Plan Number: S06-002
Parcel: Unknown

Address:
3717 E GLENN ST

Review Status: Completed

Review Details: RECORD OF SURVEY REVIEW

Plan Number - S06-002
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/06/2006 JIM EGAN COT NON-DSD FIRE Approv-Cond The plan is approved based on Project Data Note regarding units to be provided with fire sprinklers.
01/13/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-002
MW2 DEVELOPMENT
GLENN STREET DUPLEXES EAST
*********************************************************************
Confidentiality and Nondisclosure Notice: This email transmission
and any attachments are intended for use by the person(s)/entity(ies)
named above and may contain confidential/privileged information.
Any unauthorized use, disclosure or distribution is strictly
prohibited. If you are not the intended recipient, please contact the
sender by e-mail, and delete or destroy all copies plus
attachments.
*********************************************************************
01/19/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-002 Glenn Street Dupluxes East 01/18/06

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Grant-Alvernon

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 02/03/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 1/17/06
01/23/2006 JCLARK3 ENV SVCS REVIEW Denied * No known landfill with in 1000 feet of this development.
* Project is not approved for APC service. Per development standards for three or more units the development requires centralized service. There is sufficient property width for a typical 'Tee" turnaround or an 'L' turnaround.
Note: South properties and North proposed properties should be worked together for a refuse enclosure for metal dumpsters.
01/27/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: GLENN STREET DUPLEXES

S06-002



Tucson Electric Power Company has reviewed and approved the record of
survey submitted for review January 5, 2006.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Warren McElyea

Design/Build - DB 102

Tucson Electric Power
Company

P. O. Box 711

Tucson, AZ 85702



Please call me at (520) 917-8745, should you have any questions.




Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
01/30/2006 PMCLAUG1 LANDSCAPE REVIEW Denied 1. This project is being reviewed for full code compliance. Submit a separate landscape and irrigation plans plan per DS 2-07.0. to verify that entire site meets current minimum requirements for landscaping and screening. Further comments may be necessary once plans are submitted. Refer to DS 2-06 and LUC Sec. 3.7 for landscaping and screening regulations.

2. An NPP plan or application for NPPO exception must be submitted per DS 2-15.0.

3. Add the subdivision case number (S06-002) to the lower right hand corner of all sheets of the Plat, Landscape Plan and NPPO Plan.
DS 2-03.2.2.B.1

4. All lettering and dimensions must be a minimum of 12 point (0.12") in size for microfilming purposes. Revise all text within the Notes and Project Data sections to meet this minimum archiving standard.
DS2-03.2.1.C

5. Additional comments may apply once all plans are submitted for review.
01/31/2006 RICHARD WILLIAMSON TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approv-Cond Conditioned upon meeting Tucson Water requirements for water service.
01/31/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: January 31, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: S06-002 Glenn Street Dupluxes East: Record of Survey Review


Staff has no comments.
02/02/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-002 GLENN STREET DUPLEXES EAST/RECORD OF SURVEY
DATE: February 2, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Format per CDRC requirements.

Highlight project on Location Map.

Delete all street directions on Location Map.

Spell out all street suffixes except on Location Map.

Delete Parcel Codes.

Label addresses on correct locations.

Add Drive to Monte Vista.




jg
02/07/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: February 7, 2006
ACTIVITY NUMBER: S06-002
PROJECT NAME: Glenn Street Duplex East
PROJECT ADDRESS: 3711-3719 East Glenn Street
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

Please be aware this review was conducted as a site review per the Development Standards 2-02.

1. All lettering and dimensions will be the equivalent of twelve point or greater in size. The purpose of this requirement is to assure that the lettering is legible when reproduced or microfilmed for record keeping purposes. The current font measures to 10 point, it must be at least 12 point or greater in size. Revise all lettering to be at least 12 point.

2. Include existing and future sight visibility triangles on the site plan. If the existing and future SVTs are coincident, label it as both existing and future. DS 2-02.2.1.A.10.

