Review Status: Completed
Review Details: FINAL PLAT REVIEW
Plan Number - S06-083
Review Name: FINAL PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2007 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approv-Cond | PIMA COUNTY ADDRESSING 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S06-083 OASIS-HARRISON/FINAL PLAT DATE: 1/02/07 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: 1.) If "Ventaso" is Spanish, you will need to provide Spanish Review and change the suffix of Circle to the prefix of Circulo. es |
| 01/03/2007 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | |
| 01/05/2007 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Gary Ault, Mapping Supervisor Pima County Assessor's Office Mapping Department DATE: January 4, 2007 RE: Assessor's Review and Comments Regarding Final Plat S06-083 OASIS-HARRISON T141502 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements. _______ Plat does not meet Assessor's Office requirements. COMMENTS: THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390 NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. ROSANNA WERNER |
| 01/18/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Patricia Gehlen DATE: January 18, 2007 CDRC/Zoning Manager SUBJECT: Oasis-Harrison, 32 lot subdivision Final Plat S06-083 (First Review) T14S, R15E, Section 02 RESUBMITTAL REQUIRED: Final Plat. The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Final Plat: 1. Please include a response letter to the comments along with the corrected copies of the FP. 2. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: · Title Report · Special Warranty Deed · Trust Agreement · Amendment to Trust · Agreement to Construct Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. 3. The title block of the plat must match the Subdivision Assurances verbatim. 4. Show sight visibility triangles per D.S. 2-02.2.1.10. 5. Indicate the name and width of each street, alley, easement (type), and drainageway within……………..per D.S. 2-03.6.4.A. 6. Corner lots may be designated with a star symbol indicating which street will be………..………..per D.S. 2-03.6.4.G. 7. Show a 1' no access esmt. on the west property line of lots 7, 22, 23 and 14 and on the east side of lots 13, 14 and 32 per D.S. 2-03.6.4.H. 8. Indicate tract boundary lines; right-of-way and centerlines of streets, easements…….per D.S. 2-03.6.5.B. Include the Line and Curve data tables on the plat. Revise as required. 9. In casting for points on section and quarter section lines, the standard survey monuments must be set…….per D.S. 2-03.6.5.C.6. It appears there may be a discrepancy between the LEGEND on the cover sheet and monuments to be set on the centerline of the street and on Harrison Road. Revise as required. 10. Please submit a copy of the subdivision boundary closure calculations. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/Speedway Blvd.-Harrison Rd. FP |
| 01/19/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES January 19, 2007 Dan Castro Rick Engineering Company, Inc. 1745 East River Road, Suite 101 Tucson, Arizona 85718 Subject: S06-083 Oasis-Harrison Final Plat Dear Dan: Your submittal of December 4, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 7 Copies Revised Final Plat (Wastewater, Real Estate, TEP, Zoning, Addressing, Engineering, DSD) Should you have any questions, please call me at 791-5608 extension 1179. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 322-6956 fpresubmittal |
| 12/04/2006 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 12/08/2006 | MARILYN KALTHOFF | PIMA COUNTY | WASTEWATER | Denied | PIMA COUNTY WASTEWATER December7, 2006 To: Chuck Martin, Rick Engineering Thru: Patricia Gehlen, CDRC Project Manager City of Tucson Development Services Department ____________________________________ From: Michael J.Harrington (520-740-6579), representing the Pima County Departments of Wastewater Management and Environmental Quality Subject: Oasis - Harrison Lots 1-32, Block A & Common Areas "A-1", "B-1" - "B-4", "C-1" & "D-1" - "D-2" Final Plat - 1st Submittal S06-083 The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Obtain and provide a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system. This is the fourth request. 