Review Details: ASSURANCES

Plan Number - S06-061
Review Name: ASSURANCES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2006 MARILYN KALTHOFF START ASSURANCES RECEIVED Completed
04/13/2006 MATT FLICK ENGINEERING FOR ASSIGNMENT Completed
04/13/2006 LOREN MAKUS ENGINEERING REVIEW Approved DATE: April 13, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: Kilburn Place Condominiums
Assurances S06-061 (First Review)
T13S, R13E, Section 27

RESUBMITTAL REQUIRED: Water Supply Certification Letter and Location Map

The assurances and Final Plat submittals have been reviewed by the Engineering Division and we recommend Conditional approval at this time. The following items must be submitted for final approval.

1. DS 2-03.9.3.J Submit the letter of certification on assured water supply since the project is not served by the City of Tucson Water Department.
2. Include two copies of the general location map on 8.5" x 11" paper..

If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
10/13/2006 MARILYN KALTHOFF ENGINEERING ASSURANCES RECEIVED/SENT TO CITY ATTORNEY Completed