'B'. Clarify on the plat what infrastructure is included in common area 'B'. DS 2-03.2.4.C.

15. Dimension from street centerline to the future curb and sidewalk location. Label appropriately. DS 2-03.2.4.H.

16. Show all proposed easements on the plat. Indicate whether the easement is public or private. Dimension and label appropriately. Ds 2-03.2.4.J.

17. Detail 3 shown on sheet three indicates the property line is 2' from the top of basin. Was the intent to indicate the lot line of common area 'A'? The property/perimeter line of the subdivision is approximately 47' away from the top of bank of the basin. Clarify and revise appropriately. DS 2-03.2.4.A.

18. The proposed basin volume in the drainage report is 2617 cubic feet; on the plat the proposed basin volume is 2626 cubic feet. It is acknowledge it is a very small difference the proposed basin volumes provided in the drainage report and on the plat should match. Revise the documents to be consistent.

19. Security barriers must be provided at the top of all basins with a slope steeper than 4:1 and where a water depth exceeds 2'. Provide a security barrier around the basin. A minimum 42 inch barrier height is required for all basins. Indicate on the plat view and show in the appropriate details on sheet 3. Det/Ret Manual 3.6.2.

20. Show the location, size and indicate the slope of the basin maintenance access ramp on the plat and in the applicable details. The maximum roadway or access ramp slope shall not exceed 15 percent. Alternate means of access will be reviewed by the City Engineer on a case-by-case basis. SMDDFM 2.3.1.6.A.4.b.

21. Provide a Geotechnical Evaluation (soil's report) that provides a recommended setbacks from the basin to lot 1. The soils report must also demonstrate sufficient infiltration. Percolation test must show a maximum disposal time of 12 hours. SMDDFM 14.2.6.

22. It is acknowledged that a detailed basin note is provided on the plat, please note maintenance must also be discussed in the drainage report.


DRAINAGE REPORT COMMENTS

1. On the cover sheet include the tentative plat activity number, "S06-097."

2. It is acknowledged that a detailed basin note is provided on the plat, please note maintenance must also be discussed in the drainage report. The specific maintenance notes specified in the Standard Manual for Drainage Design and Floodplain Management, SMDDFM.14.3 must be included in the Drainage report. At minimum provide a detailed checklist addressing all areas of basin and drainage maintenance. Clearly indicate in the drainage report the responsibility of operating and maintaining a local detention basin rests with the owner of the facility. However, the City of Tucson reserves the right to periodically inspect or review any private-maintenance actions that would help to ensure that private maintenance, related to facility operation and safety, is being adequately provided.
06/05/2006 PGEHLEN1 COT NON-DSD REAL ESTATE Approved S06-097 The Lofts at Villa Savonna: Tentative Plat Review - The proposed 15 parking spaces within the public R/W of Smoot Drive cannot be considered for on-site parking purposes.
06/05/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-097 Lofts at Villa Savonna April 26, 2006

(X) Tentative Plat
() Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Northside Area Plan

GATEWAY or SCENIC ROUTE: NO

COMMENTS DUE BY: May 24, 2006

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(X) See Additional Comments Attached (RCP related)
() No Additional Comments - Complies With Planning Comments Submitted on:
(X) Resubmittal Required:
(X) Tentative Plat
() Development Plan
(X) Landscape Plan
(X) Other - Elevations and Color Palette

REVIEWER: msp 791-4505 DATE: May 31, 2006

Department of Urban Planning & Design
S06-097 - The Lofts at Villa Savonna: Tentative Plat Review
May 31, 2006

Staff offers the following comments:

Tentative plat, S06-097, is proposed as a Residential Cluster Project (RCP), and therefore must comply with section 3.6.1 of the Land Use Code, specifically section 3.6.1.4 of the general development criteria. In this instance, the RCP requires compliance with policies of the Northside Area Plan, the General Plan, and the Design Guidelines Manual. The Plans require community amenities; such as but not limited to; streetscapes with pedestrian oasis, and common area(s) of appropriate land size(s) to sustain passive and or active residential amenities for all, four sided architectural design on units visible from right-of-ways, and compatibility with adjacent residential uses.

Since lots 1 through 11, 24, and 25 are visible from public right-of-way, they shall be required to have five sided architectural units. The requirement is to wrap around to the sides and rear of the unit the same architectural level of detail as provided on the front façade of the unit. In addition to the proposed landscaping along the south right-of-way of Smoot Drive, the interior street (proposed private street) shall include a streetscape with canopy trees, which are to be planted within every other lot along the full length of the private street to create pedestrian oasis along the neighborhood street. Residential Cluster Projects (RCP) shall include within the required improvements, minimum five feet wide sidewalks..