2. Per written guidance provided by the PCWMD Development Services Section, a formal Sewer Service Agreement with PCWMD will not be required for this project. 3. Sheet 1: Add a General Note that states: THE LANDSCAPING WITHIN ALL PUBLIC SEWER EASEMENTS SHOWN HEREON SHALL BE IN ACCORDANCE WITH THE PLANTING GUIDELINES OF PC/COT STANDARD DETAIL WWM A-4. 4. Sheet 1: Add a General Note that states: THE OWNERS, OF LOT 32, COMMON AREAS "B-2"AND "C-1", SHALL NOT CONSTRUCT ANY PERMANENT STRUCTURE (I.E., MASONRY WALLS, FENCES, ETC.), ON OR THROUGH THE PUBLIC SEWER EASEMENTS, WITHOUT SEPARATE WRITTEN CONSENT FROM THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT. 5. Sheet 1: In the DEDICATION block, 3rd paragraph. The private streets are in the common areas and the common areas need to be granted or dedicated AS EASEMENTS TO THE CITY OF TUCSON, PIMA COUNTY AND ALL UTILITY COMPANIES FOR THE PURPOSE OF ACCESS, INSTALLATION, … 6. Sheet 1: In the DEDICATION block, 3rd paragraph, last sentence. By the wording in this dedication, it appears that the owners of lots 1-32 are going to accept responsibility for any future private sewers that may be constructed on Block A, in addition to any common recreation site. You do not need to make any revisions to this sentence if this is your intention. 7. This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet. The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter CC: Project File December 7, 2006 To: Chuck Martin, Rick Engineering Thru: Patricia Gehlen, CDRC Project Manager City of Tucson Development Services Department ____________________________________ From: , representing the Pima County Departments of Wastewater Management and Environmental Quality Subject: Oasis - Harrison, Lots 1-32, Block A & Common Areas "A-1", "B-1" - "B-4", "C-1" & "D-1" - "D-2" Tentative or Preliminary Plat - 3rd Submittal S06-083 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Sheet 2. Sheet If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter CC: Project File |
| 12/15/2006 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Denied | S06-083 Oasis-Harrison: Final Plat Review - In reference to 12/15/06 Discussion w/ Daniel Castro, Rick Eng., 1' N.V.A.E. & a C.A. to the S. of the entrance are to be annotated on forthcoming final plat. Dedication language needs to be provided on Sht. 1 of 2 for the 10' of R/w along Harrison Rd. |
| 12/19/2006 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Denied | SUBJECT: OASIS-HARRISON Lots 1-32 S06-083 Tucson Electric Power Company (TEP) has received the final plat submitted for review submitted December 4, 2006. This Company is unable to approve the plat at this time. An electrical design to determine our easement requirements will be provided on the Approved Tentative Plat within fifteen (15) working days upon receipt of the plat. Additional plans necessary for preparation of the design are: building plans including water, electrical, landscape, sidewalk and paving plans. Also, submit the AutoCAD version of the plat on a CD or email to lcastillo@tep.com <mailto:lcastillo@tep.com> . Please contact me at (520) 917-8745 if you have any questions. Liza Castillo, Right of Way Agent Land Management Tucson Electric Power Co. Unisource Energy Gas & Unisource Energy Electric PH: (520) 917-8745 lcastillo@tep.com <mailto:lcastillo@tep.com> |
| 12/20/2006 | KAROL ARAGONEZ | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Karol Aragonez Planner PROJECT: S06-083 Oasis-Harrison Final Plat TRANSMITTAL DATE: December 20, 2006 DUE DATE: January 2, 2007 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. An applicant has one (1) year from the date of approval of tentative plat to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before December 10, 2007. 2. Please change all dates in the dedication, approval, and recording blocks from 2006 to 2007. 3. Please provide the various widths of Ventaso Circle. DS 2-03.6.4.A 4. Please identify the area west of lot 23. Is this a part of Common Area "B"? DS 2-03.6.4.C If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197. KAA S:\zoning review\karol\planning\cdrc\finalplat\S06-083fp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, CC&R's and additional requested documents. |