Review Status: Completed
Review Details: FINAL PLAT REVIEW
Plan Number - S06-093
Review Name: FINAL PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2006 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 11/17/2006 | KAROL ARAGONEZ | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Karol Aragonez Planner PROJECT: S06-093 Eastside Industrial Center Final Plat TRANSMITTAL DATE: November 17, 2006 DUE DATE: December 5, 2006 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. An applicant has one (1) year from the date of approval of tentative plat to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before September 7, 2007. 2. Please revise general note 3 to read "total miles of private streets is zero (0)", removing reference to PAALs. DS 2-03.6.2.C 3. Please fill in beneficiary information in that block. DS 2-03.6.3.C 4. Please revise the recording data block to read verbatim to the development standard. DS 2-03.6.3.D If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197. KAA S:\zoning review\karol\planning\cdrc\finalplat\S06-093fp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, CC&R's and additional requested documents. |
| 11/17/2006 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | SUBJECT: EASTSIDE INDUSTRIAL CENTER S06-093 Tucson Electric Power Company (TEP) approves the final plat submitted November 6, 2006. Additional easements will be required by separate instrument. Please contact me at (520) 917-8745 if you have any questions. Liza Castillo, Right of Way Agent Land Management Tucson Electric Power Co. Unisource Energy Gas & Unisource Energy Electric PH: (520) 917-8745 lcastillo@tep.com <mailto:lcastillo@tep.com> |
| 11/28/2006 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approved | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S06-093 EASTSIDE INDUSTRIAL CENTER/FINAL PLAT DATE: 11/28/06 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. ***The Pima County Addressing Section can use digital CAD drawing files when submitted with your final plat Mylar. These CAD files can be submitted through the Pima County Subdivision Coordinator. The digital CAD drawing files expedite the addressing and permitting processes when we are able to insert this digital data into the County’s Geographic Information System. Your support is greatly appreciated.*** ES |
| 12/06/2006 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Denied | S06-093 Eastside Industrial Center: Final Plat Review - Request consideration for the following: 1. Provide the correct Docket/Page for the 15' wide water easement. 2. Per Dkt./Pg. 7255/1138 & 11495/4275 and Dedication language on Plat, Bk. 37 Pg. 29; Request language to reflect the maintenance of private drainage ways, as specified in the CC&R's. |
| 12/06/2006 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559 FROM: Gary Ault, Mapping Supervisor Pima County Assessor's Office Mapping Department DATE: December 5, 2006 RE: Assessor's Review and Comments Regarding Final Plat S06-093 EASTSIDE INDUSTRIAL CENTER T141521 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements. _______ Plat does not meet Assessor's Office requirements. COMMENTS: THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390 NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. ROSANNA WERNER |
| 12/07/2006 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | |
| 12/07/2006 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | December 7, 2006 TO: Greg Carlson, P.E. Greg Carlson Engineering THRU: Patricia Gehlen, CDRC Manager City of Tucson, Development Services Department FROM: Chandubhai C. Patel, P.E. Pima County Development Services Department Development Review Division (Wastewater) SUBJECT: Eastside Industrial Center, Lots 1-12 & Common Element “A” Final Plat – 1st Submittal S06-093 The drawings for the proposed Final Plat for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. SHEET 1. The BENEFICIARY block needs to be completed. SHEET 1. In the DEDICATIONS block, 4th paragraph, replace the words COMMON AREAS with COMMON ELEMENTS. This needs to be done at three places in this paragraph. SHEET 1. In the DEDICATIONS block, 4th paragraph, 3rd line, add PIMA COUNTY after the word PUBLIC. The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and the response letter. For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above comments, please do not hesitate to contact me. Sincerely, Chandubhai C. Patel, P.E. Telephone: (520) 740-6563 Copy: Project File |
| 12/19/2006 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES December 19, 2006 Greg Carlson Greg Carlson Engineering LLC 1521 East Broadway Blvd. Tucson, Arizona 85719 Subject: S06-093 Eastside Industrial Center Final Plat Dear Greg: Your submittal of November 6, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 5 Copies Revised Final Plat (Zoning, Real Estate, Wastewater, Engineering, DSD) Should you have any questions, please call me at 791-5608 extension 1179. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 624-4197 fpresubmittal |
| 12/19/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Patricia Gehlen DATE: December 18, 2006 CDRC/Zoning Manager SUBJECT: Eastside Industrial Center,1820 S. Research Loop Final Plat S06-093 (First Review) T14S, R15E, Section 14 RESUBMITTAL REQUIRED: Final Plat. The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Final Plat: 1. Please provide North arrow and scale per D.S. 2-02.2.1. 2. Please include a response letter to the comments along with the corrected copies of the FP. 3. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: · Title Report · Special Warranty Deed · Trust Agreement · Amendment to Trust · Agreement to Construct Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. 4. The title block of the plat must match the Subdivision Assurances verbatim. 5. Correct the dedications to read "Common Elements" instead of "Common Areas". 6. Please re-label all common elements that may be used in a dual and/or single use capacity per D.S. 2-03.6.4.C. For example, a Ret./Det. Basin may also be used as a recreation facility or only as a drainage facility or drainage channel and this must be reflected on the Final Plat. A key note explaining the labels could be used in conjunction with the labels, ie.: Common Element "A" - Streets Common Element "B" - Drainage/Recreation Facilities Common Element "C" - Recreation Facilities Common Element "D" - Drainage Facilities Common Element "E" - Landscaping 7. Show sight visibility triangles per D.S. 2-02.2.1.10. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/1820 S. Research Loop FP |