Plan Number: S05-255
Parcel: Unknown

Address:
1979 E AJO WY

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S05-255
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/17/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: SOUTHGATE BUSINESS PARK
S05-255



Tucson Electric Power Company (TEP) has reviewed the final plat
submitted August 4 , 2006. TEP is unable to approve the plat at this
time.



In order for this Company to approve the final plat, the following is
required:

* Add the following paragraph to the dedication:

"An easement is granted for the purpose of access, installation
replacing repairing and maintenance of electrical meters, cable and
conduits, which grouped electrical meters are attached to the exterior
walls."



Show the dedication on the re-submittal of the plat and submit one copy
of the plat to the City of Tucson for TEP's final approval. Any
additional easements will be required by separate instrument.



Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
08/23/2006 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S05-255
Southgate Business Park
Final Plat

TRANSMITTAL DATE: August, 4, 2006

DUE DATE: September 1, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. An applicant has one (1) year from the date of approval of tentative plat to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before April 23, 2007.

2. Case number S06-255 has been assigned to this final plat. Please add the case number to the lower right corner all sheets of the final plat.
DS 2-03.6.1.K

3. Please correct General Note 4. Co9-02-032 should be C9-02-032.

4. Please provide width of the ingress/egress easement on sheet 2 of 5 and the public utility easement on sheet 3 of 5 of the final plat.
DS 2-03.6.4.A

5. Please include the square footage for all units on the final plat.
DS 2-03.6.4.B

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA C:\planning\cdrc\finalplat\S05-255fp.doc


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
08/25/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: PIMA COUNTY SUBDIVISION COORDINATOR
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-255 SOUTHGATE BUSINESS PARK/FINAL PLAT
DATE: August 24, 2006


********************************************************************

The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.



***The Pima County Addressing Section can use digital CAD drawing files when submitted with your final plat Mylar. These CAD files can be submitted through the Pima County Subdivision Coordinator. The digital CAD drawing files expedite the addressing and permitting processes when we are able to insert this digital data into the County’s Geographic Information System. Your support is greatly appreciated.***







jg
08/31/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approv-Cond Office of the Pima County Assessor


115 N. Church Ave.


Tucson, Arizona 85701



BILL STAPLES

ASSESSOR










TO: CDRC Office

Subdivision Review

City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor

Pima County Assessor's Office

Mapping Department



DATE: August 31, 2006





RE: Assessor's Review and Comments Regarding Final Plat

S05-255 SOUTHGATE BUSINESS PARK T141430



* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *



X Plat meets Assessor's Office requirements.(SEE COMMENTS BELOW)

_______ Plat does not meet Assessor's Office requirements.





COMMENTS: AS REQUESTED IN THE PREVIOUS COMMENT LETTER, PLEASE REFERENCE
SEC 30 IN THE TITLE BLOCK BEFORE RECORDING.

THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL
ROSANNA WERNER AT 740-4390.



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS
TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN
THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING
THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK
YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.











ROSANNA WERNER

520-740-4390
09/11/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S05-255 Southgate Business Park: Final Plat Review - No comment.
09/13/2006 FRODRIG2 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
09/14/2006 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond May 31, 2006

TO: Tri Miller
Rick Engineering Company

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Chandubhai C. Patel, P.E.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Southgate Business Park, Block A, Units 1-37
Final Plat – 1st Submittal
S05-255

The drawings for the Final Plat of the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


All Sheets. Show the project number S05-255 with large and bold letters. Delete the number S06-.

All Sheets. Add the word FINAL between the words Condominium and Plat in the Title Blocks.

Add the following notes in the GENERAL NOTES:

ALL ON-SITE SEWERS ARE PRIVATE.

ALL LANDSCAPING WITHIN 10 FEET OF ANY PUBLIC SEWER, IN THE COMMON AREAS OR PUBLIC SEWER EASEMENTS SHOWN HEREON, SHALL BE IN ACCORDANCE WITH GUIDELINES OF PC/COT STANDARD DETAIL WWM A-4.

NO PERMITS SHALL BE ISSUED FOR ANY PERMANENT STRUCTURES WITHIN 10 FEET OF ANY PUBLIC SEWER, IN THE COMMON AREAS OR PUBLIC SEWER EASEMENTS SHOWN HEREON, WITHOUT SEPARATE WRITTEN CONSENT OF THE PCWMD.

Dedication Block: In the first line of the second paragraph, following the word PUBLIC, add: ,CITY OF TUCSON, PIMA COUNTY

Dedication Block: In the third line of the fourth paragraph, following the word Public, add:
, CITY OF TUCSON, PIMA COUNTY

Sheet 2. Where the sewer easement is shown, add the word Public to read Public Sewer Easement, and show the width of this easement.

Sheet 2. Show the widths for all easements shown on this drawing.

8. Sheet 3. Show the widths for all easements shown on this drawing.

Subject to satisfactorily addressing the above comments, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat as received by us on August 3, 2006.

Please note the following: Approval of the above referenced submittal does not authorize
the construction of public or private sewer lines or water distribution lines. Prior to the
construction of such features, a Construction Authorization (Approval To Construct) may
need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the
Pima County Department of Environmental Quality prior to constructing, operating or engaging
in an activity which may cause or contribute to air pollution.

If you have any comments regarding the above comments, please do not hesitate to call me.

Sincerely,



Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: Project File
09/27/2006 LOREN MAKUS ENGINEERING REVIEW Denied DATE: September 27, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: Southgate Business Park
Final Plat S05-255 (First Review)
T14S, R14E, Section 30

RESUBMITTAL REQUIRED: Final Plat
The Final Plat has been reviewed by the Engineering Division and we do not recommend approval at this time. The following comments must be addressed.

1. Revise the Basis of Bearing to reference two found monuments that are fully described. It appears that the basis of bearing is depicted on the plat. If it is clearly indicated as the basis of bearing, no further descriptions are required. (DS 2-03.6.5.C.1)
2. The Final Plat shows two buildings over easements for TEP and for SW Gas. The Tentative Plat indicates that these easements are to be abandoned. Provide the recordation information for the abandonment of these easements. These easements must be abandoned before the approval of the Final Plat.
3. Explain in the response letter the assurance mechanism for this project. If a third-party land trust will be used, provide the appropriate beneficiary information on the plat.
4. Revise the Condominium Declaration or provide CC&Rs to address the required basin maintenance language as discussed in the drainage manual.

If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
09/29/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 29, 2006

Tri Miller
Rick Engineering Company
1745 East River Road, Suite 101
Tucson, Arizona 85718

Subject: S05-255 Southgate Business Park Final Plat

Dear Tri:

Your submittal of August 4, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

5 Copies Revised Final Plat (TEP, Zoning, Wastewater, Engineering, DSD)






Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 322-6956
fpresubmittal