Plan Number: S05-255
Parcel: Unknown

Address:
1979 E AJO WY

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S05-255
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/17/2006 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
03/21/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied March 21, 2006

TO: Tri Miller
Rick Engineering Company

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Southgate Business Park, Lots 1-5, Units 1-38
Tentative Plat – 2nd Submittal
S05-255

The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


ALL SHEETS. Add the project number, S05-255, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Two additional sheets were submitted with this plan, thus, an additional $100.00 should have been paid. Item 9 of this letter will include this amount for the next review.

Please follow the sewer improvement plan review comments provided for G-2006-026 and incorporate those that apply to this project accordingly so that they are synchronized.

SHEET 7. Show the proposed sewer all the way to its point of connection to the existing public sewer.

SHEET 7. Show the size of the existing public sewer to which this project is connecting.

SHEET 7. Show the same elevations for the storm drain and the proposed sewer at their crossing, so it matches the elevations shown on G-2006-026.

A revised Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents was sent to your office on March 20, 2006. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve of the tentative plat/development plan.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $139.00 ($39.00 for 3rd review + $100.00 for two additional sheets received with 2nd submittal) made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
03/24/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Denied ADOT has not received a copy of the traffic study on this project
* access control has not been shown on the plans - this needs to be defined
* the driveways on Ajo Way, SR-86, lie in ADOT jurisdiction and a permit will be required and built to ADOT standards
* there is no justification for two driveways on Ajo Way without proper documentation - one may be allowed?

If you have any questions or comments I can be reached at 620-5435. Thank you. TM.

*********************************************************************
Confidentiality and Nondisclosure Notice: This email transmission
and any attachments are intended for use by the person(s)/entity(ies)
named above and may contain confidential/privileged information.
Any unauthorized use, disclosure or distribution is strictly
prohibited. If you are not the intended recipient, please contact the
sender by e-mail, and delete or destroy all copies plus
attachments.
*********************************************************************
03/27/2006 PETER MCLAUGHLIN ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
S05-255
Southgate Business Park
Tentative Plat/Development Plan

TRANSMITTAL: March 27, 2006
DUE DATE: March 29, 2006

The Zoning Review Section at Development Services verifies that the tentative plat meets the requirements of the Land Use Code, subject to the following requirement. However, should there be any changes requested by other CDRC members, the approval is void, and we request copies of the corrected tentative plat to verify that those changes do not affect any zoning requirements.

1. All sidewalks must be ADA compliant with the required truncated domes rather than the grooves indicating grade changes and pedestrian crosswalks. Indicate the truncated domes on the tentative plat/development plan as required.
IBC/ANS

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
03/29/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-255 SOUTHGATE BUSINESS PARK/REVISED TENTATIVE PLAT
DATE: March 28, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

INDIVIDUAL BUILDING ADDRESSES AND UNIT NUMBERS WILL BE ASSIGNED TO THE CONDO UNITS UPON RECORDATION OF PLAT.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***








jg
03/30/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S05-255 Southgate Business Park: Resubmittal - CDRC - Tentative Plat. No Comment.
04/03/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-255 Southgate Business Park 03/31/06

(X) Tentative Plat/Development Plan
()
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-02-32

NEIGHBORHOOD PLAN: Kino Area Plan & Western Hills/Pueblo-Sunland Gardens

GATEWAY/SCENIC ROUTE: No

COMMENTS DUE BY: March 29, 2006

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 1/23/06








REVIEWER: msp 791-4505 DATE: 3/29/2006
04/10/2006 LOREN MAKUS ENGINEERING REVIEW Approved DATE: April 10, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: Southgate Business Park
Tentative Plat S05-255 (Second Review)
T14S, R14E, Section 30

RESUBMITTAL REQUIRED: Tentative Plat (See below)
The Tentative Plat and Drainage Report have been reviewed by the Engineering Division and we recommend approval at this time. The Engineering Division Requests a copy of future submittals since comments by other reviewers may result in changes that may impact the Engineering Division approval. If any changes are made to the vehicle use areas, the resubmittal must demonstrate that loading zones and solid waste enclosures are accessible.

Please note that a Stormwater Pollution Prevention Plan will be required as part of the grading permit submittal.

If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
04/13/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP submittal:

1. Tucson City Code Chapter 25 Section 39 states that the maximum driveway width for business districts is 35'. A 3-lane section for the entrance can be accommodated with 2-12' lanes and 1-11' lane.

2. The northern most access point does not seem to satisfy rezoning condition 15. While the submitted TIA states that this access does not meet numerical warrants for a deceleration lane, there are horizontal and vertical alignment changes that also need to be taken into consideration. And, a deceleration lane is a condition of rezoning. The Developer has the option to seek a change of rezoning conditions, but Traffic will not support such a request.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
04/14/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

April 14, 2006

Tri H. Miller
Rick Engineering, Co.
1748 E. River Road, Suite 101
Tucson, Arizona 85718

Subject: S05-255 Southgate Business Park Tentative Plat

Dear Tri:

Your submittal of December 21, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

4 Copies Revised Tentative Plat (ADOT, Wastewater, Traffic, DSD)

3 Copies Traffic Impact Analysis (ADOT, Traffic, DSD)



Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager