Plan Number: S05-252
Parcel: Unknown

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S05-252
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/17/2006 JIM EGAN COT NON-DSD FIRE Denied 1. A minimum 20 feet wide, paved, fire access roadway must be provided and extedned to within 150 feet of all portions of the exterior walls of all structures.
2. An approved turnaround, dimensioned in accordance with COT Dev. Standard 3-01 must be provided. No center islands permitted.
3. Fire hydrants required. Provide a note on the plan stating "Additional fire hydrants shall be provided by the developer in accordance with the Tucson Fire Code."
01/30/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* 5 individual lots off of a col-de-sac off Ft. Lowell Road. Approved for APC service off the dead end cul-de-sac road. APC to be placed and removed from the curbside collection area on the day of service.
02/07/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: FT. LOWELL PLACE

S05-252



Tucson Electric Power Company has reviewed and approved the minor
subdivision plan submitted January 11, 2006.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Warren McElyea

Design/Build - DB 102

Tucson Electric Power
Company

P. O. Box 711

Tucson, AZ 85702



Please call me at (520) 917-8745, should you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
02/08/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: February 7, 2006
CDRC/Zoning Manager

SUBJECT: 5020 E. Fort Lowell Road
Final Plat S05-252 (First Review)
T14S, R15E, Section 14


RESUBMITTAL REQUIRED: Final Plat and Drainage Report.


The Final Plat (FP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. The proposed street width does not meet development standards per D.S. 3-01.0. A Development Standard Modification Request (DSMR) will be necessary for the proposed street width.
3. Subdivisions over an acre equal to 3 units but not greater than 6 units are required to provide 2-year threshold retention.
4. Show detention/retention areas in a surveyable and readily retraceable manner per D.S. 2-03.6.4.I.
5. Show the subdivision case number (S05-252) in the lower right corner of the plat next to the title block per D.S. 2-02.6.1.K.
6. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used:
· Title Report
· Special Warranty Deed
· Trust Agreement
· Amendment to Trust
· Agreement to Construct
Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.
7. The title block of the plat must match the Subdivision Assurances verbatim.
8. Please re-label all common areas that may be used in a dual and/or single use capacity per D.S. 2-03.6.4.C. For example, a Ret./Det. Basin may also be used as a recreation facility or only as a drainage facility or drainage channel and this must be reflected on the Final Plat. A key note explaining the labels could be used in conjunction with the labels, ie.:
Common Area "A" - Streets
Common Area "B" - Drainage/Recreation Facilities
Common Area "C" - Recreation Facilities
Common Area "D" - Drainage Facilities
Common Area "E" - Landscaping
9. Show sight visibility triangles per D.S. 2-02.2.1.10.
10. Correct the mile of new public street on general note 3 per D.S. 2-03.6.2.C.
11. Show a 1' no access esmt. along the East property lot lines per D.S. 2-03.6.3.A.
12. At least one corner of the subdivision will be tied by course and distance to a section corner, a quarter corner, or an established……….per D.S. 2-03.6.5.A.
13. Show the distance and bearing between all monuments used…per D.S. 2-03.6.4.C.5.
14. Complete "Basis of Elevation" per D.S. 2-03.6.5.C.
15. Please submit a copy of the subdivision boundary closure calculations.

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The DR states that only 1 house will be constructed on the site. If not, a future condition hydrology data sheet must be included in the DR.
3. Subdivisions over an acre equal to 3 units but not greater than 6 units are required to provide 2-year threshold retention.
4. Show all details of and cross sections of the proposed basin.
5. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.
6. Correct the address listed on the DR.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/5020 E. Fort Lowell Rd. FP
02/08/2006 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The site does have special development requirements, the Watercourse Amenities, Safety, and Habitat (WASH) ordinance and the Native Plant Preservation ordinance.
LUC 4.2.2.I

2) The native plant preservation application is denied. We find that the project may have a substantial impact on protected native plants. A native plant preservation plan will be required.

3) The WASH ordinance is applicable to this site. A plant/habitat inventory and is required for any
development within 50' of the banks of the wash. Additional requirements apply for any resource area development. TCC 29-12. The review procedure is specified in TCC 23A-51.
02/09/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied February 8, 2006

To: Lloyd Rogers, Rogers Civil Engineering

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: 5000 Ft. Lowell Place Lots 1-4
Final Plat - 1st Submittal
S05-252

The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



This project will be tributary to the Ina Road Water Pollution Control Facility and the Roger Road Wastewater Treatment Facility via the South Rillito Central Interceptor. Per written guidance provided by the PCWMD Development Services Section, sufficient conveyance and treatment capacity exists in the downstream public sewerage system for this small project, and a formal capacity response letter from the PCWMD will not be required for this project.

How do you intend to provide sewer service to these lots? Provide this office with a separate utility improvement plan that shows all public and private sewers (and easements) necessary to provide sewer service to these lots.

Note: The sewer improvement plan for 5068 E. Ft. Lowell Rd., G-2002-116, (that might have provided public sewer service to the boundary of this subdivision) has expired and the construction plans have been purged from our map racks.

