Plan Number: S06-056
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S06-056
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/01/2006 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: SIERRA MORADO, UNIT 3

Lots 807-1117

S06-056



Tucson Electric Power Company (TEP) has received the final plat
submitted for review October 17, 2006. TEP is unable to approve the
plat at this time.



An electrical design to determine our easement requirements will be
provided on the Approved Tentative Plat with thirty (30) working days
upon receipt of the plat. Additional plans necessary for preparation of
the design are: building plans including water, electrical, landscape,
sidewalk and paving plans. Also, submit the AutoCAD version of the plat
on a CD or email to lcastillo@tep.com <mailto:lcastillo@tep.com> .
Should you have any questions, please contact me at (520) 917-8745.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
11/15/2006 LAITH ALSHAMI ENGINEERING REVIEW Approv-Cond Laith Alshami, Engineering and Floodplain Review, 11/15/2006


TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Sierra Morado Unit 3
S06-056, T15S, R15E, SECTION 12

RECEIVED: Final Plat and Assurances on October 17, 2006

The subject project has been reviewed. The Final Plat is acceptable and it is hereby recommended for conditional approval pertaining to Engineering and Floodplain Review subject to the following conditions:

In accordance with Development Standard 2-03.7.1.G. the Final Plat cannot be scheduled for Mayor and Council consideration until the assurances are approved by the City Engineer's Office. The previous Assurances comments have not been addressed properly. The Assurances can not be approved until the following comments have been satisfactorily addressed:

1. Remove the word "Grading" from Common Area "B" description in the Original Agreement recitals, the Amendment and all exhibits "A".
2. Add as a separate assurable item, in Exhibit "B", the following: "All applicable fees, e.g. permit fees, impact fees must be paid in full to the City of Tucson prior to the final release of subdivision assurances.
3. Include the "Trust Agreement" in the Assurances Package.
4. Include the "Special Warranty Deed" in the Assurances Package.
5. Include in the Assurances Package and up to date Title report.

Prepare a detailed response that explains the revisions that were made and references the exact location in the drainage report and on the Tentative Plat where the revisions were made.


RESUBMITTAL REQUIRED: Revised Assurances Package
11/16/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-056 SIERRA MORADO UNIT 3/REVISED FINAL PLAT
DATE: 11/15/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


Change Block 79 Bk 50, Pg 36 and the western portion of Block 81 Bk 50, Pg 36 to the correct books and pages. These have been resubdivided.

Change Beautybush Trail to Terrace per letter dated 11/08/06 or is the suffix going to be changed to trail?

Change Franklinia trail to Terrace per letter dated 11/08/06 or is the suffix going to be changed to trail.

Fill in all books and pages before this plat records.

Label all streets on all pages, even ghosted areas.

Change all lettered streets to the correct street names.



es
11/21/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

November 21, 2006

Ryan R. Stucki
Stantec Consulting
201 North Bonita
Tucson, AZ 85745

Subject: S06-056 Sierra Morado Unit 3 Final Plat

Dear Ryan:

Your submittal of October 17, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

3 Copies Revised Final Plat (Addressing, TEP, DSD)










Should you have any questions, please call me at 791-5608 ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 750-7470