3. Add a legend to the plan indicating different line type, shading, etc.

4. Sidewalks must be flood free for up to the 10-yr. event. Add a note on the plan, "All roof down spouts on all structures must be routed under any adjacent sidewalk." DS 2-08.4.1.E

5. Per the Transportation Access Management Guidelines (TAMG) for an ingress/egress to a collector street 25' curb returns are required. Indicate 25' curb returns for the ingress/egresses to Glenn Street. TMAG was adopted on March 17, 2003 by Mayor and Council.

6. The dimensions of the PAAL is difficult to determine throughout the site. Because this is a full code compliance review the PAAL must be clearly indicated throughout the site plan. Indicate the width of the PAAL throughout the site. DS2-02.2.1.A.11., 12.

7. Handicap curb access ramps are required to be constructed with truncated domes, per recent a Federal ADA requirement. Show a detail or add a general note to the site plan indicating all public and private handicap curb access ramps will have truncated domes.

8. A minimum setback distance of five (5) feet for a pedestrian refuge area must be maintained between any enclosed structure and a PAAL. The refuge area may have a roof for shade, provided it contains a sidewalk and pedestrian access which is unobstructed and is set back one (1) foot from the PAAL. Sidewalk is required adjacent and parallel to any PAAL on the side where buildings are located. Provide a sidewalk and pedestrian refuge between the PAAL and existing structures. Revise plan as necessary. DS 3-05.2.2.B.1., Figure 1 and DS 2-08.4.1.B.

9. Sidewalks within a project must be physically separated from any vehicular travel lane by means of curbing, grade separation, barriers, railings or other means. It is difficult to determine if there is a grade separation, vertical curb, barrier, etc, between the edge of the PAAL and the designated 5' pedestrian access (keynote 1). Clearly indicate on the site plan a barrier, vertical curb or grade separation between the PAAL and the 5' pedestrian access. DS 2-08.4.1.

10. Sidewalks or pedestrian access areas may not be located between a vehicle parking space and a PAAL providing access to that space. The site plan indicates the pedestrian access area in the middle of a PAAL. Revise the site plan to show the pedestrian access (sidewalk) in a different location. DS 2-08.4.1.F.

11. There are very specific construction standards for the material used for a sidewalk (pedestrian access area) outlined in DS 2-08.5.0. Keynote 1 indicates asphalt will be used for the pedestrian area. Asphalt may only be used for jogging paths, nature trails and pedestrian areas that are not required to connect to required pedestrian paths. Because this proposed pedestrian access is a requirement and is required to connect to the sidewalk within the ROW the sidewalk must meet the standards found in 2-08.5.1.C. Revise accordingly.

12. The back up spur located to the south of the proposed structures must meet the requirements found in DS 3-05.2.2.D. Dimension the required 3' depth and 3' radius. Also see figure DS 3-05.2.2.D.

13. Indicate the drainage patterns for the site. DS 2-02.2.1.A.16.

14. Show roof drainage (flow arrows). DS 2-02.2.1.A.16

15. Show finish grades for the site and provide finish floor elevations for the proposed structures. DS 2-02.2.1.A016.

16. Include on the site plan estimated cut and fill quantities. If cut and fill quantities equal zero, please note on the plan. DS 2-02.2.1.A.17.

17. Indicate recordation data for Glenn Street. Indicate if Glenn Street is public or private. DS 2-02.2.1.A.18.

18. Dimension from street centerline the existing ROW width. Indicate the existing curb and sidewalk location. DS 2-02.2.1.A.21.

19. Glenn Street is designated as a collector street and has a full future ROW width of 64'. A half future ROW width of 32'. Dimension the ½ ROW width from street centerline. Show the future sidewalk and curb location. Label appropriately. DS 2-02.2.1.A.19.

20. Is their sidewalk along Glenn Street (within the ROW)? Sidewalks are required as part of new development of all properties. All new development shall provide 6 foot wide sidewalk along the entire length of the street frontage on an MS&R street. The space between the curb and sidewalk within the ROW is a minimum width of two feet. If existing sidewalk is already located with the ROW indicate on the plan. Otherwise indicate a proposed 6' sidewalk within the ROW along Glenn Street. DS 3-01.2.7.B., DS 3-01.3.3.A.