All Sheets: Add the final plat case number, S05-252, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers. No wastewater review fees will be charged for sheets where this is the only required revision.

Sheet 1: Revise the plat map so that:

The lot numbers that appear on sheet 1 are changed so that they match the lot numbers that appear on sheet 2.

Sheet 2: The easement label is incomplete and does not allow for INGRESS. Revise the site plan so that:

The off-site easement, west of the project boundary, is correctly labeled and the appropriate recording information, docket and page, is included.

The on-site easement is correctly labeled with appropriate recording information, by final plat.

We will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
02/09/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this Final Plat:

1. The proposed access road for this subdivision does not meet DS 3-01.0 figure 2.

2. Local streets must be designed with parking on both sides of the street, unless parking is provided in common areas distributed throughout the subdivision, at a ratio of one parking space per dwelling within the subdivision. (DS 3-01.2.4.D)

3. The proposed cul-de-sac does not meet DS 3-01.0 figure 21.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
02/09/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-252 5000 FORT LOWELL PLACE / MINOR SUBDIVISION REVIEW
DATE: February 8, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Correct Sections on Location Plan.

2: Correct legal description on all Title Blocks.
02/10/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: February 10, 2006


RE: Assessor’s Review and Comments Regarding Final Plat
S05-252 5000 Fort Lowell Place T131435 (110-10)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Susan King
02/17/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-252 5000 Fort Lowell Place 02/16/06

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – Final Plat

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Old Fort Lowell

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 2/9/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP –

Note: To enhance public safety and reduce the incidences of crime, “Safe by Design” concepts consider incorporating the following:

Where perimeter walls are provided along lot lines that abut designated open areas, common areas, and trail system, the masonry portion of the wall is not to exceed three (3’) feet in height, except for pillars, with wrought iron or other similar open fencing materials on top.

() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:



REVIEWER: D. Estolano 791-4505 DATE: 2/2/06
03/01/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied DATE: March 1, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: S05-252 5000 Fort Lowell Place:Minor Subdivision Review

Denied.

The site is adjacent to Alamo Wash Linear Park.
Show the east and west boundaries of the drainage easement over Alamo Wash.
Staff finds that native plants will be impacted.
03/29/2006 FRODRIG2 ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
S05-252
5020 East Fort Lowell Road
Minor Subdivision (Group B)


TRANSMITTAL: April 4, 2006


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1) An applicant has one (1) year from the date of submittal of a minor subdivision to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before December 15, 2006.

2) This review is for a Group B Minor Subdivision (LUC Section 4.2.2.2) in the in the R-1 zone (LUC Section 2.3.4.2.A.1). The Development Designator is "G" for each individual lot and is subject to Section 3.5.7.1.E, .F, .G, and .H. The Perimeter Yard Indicator is AA for each lot (LUC Sections 3.2.3.1.B and 3.2.6.4). Please place a note stating that each individual lot must comply the requirements of the Land Use Code and Development Standards on the plat and any related Development Plan.

3) Please place the subdivision case (S05-252) number in the lower right corner of the plat and any other related sheets, such as the landscape plans, NPPO and grading plans (DS 2-03.6.1.K).

4) Please identify the conditions within the square mile area of the small projection map in the upper right corner. Identify the subdivisions plats by name with the book and page recording information. Also identify all major streets and major watercourses on the Final Plat (DS 2-03.6.1.D.2).

5) Please revise the APPROVAL note to read: " I, Kathleen S. Detrick, Clerk of the City of Tucson, Arizona, hereby certify that this plat was approved by the Mayor and Council of the City of Tucson, Arizona, on this _____ day of _______, 2006." (See DS 2-03.6.3.D.)

6) Clearly delineate the street. The minimum street width is twenty-four feet (24') without parking lanes and thirty-two feet (32') with parking lanes on each side of the street (DS 3-01.2.3.A.1). The minimum width for a parallel parking lane is seven feet (7') with a vertical curb (DS 3-01.2.4.A). Please revise the street to the proper width.

7) "Local streets must be designed with parking on both sides of the street, unless parking is provided in common areas distributed throughout the subdivision, at a ratio of one parking space per dwelling within the subdivision" (DS 3-01.2.4.D). "Visitor parking spaces should be provided within one hundred fifty (150) feet of the front or street side yard property lines of each residential unit" (DS 3-05.2.4.A.1). If one street parking is not provided there must be five (5) common area guest parking spaces provided within the one hundred fifty feet (150') of each front property line. Please revise the plans.

8) Clearly delineate the floodplain setback. Also provide an individual plot plan for Lot 5, with dimensioned elevations and a basic floor plan.
03/29/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Needs Review
03/29/2006 FRODRIG2 COT NON-DSD REAL ESTATE Needs Review
03/29/2006 FRODRIG2 ZONING-DECISION LETTER REVIEW Needs Review
03/29/2006 FRODRIG2 ZONING-RECORDATION REVIEW Needs Review
03/29/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Needs Review