1. Please revise proposed tentative plat, sheet 2 of 3, key note #8 to read 5.5 feet wide concrete sidewalks to concur with sheet 3 of 3, cross-section B/3
2. Please revise proposed tentative plat, sheet 3 of 3, cross-section A/3 to provide a five feet wide sidewalk along the southern right-of-way of Smoot Drive.
3. In addition to the proposed landscape buffer along Smoot Drive, please revise tentative plat/landscape plan to provide at minimum, one 15-gallon canopy tree within every other lot, and planted no more than (10) ten feet back from back of sidewalk.
4. Please revise tentative plat to include passive recreational amenities within Common Area “A,” (functional open space and drainage). Passive recreational amenities to include a tot lot and three other amenities, such as but not limited to; Half court basketball play area, Ramada structure, Table, bench, BBQ grill, Trash container.
5. Please revise the tentative plat/landscape plan to show the location of the required recreational amenities within the retention/detention basin. Recreational amenities to be handicapped accessible and located outside of the flow channel and shall be connected to the sidewalk system by an all-weather path.
6. Revise tentative plat to identify lots restricted to single story units. All lots along the perimeter that are located adjacent to single story units shall be restricted to single story construction. Please identify which of the following lots, 10 through 25 are located adjacent to existing single story units.
7. Please provide building elevations and a color palette for each proposed model unit (front, sides, rear, & roof) for lots 1 through 10, 24, and 25, to satisfy compliance with the five-sided architectural design element.
06/23/2006 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
06/30/2006 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: S06-097, Lofts at Villa Savonna, 3808 N. 1st (administrative address)
New residential subdivision, (Residential Cluster Project)
Tentative Plat

TRANSMITTAL DATE: June 28, 2006

DUE DATE: May 24, 2006

COMMENTS:


1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is April 25, 2007.

2. This project was reviewed for compliance with the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI) and International Building Code 2003 (IBC). Specifically, the content of this project was reviewed under DS 2-03 and LUC 3.6.1.

DS 2-03 REVIEW COMMENTS

3. Per DS 2-03.2.1.B, on resubmittal, ensure left margin of all sheets is only half inch.

4. Per DS 2-03.2.1.D, please list all subdivisions with recordation info within the area depicted on location map. In addition, please add Smoot Drive and Tyndall Avenue to the location map.

5. Per DS 2-03.2.1.G.2, declare in title block this subdivision is a residential cluster project.

In addition, in the title block (and on the plat) common areas should be referenced with their associated use (i.e. common area A is a drainage basin, common area B is the private street and parking, etc.)

6. Per DS 2-03.2.2.B1, place subdivision case number of S06-097 in the title block area.

7. Per DS 2-03.2.2.B.7, add code section "LUC 2.8.3." to general note 17.

8. Per DS 2-03.2.3.H, in response letter, clarify if existing church building is to be demolished.

9. Per DS 2-03.2.4.A, please provide separate line weights for buildings, lots, common areas, etc. It is really difficult to determine on this plan where the building foot prints and lot boundaries are.

10. Per DS 2-03.2.4.C, label each common area with letter designation A, B, C - i.e. drainage common area A, common area B landscaping or open area, parking/private drive common area C, etc. Provide square footage note for each common area element.

11. Per DS 2-03.2.4.G and 3-05, With regards to visitor parking spaces:
A) Visitor parking spaces must be provided within 150 feet of all lot lines, as a pedestrian travels, not as a bird flies. It appears the lack of on street parking provided on Villa Savonna and the position of the subsequent common area parking will not meet this requirement. (lots 15,16)

B) The visitor parking spaces which are 90 degrees to the street do not meet the requirements of LUC Sec. 3.3.7.5 (street may not be used for maneuvering in or out of a parking space). The exception to this provision is if a letter is provided from the City Engineer approving the location of the parking spaces.

C) Provide wheel stop barriers for all parking spaces to ensure pedestrian circulation is not compromised.

D) Staff is concerned about guest parking being provided directly adjacent to an emergency turn around area. Please see Engineering and Fire Dept. comments for further details. Be advised, the parking configuration may have to be change if these divisions assess a need.

E) Proposed on street parking and widening of the established Smoot Drive requires approval from Permits and Codes for right of way work 791-5100. Please provide commentary from this department that work on Smoot Drive will be permitted as shown.

12. Per DS 2-03.2.4.J, please ensure all easements on the property - current and proposed, are shown with associated recordation information.

TYPICAL DETAIL DRAWING COMMENTS

13. On detail A/3, change the sidewalk to a minimum of 5' in width for Smoot. Per DS 3-01, Figure 2.

14. On detail B/3, list the Average Daily Traffic. As proposed with 25 units accessing of the same street, the ADT for this street does not fall under 140 or less. The ADT determines building setbacks.

RCP 2-10.3.1 / RCP LUC 3.6.1 REVIEW COMMENTS

15. Per DS 2-10.3.1.B, please provide a typical detail drawing for a corner lot and a lot nearest 1st Street (it appears there is no setback issue from 1st due to the great length the buildings are away from the future road widening) for record purposes.

16. Per DS 2-10.3.1.D, provide note on first page indicating "Barrier-free accessibility for the elderly and physically disabled shall be provided to 25% of the ground floor units and all common use areas, including parking areas, within the project. And specify which lots, 6 are required for a 25 unit subdivision (staff acknowledges the note provided on the typical detail drawings, however, it should be in the general notes as well.)

17. Per DS 2-10.3.2.A, as 1st Street is a Major Streets and Routes (MS&R), Smoot Drive is also a MSR for setback purposes because it is a tributary off 1st Street. In light of this, please show:
A) the back of the future curb location off 1st Avenue
B) the distance from centerline of 1st Avenue to back of future curb
C) the setback line at a distance of 21 feet from the back of future curb east into the property
D) the setback line at a distance of 21 feet from nearest edge of travel lane from Smoot

18. Per LUC 3.6.1.4.D.2.c, provide 300 square feet of open area on each lot, 100 contiguous. And provide dimensions to verify on each lot or in table format.

19. Per DS 2-10.3.2.D, as each lot is under 4000 sf, provide elevations to be used to verify setbacks - measure from design grade to top of building - clarify if parapet roof.

20. Per LUC 3.2.6.5.B.2, With regards to building setbacks:
These townhomes will have a 140 ADT from each direction on each side of the entry street. Given the ADT, the residence setbacks from Villa Savonna are as follows:

For the garage, the setback is a maximum of 8' from the edge of pavement to the face of the garage - AND the garage must ALSO be setback 1 foot minimum from the sidewalk AND 1 foot back from the property line.

The setback shown for the garage to the edge of pavement is suffice, it's the 1' setback from the property line that cannot be accomplished without compromising the required maximum setback of 8' from pavement edge.

There are 4 options to seek remedy to this setback issue:
A) move property line to back of curb and provide Public access/utility easements to contain the sidewalk and maintenance area on each lot
B) move garage design back to accommodate the full length of a parking space of 18 feet in front of the garage to the property line
C) seek a DSMR (Development Standard Modification Request) to reduce the width of the right of way at least 1 foot on either side of the street
D) seek Board of Adjustment variances to allow for a 0 setback to existing property line

Please provide a setback notation for the south side of the development, perimeter area abutting the C-1 zone.

21. Provide a typical detail drawing for the handicapped accessible ramps, showing truncated domes.

22. Please provide an additional handicapped accessible ramp on the south side of Villa Savonna, positioned across from the ramps on the north side of the street that enters the subdivision. This will allow HC access to cross the street at midpoint rather than having to utilize the ramps at each end of the street.

23. Please provide a sidewalk around the guest parking at the west side of the project, abutting the drainage basin. Pedestrian/Handicapped access would otherwise have to cross behind the parking spaces and utilize the right of way pavement area. This would not meet standards of DS 2-08.

24. Per DS 2-10.3.2.E, provide CCRs.

25. Depending upon the responses given, further review comments may be forthcoming. Should you have any questions about this review, email me at Heather.Thrall@tucsonaz.gov or contact me at 520-791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.


C:\planning\cdrc\tentativeplat\S06-097 lofts at villa savonna.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, CC&R's and additional requested documents.
07/12/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 12, 2006

Thomas E. Guido, P.E.
T & T Engineering, LLC.
5980 East Verde Place
Tucson, AZ 85750

Subject: S06-097 The Lofts at Villa Savonna Tentative Plat

Dear Thomas:

Your submittal of April 26, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

8 Copies Revised Tentative Plat ( Addressing, Assessor, Traffic, Landscape, Engineering, Community Planning, Zoning, DSD)

5 Copies Revised Landscape Plans (Community Planning, Landscape, Engineering, Zoning, DSD),

2 Copies Revised NPPO Plans (Landscape, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies Geotechnical Report (Engineering, DSD)

2 Copies Elevations and Color Palette (Community Planning, DSD)


Should you have any questions, please call me at 791-5608 ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 577-0929