21. Show on the site plan existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. DS 2-02.2.1.A.23.

22. Indicate refuse container location, size and access thereto fully dimensioned. Demonstrate vehicle maneuverability fully dimensioned. Be aware refuse vehicles require 36' inside radius and 50' outside radius. Indicate a refuse enclosure detail as per D.S. 6-01.4.2 . New projects consisting of 3 or more dwelling units will provide centralized on-site refuse storage, collection and pickup areas. Revise accordingly.

23. Show the depth of the water harvesting areas in the landscape borders. Either by a general note or label on the plan.

24. Additional comments could be forth coming.
02/08/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S06-002; Glenn East - No Comment
02/08/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this ROS:

1. Show and label as to size (i.e. 20x110) both existing and future SVTs (DS 2-02.2.1.A.10). If the existing and future SVTs are coincident, label it as both existing and future.

2. Locate driveways on adjacent properties to verify compliance with driveway spacing requirements of Tucson City Code Chapter 25 and Access Management Guidelines

3. Show dimensioned ROW width. Include existing and future ROW for those streets that are on the MSRP. (DS 2-02.2.1.A.19) This plan shows something that might be a dimension but it is so small it is illegible.

4. Provide 25' radius curb returns at the access point.

5. Note 2 has "striped" misspelled.


D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
02/27/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied February 27, 2006

TO: David Stewart
MW2 Development

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: New Duplexes Glenn East
Record of Survey – 1st Submittal
S06-002

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

ALL SHEETS. Add the project number, S06-002, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates.

SHEET 1. If any new sewers are proposed, add the following General Note

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.




SHEET 1. If any new sewers are proposed, add the following General Note

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

Add the following General Note

ANY WASTEWATER DISCHARGED INTO THE PUBLIC SANITARY SEWERAGE SYSTEM SHALL MEET THE REQUIREMENTS OF THE INDUSTRIAL WASTE ORDINANCE (PIMA COUNTY ORDINANCE NO. 1991-140, AS AMENDED).

Add the following General Note

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

Add the following General Note

ANY RELOCATION, MODIFICATION, ETC., OF THE EXISTING UTILITIES AND/OR PUBLIC IMPROVEMENTS REQUIRED BY THIS DEVELOPMENT WILL BE AT NO EXPENSE TO THE PUBLIC.

Show the size and Pima County plan number for the existing public sewer to which this project would be connecting/is already connected.

Show the six-digit Pima County manhole number for any existing public manhole shown on the layout.

Show the length, size and slope for all newly proposed sewers.

It is assumed that there will be different owners of property sharing the use of the private sewers. If that is the case, this project will require a Joint Use And Maintenance Agreement. Please contact Ilene Deckard (Pima County Wastewater Management Department) at (520) 740-6544 to coordinate this matter. If each owner of property, will not share the use of their respective private sewer line, you may disregard this comment.

It appears that this project proposes connecting to an existing public sewer line 15 inches in diameter or larger. This existing public sewer line conveys high volumes of wastewater, therefore the owner, engineer and contractor shall be aware that a flow management plan may be required. The owner, engineer and contractor shall also be aware that Pima County Wastewater Management Department may require review of this project.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
03/01/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: S06-002
3711 - 3719 E. Glenn
Commercial Site plan
1st Review

TRANSMITTAL DATE: March 1, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This plan was reviewed in accordance with requirements of the Land Use Code (LUC), Development Standards (DS), American National Standard Institute (ANSI), and International Building Code 2003 (IBC). For reference, see DS 2-08 for pedestrian access, DS 2-09 for bicycle parking, 3-01 for sight visibility triangles and 3-05 for vehicular circulation requirements.

2. This project was reviewed under requirements for a commercial site plan, DS 2-02, rather than as a CDRC process for the lot line reconfiguration, as was submitted. This project comprises of 4 new residential apartment units and a lot line reconfiguration between two lots. Thus, the project was review for commercial site plan content, and should be resubmitted through the permit counter as a commercial site plan for further reviews.

3. This project was reviewed under full code compliance requirements, as the two lots will be functioning as one site and the increase in both lot area and building area are greater than 25% of the existing development.

