Plan Number: S06-018
Parcel: Unknown

Address:
6105 E PIMA ST

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S06-018
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/31/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: ALAMO LOFTS
S06-018



Tucson Electric Power Company (TEP) has reviewed the final plat
submitted July 24, 2006. TEP is unable to approve the plat at this
time.



In order for this Company to approve the final plat, the following
dedication is required.



"An easement is granted for the purpose of access, installation
replacing repairing and maintenance of electrical meters, cable and
conduits, which grouped electrical meters are attached to the exterior
walls."



Show the required dedication on the resubmittal of the final plat.
Submit two bluelines to the City of Tucson for TEP's final approval.
Any additional easements that are required after TEP prepares an
electrical design will be secured by separate instrument.



Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
08/08/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor


115 N. Church Ave.


Tucson, Arizona 85701



BILL STAPLES

ASSESSOR










TO: CDRC Office

Subdivision Review

City of Tucson (FAX# 791-5559)



FROM: Rosanna Werner, GIS Cartographer

Pima County Assessor's Office

Mapping Department



DATE: August 8, 2006





RE: Assessor's Review and Comments Regarding Final Plat

S06-018 Alamo Lofts T141401 (121-01)




* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *



X Plat meets Assessor's Office requirements.

_______ Plat does not meet Assessor's Office requirements.





COMMENTS: THANK YOU FOR YOUR SUBMITTAL





NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS
TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN
THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING
THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK
YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
08/15/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: August 15, 2006
CDRC/Zoning Manager

SUBJECT: Alamo Lofts, 6105 E. Pima Street
Final Plat S06-018 (First Review)
T14S, R14E, Section 01

RESUBMITTAL REQUIRED: Final Plat.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used:
· Title Report
· Special Warranty Deed
· Trust Agreement
· Amendment to Trust
· Agreement to Construct
Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.
3. Correct the title block to match the plan views to read "Common Elements "A" and "B" instead of "Common Areas "A" and "B".
4. The title block of the plat must match the Subdivision Assurances verbatim.
5. Please re-label all common areas that may be used in a dual and/or single use capacity per D.S. 2-03.6.4.C. For example, a Ret./Det. Basin may also be used as a recreation facility or only as a drainage facility or drainage channel and this must be reflected on the Final Plat. A key note explaining the labels could be used in conjunction with the labels, ie.:
Common Element "A" - Streets
Common Element "B" - Drainage/Recreation Facilities
Common Element "C" - Recreation Facilities
Common Element "D" - Drainage Facilities
Common Element "E" - Landscaping
6. Please submit a copy of the subdivision boundary closure calculations.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/6105 E. Pima St. FP
08/22/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied August 22, 2006

To: Doug Schneider, Rick Engineering

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J.Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Alamo Lofts
Units 1-22, Common Areas "A" & "B"
And Limited Common Elements "A-1" thru "A-22" and "B-1" thru "B-22"
Final Plat - 1st Submittal
S06-018

The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacities for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The final plat for this project cannot be approved until this office has received a copy of this letter. This is the 3rd request.

Sheet 1: In the DEDICATION block, 5th paragraph. There is no Trust Number shown. Once the ownership is resolved we will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of residential units. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the final plat.

Sheet 1: In the DEDICATION block, 4th paragraph. There is no mention of the Common Areas “A” & “B” that appear in the project Title block. Please clarify. The Common Areas will need to be:

GRANTED AS EASEMENTS TO THE CITY OF TUCSON, PIMA COUNTY AND ALL UTILITY COMPANIES FOR THE PURPOSE OF ACCESS, INSTALLATION AND MAINTENANCE OF PUBLIC SEWERS, UTILITIES AND DRAINAGE.

And also, the Dedication block does not address the ownership of the Common Areas.

Sheet 2: Revise the site plan so that it shows:

The common areas mentioned in the project title, COMMON AREAS “A” & “B”.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
08/29/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S06-018 Alamo Lofts: Final Plat Review - No comment.
09/07/2006 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S06-018
Alamo Lofts
Final Plat

TRANSMITTAL DATE: September 6, 2006

DUE DATE: August 21, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. An applicant has one (1) year from the date of approval of tentative plat to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. As of this final plat review date the tentative plat has not been approved therefore the one year date of the final plat approval is based on the date of submittal of the final plat documents. This final plat must be approved and recorded on or before July 23, 2007. Once the tentative plat has been approved the approval date of the final plat will be on one year from the tentative plat approval date. This date will be provided on a future review of the final plat.

2. Please correct the rezoning case number from Co9-05-19 to "C9-05-19". Co9 would indicate a Pima County rezoning case. Please make correct on all sheets of the final plat and to general note 4.

3. The reviewer for the tentative plat is requesting that the RCP be removed and that the applicant use R-3 development designator "P". If the applicant changes the tentative plat by removing the RCP designation please do the same to the title block of the final plat.

4. Please provide the cubic air volume for each condo unit on the final plat.

5. Please indicate in response if these units are single units or multiple units (1st, 2nd , 3rd) floor occupied by several families. The CC&Rs discusses noise impact to unit below floor. If multiple units these must be indicated and volumes and SF provided.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA S:\zoning review\karol\planning\cdrc\finalplat\S06-018fp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, CC&R's and additional requested documents.
09/07/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-018 ALAMO LOFTS/FINAL PLAT
DATE: 8/18/06



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Add Road to Wilmot (Southern most) on Location Map per letter dated 5/24/06.

Spell out Avenue of Sahuara Ave. on pg. 2.

Label occupant identifiers for each condominium. See attachment.
09/08/2006 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
09/11/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 11, 2006

Doug Schneider
Rick Engineering Company
1745 East River Road, Suite 101
Tucson, Arizona 85718

Subject: S06-018 Alamo Lofts Final Plat

Dear Doug:

Your submittal of July 24, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Final Plat (TEP, Engineering, Wastewater, Zoning, Addressing, DSD)








Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 622-6956
fpresubmittal