Plan Number: S06-065
Parcel: Unknown

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S06-065
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/24/2006 JIM EGAN COT NON-DSD FIRE Denied Detail of curb shows vertical curbs. Radius on plans show 50' to back of sidewalk. Therefore, actual turning radius available is 40', insufficient for Fire Department and/or COT street standards.
03/29/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-065
CIVIL WORKS ENGINEERING
CASITAS AT LIBERTY
*********************************************************************
Confidentiality and Nondisclosure Notice: This email transmission
and any attachments are intended for use by the person(s)/entity(ies)
named above and may contain confidential/privileged information.
Any unauthorized use, disclosure or distribution is strictly
prohibited. If you are not the intended recipient, please contact the
sender by e-mail, and delete or destroy all copies plus
attachments.
*********************************************************************
03/29/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this develpoment.
* All lots have curbside frontage. Approved for APC curbside service. APC's are to be placed and removed from the collection area on the day of service.
04/04/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied April 4, 2006

TO: Joaquín Rincón
Civil Works Engineering

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Casitas at Liberty
Tentative Plat – 1st Submittal
S06-065

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

ALL SHEETS. Add the project number, S06-065, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates.

SHEET 1. Delete General Note 13.

SHEET 2. Delete General Notes 11 and 12.

SHEET 2. For reference purposes, please assign a number to all newly proposed manholes.

SHEET 2. Revise the proposed public sewer design shall be design to a minimum one percent slope. Additionally, revise this design to place the upstream manhole at a more central location within the cul-de-sac to avoid such a long HCS connection from Lot 7.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
04/06/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: CASITAS AT LIBERTY
Lots 1-12
S06-065

Tucson Electric Power Company (TEP) has reviewed the tentative plat
dated March 21, 2006. This Company is unable to approve the plat at
this time.

There are existing electrical facilities within the boundaries of the
development. The facilities along with the easement recording
information must be shown on the plat prior to approval. Existing
easement recorded in Docket 9412 at page 467. If an existing easement
is not found add a dimensioned easement by prescription and a general
note that the facilities will be abandoned. All relocation costs will
be billable to the developer. Please direct questions concerning
easements) to Liza Castillo, Right-of-Way Agent in our Land Department
at 520-917-8745.

TEP will provide a preliminary electrical design on the Approved
Tentative Plat within fifteen (15) working days upon receipt of the
plat. Additional plans necessary for preparation of the design are:
building plans including water, electrical, landscape, sidewalk and
paving plans. Should you have any questions, please contact the
Designer assigned to this project, Frank Grijalva at (520) 918-8361.


Sincerely,



Kathy Clark
Scheduling Coordinator
Design/Build
kc
enclosure
cc: P. Gehlen, City of Tucson
A.Espinosa, ESS Properties (Letter only)
F. Grijalva, Tucson Electric Power Company


Kathy Clark
Scheduling Coordinator
Design/Build
520-918-8271
kclark@tep.com
04/11/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-065 Casitas at Liberty 04/07/06

(XXXX) Tentative Plat
() Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: 12th Avenue/Valencia

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 04/18/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 4/07/06
04/12/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-065 CASITAS AT LIBERTY/TENTATIVE PLAT
DATE: April 12, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Title Block should include: Lots 1-12.

Delete 5031 S. Liberty Avenue on sheet 2. Lot 12 will keep this address, however, this plat will receive an Administrative Address plus individual lot addresses.
Liberty Place is unacceptable due to duplication. Please choose a new name.












jg
04/12/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied S06-065 Casitas at Liberty: Tentative Plat Review. Easements listed in Schedule B, Sec. II, are not annotated or listed in notes.
04/14/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Estimated daily traffic trip in 24 hr period - 118
04/17/2006 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Add the CDRC case number and any related case numbers to the landscape and native plant preservation plans. DS 2-07.2.1.B

2) All disturbed, grubbed, graded, or bladed areas not otherwise improved shall be landscaped, reseeded, or treated with an inorganic or organic ground cover to help reduce dust pollution. Revise landscape plan to identify inert ground cover materials for all common areas and the adjacent right-of-way area.
LUC 3.7.2.7., DS 2-06.5.2.C

3) Provide landscaping for Common Area 'A' also. Any required storm water detention/retention basins shall be landscaped to enhance the natural configuration of the basin. Design criteria are set forth in Development Standard 10-01.0. LUC 3.7.4.3.A

4) Show and identify any existing plants to remain in place on the landscape plan. DS 2-07.2.2.A.1.e

5) The native plant preservation application is denied. A native plant inventory will be required due to the presence of protected species on the site (as indicated in photos submitted). DS 2-15.2.0

6) Revise the landscape plans to show the limits of grading. DS 2-07.2.2.B.5

7) Revise the landscape border calculations and remove incorrect data.

Resubmittal of all plans is required, including a native plant preservation plan.
04/18/2006 LOREN MAKUS ENGINEERING REVIEW Denied DATE: April 25, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: Casitas At Liberty
Tentative Plat S06-065 (First Review)
T15S, R13E, Section 01

RESUBMITTAL REQUIRED: Tentative Plat, Drainage Report

The Tentative Plat and Drainage Report have been reviewed by the Engineering Division and we do not recommend approval at this time. The following review comments must be addressed.

Tentative Plat
1. Clarify the relationship of boundaries of lot 12 and the proposed right-of-way. It appears that the proposed lot encroaches into the required right-of-way area.
2. Revise the street detail to indicate that the parking lanes must be 8 feet wide. The pavement width must be 36 feet.
3. Provide details to show how the driveway crossings over the sidewalk will be ADA compliant.
4. Provide an entry in the legend for the symbol used around lot 12 and between the rear portions of other lots.
5. Provide a complete title block. Note that any common area containing basins must be called out as a basin in the title block on the Tentative Plat and on the Final Plat. Indicate in the title block that this is a resubdivision of the north half of lot 7 block 2 of Arcadia Subdivision.
6. Please place all of the general notes in one location.
7. Show benchmark locations, the proposed location of and method of tie to permanent survey monuments or to the nearest section or quarter section corner, and the proposed location and type of subdivision control monuments. All monuments found or set will be described.
8. It appears that lots 1 and 2 may be in violation of the differential grading requirements of the developments standard. Fills of greater than 2 feet may not be placed in the outer 100 feet of the project. Revise the proposed FFEs or provide proposed pad grades that comply with the development standard.

Drainage Report.
9. Revise the drainage report to clearly describe the existing and proposed conditions. The revisions must include but are not limited to the following.
10. Clearly label all of the exhibits including the hydrographs
11. Number all of the pages in the drainage report.
12. Provide a discussion of the hydraulic calculations for wall openings, roadways and scuppers to ensure adequate capacity. Explain which equations from the Drainage Manual were used and which clogging factors were used.
13. Show that the retention and detention volumes will be comprised of discharges of on-site flows since this project cannot regulate the off-site flows. (Note that retention and detention are not required for the discharges from off-site areas.)
14. Provide details and calculations to show the basin will be sized correctly.
15. The drainage report indicates that the basins are designed as multi-use basins. Revise the basin design to remove unnecessary rip rap to be consistent with the mult-use design concepts. Rip rap is required only where there is significant velocities.
16. Provide an exhibit that describes the proposed drainage conditions. Revise the existing conditions exhibit so that it accounts for the whole project area.
17. Explain how the discharge will be directed to the basin since the road slopes away from the basin inlet.
18. Justify the percent of impervious area used in the existing conditions hydrology analysis for onsite conditions.
19. Revise the retention volume caluculations to use the 5-year run-off coefficients. Provide a discussion of the soil types on the site.
20. Include a basin maintenance inspection checklist in the drainage report. Provide a clarification that indicates that a homeowners' association will be responsible for basin inspection and maintenance.
21. Provide a calculation of the expected sedimentation buildup for the basins. Use equation 3.8 in the retention/detention manual. Provide a permanent concrete marker in the bottom of the basin as described in section 3.4.2 of the manual.


Submit a revised Tentative Plat and a revised Drainage Report addressing these comments. Include a detailed response letter, detailing how each comment has been addressed.
If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
04/21/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: April 19, 2006


RE: Assessor’s Review and Comments Regarding Tentative Plat
S06-065 Casitas at Liberty T151301 (137-07)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal. Please make the following additions/corrections in the final plat.
Add the number of lots and the common areas to the title block in the lower right corner. Also add the section, township and range.
The perimeter line must be a solid line.
Add the interior bearings for the lots and the dimensions and bearing for the street centerline.
Add complete curve data.
Add adjacent subdivision names and the map and plat for each.
Add the section tie.
If there are any questions, please contact Susan King at 740-4391.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.





Susan King
05/02/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied DATE: May 2, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: S06-065 Casitas at Liberty: Tentative Plat(3-21-06)


Denied.
Please show a publicly accessible pedestrian connection between the east end of Liberty Place and El Pueblo Park.
05/03/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic engineering REJECTS this TP:

1. Jogs of less than 150’ in local alignment are not acceptable (DS 3-01.6.3)

2. The SVTs are mislabeled. Near side is labeled where the far side should be and vice versa. The dimensions are correct. Near side is 180' and far side is 110'.

3. List the name, ROW width, recordation data, type and dimensioned with of paving, curbs, curb cuts and sidewalks. (DS 2-03.2.3.D) There is no recordation data for Liberty Ave.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
05/15/2006 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
05/19/2006 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S06-065
Casitas at Liberty
Tentative Plat

TRANSMITTAL: 05/19/06

DUE DATE: 4/18/06

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is 4/17/07.

2. DS 2-03.2.1.C All lettering and dimensions will be the equivalent of twelve (0.12) point or greater in size. The purpose of this requirement is to assure that the lettering is legible when reproduced or when photographically reduced (microfilmed) for record keeping purposes.

In addition to the above, some of the bearings and distances along the west and east property lines are not legible.


3. DS 2-03.2.1.D A small, project-location map will be provided, drawn at a scale of 3" = 1 mile. The location map will provide the following information.

2. Identify conditions within the square mile area, such as subdivisions, major streets, major watercourses, and railroads. Reference recorded subdivision plats by book and page numbers. Indicated street names are not legible.

4. DS 2-03.2.1.G A title block with the following information is to be provided approximately in the lower right corner of the first page of the plat.

1. List the common areas with the use of each common area.

2. The number of proposed lots is to be noted.

3. A brief legal description and a statement as to whether the project is a
resubdivision are to be provided. On resubdivisions, provide the recording
information of the existing subdivision plat. This project is a resubdivision of an existing subdivision lot.

5. DS 2-03.2.2.B.1 This project has been assigned the subdivision case number S06-065. Please list the case number in the lower right corner of all tentative plat sheets including the NPPO and landscape sheets.

6. DS 2-03.2.2.B.5 In note #4 list the proposed use as follows: "Family Dwelling "I", subject to: Sec. 3.5.7.1.F"

7. For clarity purposes provide only one set of "General Notes" with all of the required notes and calculations.

This project is not a RCP nor a rezoning case. Remove from the notes on page one all notes which refer to a RCP subdivision (#17, #20). From page two note #2 referring to proposed zoning, also remove from page one in the LUC requirements data list.

Revise note #18 on page one to read: "There shall be no further division of land or resubdivision without the written approval of Mayor and Council."

8. DS 2-03.2.4.A Provide the lot dimensions for lot #12.

9. DS 2-03.2.4.C Clearly indicate the separate common areas with a solid line and clearer letter designation.

10. DS 2-03.2.4.I The existing easements as indicated are to be abandoned. Clearly indicate that the abandonment will be by separate instrument. Provide recordation information (docket and page) on the tentative plat.

11. Add a note stating that a separate site plan will be required for each lot meeting the LUC standards for a family dwelling unit with a development designator "I".

12. The typical lot layout detail provided indicates the setback for the garage as 19' from the utility easement line. I believe you meant to indicate the distance from back of sidewalk. If so please revise. Indicate also on the typical lot layout the location of the driveway.

The typical lot layout provided will work for all lots except lot #7. Provide a lot layout detail clearly indicating the minimum required setbacks for this lot.

On lot #12 indicate the setback from the northeast corner of the existing structure to the property line.

13. In the lot coverage calculations provided vehicular use areas (driveways, garages, carports, etc.) have been omitted. Please revise calculations and percentage of coverage.

14. CC&R's will be required for maintenance of common areas. If available at this time please provide with next submiital. If not they will be required to be submitted at time of final plat.

14. Based on changes to the plans and responses to the comments further comments may be forth coming.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.


TLS C:\planning\cdrc\tentativeplat\S06-065tp.doc
05/24/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

May 24, 2006

Joaquin Rincon
Civil Works Engineering
515 East Grant Road #141-226
Tucson, AZ 85705

Subject: S06-065 Casitas at Liberty Tentative Plat

Dear Joaquint:

Your submittal of March 21, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

11 Copies Revised Tentative Plat (Fire, TEP, Traffic, Landscape, Real Estate, Parks and Recreation, Addressing, Wastewater, Zoning, Engineering, DSD)

5 Copies Revised Landscape and Irrigation Plans (Landscape, Parks and Recreation, Zoning Engineering, DSD),

2 Copies NPPO Plans (Landscape, DSD),

2 Copies Revised Drainage and Geotechnical Reports (Engineering, DSD)





Should you have any questions, please call me at 791-5608 ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 628-7503