4. Per 2-02.2.1.4 - Revise the location map to include the township, range and section numbers where the project is located, and adjacent. The scale of the drawing must be 3" is equal to 1 mile.

5. Per 2-02.2.1.6 - Provide the height for all buildings, existing and proposed.

6. Per 2-02.2.1.7 - Provide proposed and existing building setbacks to all applicable adjacent existing/proposed lot lines. (Further comments may be forthcoming, as it appears existing building setbacks at the east site are within the required setback.)

7. Per 2-02.2.1.8 - With regards to parking:
A) Provide dimensioned back up spurs near parking space 8 and near building 3715.
B) Provide distance between building 3711 and existing parking space, show curbing.
C) Number all parking spaces
D) clarify if area between proposed lot line and building 3717 is a parking area.
E) clarify use of area directly to east of building 3715, provide curb if not vehicle area.
F) Dimension distance from wheel stop barrier to front of parking space, and proximity of space to property line.
G) Note if walls proposed anywhere on property.
H) Provide a shared access/parking agreement between lots.

8. Per 2-02.2.1.9- Provide bicycle parking per ratio described in LUC 3.3.4 mult-ifamily residential parking requirements of 0-70 units, meeting standards of DS 2-09.

9. Per 2-02.2.1.10 - Provide existing and future sight visibility triangles.

10. Per 2-02.2.1.11 - Show all curbing for Parking Area Access Lane, and dimension width of PAAL with curbing at the crosswalk area proposed at the new property line.

11. Per 2-02.2.1.12 - A continuous (raised from asphalt) concrete sidewalk is required throughout the site, from Glenn Street to all buildings, including existing buildings. Revise plan to show the sidewalks leading to all buildings, and being made of concrete raised from the asphalt.

12. Per 2-02.2.1.12 - Handicapped circulation is not provided on this site. Provide a typical detail drawing of a handicapped ramp, at a 1:12 slope maximum, with notation on the plan showing handicapped ramps at all areas where transitioning from pedestrian to/across vehicular use areas. Per ANSI, ensure early warning systems (truncated domes) are provided on all handicapped access ramps.

Clarify what appears to be crossing/blocking the sidewalks at the new buildings - access cannot be compromised.

13. Per 2-02.2.1.13 - Clarify if any signage is proposed, or free-standing lighting. Provide details drawings with heights and dimensions if applicable.

14. Per 2-02.2.1.19 - Glenn Street is a Major Streets and Routes with a future right of way of 64 feet. Dimension Glenn Street, labeling both the centerline and the future/existing curb locations.

15. Per 2-02.2.1.20 - Provide easement agreement allowing access to rear (north) parcel over parcel abutting Glenn Street. Provide easement for electric power pole, with recordation information. (further comments may be forthcoming).

16. Per 2-02.2.1.32 - provide trash container and enclosure - see engineering for further details.

17. Per 2-02.2.1.38 - list any prior LDOs or Board of Adjustment variances, with paperwork, that may have been obtained for the site (reduced setback permission, etc.).

18. Per 2-02.2.2.A.1. - list the lot coverage calculations for each lot.

19. Please note, depending upon the responses provided, further review comments may be forthcoming. Should you have any questions on this review, please contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.

If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\3711 e glenn.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/02/2006 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Needs Review
03/02/2006 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
03/02/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 2, 2006

David Stewart
MW2 Development
3326 North Winstel Blvd
Tucson, Arizona 85716

Subject: S06-002 Glenn Street Duplexes East Record of Survey

Dear David:

Your submittal of January 30, 2005 for the above project has been reviewed by the Community Design Review Committee. After submittal of this plan, it was discovered that a Record of Survey is not required. The correct review process is a Commercial Site Plan review. The comments on line should be reviewed and addressed prior to submittal of the commercial site plan.

A commercial site plan review requires two (2) rolled sets of all plans required (site, landscape, NPPO etc…) and all drainage documents required. The City of Tucson will transfer the fees already paid to the correct account so there will be no fees required when the commercial site plan is submitted. Please bring a copy of this letter with you to DSD when submitting the site plan. Should you have any trouble submitting the commercial site plan please ask for Beth Grant or myself for assistance





Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 318-4486