Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-222 Vasquez Plat 01/05/06

(XXXX) Tentative Plat
() Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Santa Cruz Area Plan

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 12/28/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 12/22/05
01/07/2006 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S05-222
Vasquez Plat - 150 S. Sentinel Peak Rd.
Tentative Plat

TRANSMITTAL: 01/07/06

DUE DATE: 12/28/05

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is 12/27/06.

2. DS 2-03.2.1.D.2, & .3 A small, project-location map will be provided, drawn at a scale of 3" = 1 mile. The location map will provide the following information.

2. Identify conditions within the square mile area, such as subdivisions, major
streets, major watercourses, and railroads. Reference recorded subdivision plats by book and page numbers.

3. Section, township, and range; section corners; north arrow; and the scale will be labeled. The range and section numbers are incorrect on the plan. Please correct.

3. DS 2-03.2.1.G, & .2 A title block with the following information is to be provided approximately in the lower right corner of the first page of the plat.

2. The number of proposed lots is to be noted.

4. DS 2-03.2.2.A.1 Ownership and Preparation Notes.

1. List the names, addresses, and telephone numbers of the primary owner of
the site and the developer of the project.

5. DS 2-03.2.2.B.1 This project has been assigned the case number S05-222, list in the lower right corner next to the title block of all pages of the plat including the landscape and NPPO pages.

6. DS 2-03.2.4.A Draw in all proposed lot lines with approximate distances and measurements.

Remove topographic and section lines from the tentative plat for clarity purposes. If required by other CDRC reviewers a separate sheet with the required information may be attached.

Change the line weight of the boundaries of the subdivision along the north property line between the City of Tucson property and the subdivision property, in order to clearly define the boundaries of this subdivision.

Change the line weight of the new lots to a more legible thickness (not dashed lines) for clarity purposes.

The lot dimensions provided along the southern boundary of the subdivision for the proposed lots do not appear to be correct. Please change.

The lot dimension on the west property line of lot #2 does not appear to be correct. Please clarify.

7. DS 2-03.2.4.B Identify each block or lot by number within the subdivision boundary and include the approximate square footage of each.

The indicated square footage for lots #1 & #2 appear to be in conflict. Lot #2 does not appear to be twice the size of lot#1. Lot #3 does not appear to include in the square footage the area called out as an ingress/egress easement, which is part of lot #3. Please clarify.

8. DS 2-03.2.4.J All proposed easements (utility, sewer, drainage, access, etc.) are to be
dimensioned and labeled as to their purposes and whether they will be public or private.

Provide docket and page recordation information as well as dimensions for the existing easement for El Paso Natural Gas.

It appears the ingress/egress easement along the northern edge of the subdivision is serving all three lots. If this is the case a street designed to meet Development Standards 3-01 is required. Full 51' R.O.W. width, sidewalks, curbs, visitor parking on both sides of the street, etc.

If a driveway is provided from lot #1 directly to Sentinal Peak Rd. (not using the ingress/egress easement) then the proposed ingress/egress easement can serve the two single family residences to the rear without being an improved street. If this is the case a one (1) foot no access easement will be required along the north and west property lines of lot #1. Clearly indicate the location of the driveways for all 3 lots on the plat.

An easement will be required for the indicated sewer lines from lots 2 &3 which cross lots 1 and 2 or relocate the indicated sewer lines into the utility easement to the north.

Clearly indicate the location of all existing utilities for lot #1.

9. The density calculations provided indicate that 2 units are being designed for each lot. If this is an error please correct. If this is not an error and two units are proposed for each lot a street will be required as in comment #8.

10. The lot coverage calculations provided appear to be incorrect. The size of the lots are incorrect (see comment #7). The vehicular use areas are the same for all three lots which does not appear to be correct. The vehicular use areas are to include driveways (the ingress/egress easement is considered a driveway for lot #3), carports, and or garages (see comment #8).

11. As per the Pima County Assessors records the existing house on lot #1 is a two-story structure. The height of the structure is indicated as 10', if this is an error please correct. If this is not an error provide documentation verifying the height of the existing structure.

12. Based on responses to the above comments and changes to the plat, further comments may be forth coming.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext 2000.

TLS C:\planning\cdrc\tentativeplat\S05-222tp.doc
01/09/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied January 8, 2006

TO: Charles Corrales
Corrales Engineering Corp.

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Anacleto Vasquez, 150 S Sentinel Peak Road
Tentative Plat – 1st Submittal
S05-222


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the Northwest Outfall Interceptor. Due to the insignificant amount of flow expected from this project, a capacity response letter will not be required.

An evaluation to analyze if this project is Participating or Non-Participating will be done during the review of the second submittal.

Add the project number, S05-222, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Add the following General Note

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.





Add the following General Note

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

Show all existing public sewers within 100 feet of the project boundaries. Include the size and Pima County plan number.

The legend must match the line types used in the layout of this plan. Use different line types for existing public sewers, existing private sewers and proposed private sewers.

Show the length, size and slope of any proposed private sewes.

Show the proposed/existing private sewers all the way to their point of connection with the existing public sewer.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
01/12/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied S05-222; Vasquez; Easements shown on the Preliminary Title Report not shown on plat.
01/26/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: December 30, 2005


RE: Assessor’s Review and Comments Regarding Tentative Plat
S05-222 Vasquez Plat T141314 (116-21)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal. Please make the following additions/corrections in the final plat.
Add the number of Lots in the title block.
Make the lot lines solid and show what the actual lots will be.
If there are any questions, please contact Susan King at 740-4391.


NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Jessica Shettleroe
01/30/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 30, 2006

Charles Corrales
Corrales Engineering Corp.
1008 West Saint Mary's Road
Tucson, Arizona 85745

Subject: S05-222 Vasquez Plat Tentative Plat

Dear Charles:

Your submittal of November 30, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

9 Copies Revised Tentative Plat (Real Estate, TEP, Traffic, Wastewater, Addressing, Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape and NPPO Plans (Engineering, Landscape, Zoning, DSD)

2 Copies Revised Drainage Report (engineering, DSD)




Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 622-2553
11/29/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/01/2005 JIM EGAN COT NON-DSD FIRE Approved The Tentative Plat is approved per General Note #9.
12/02/2005 DBELL1 LANDFILL ENVIRONMENTAL SERVICES Approved
12/05/2005 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this lot split.
* Approved for APC curb side sertvice for individual residences.
* APC's are to be placed and removed from the curb side collection area on the day of service.
12/06/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
SO5-222
CORRALES ENGINEERING CORP
VASQUEZ PLAT
*********************************************************************
Confidentiality and Nondisclosure Notice: This email transmission
and any attachments are intended for use by the person(s)/entity(ies)
named above and may contain confidential/privileged information.
Any unauthorized use, disclosure or distribution is strictly
prohibited. If you are not the intended recipient, please contact the
sender by e-mail, and delete or destroy all copies plus
attachments. Neither the State nor the Arizona Department of
Transportation and/or its employees shall be liable for violations of
law, or damages resulting from your dissemination or use of this
email transmission if you are not the intended recipient.
*********************************************************************
12/09/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-222 VASQUEZ PLAT / TENTATIVE PLAT
DATE: December 8, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Delete street directions.

2: Correct Location Map Scale & Sections.

3: Change range 14E to 13E and section 13 to 14 under Location Map.

4: Spell out all street suffixes except on Location Map.

5: Delete address on Title Block.

6: Add lots 1-3 on Title Block.

7: What do sections #1 - #5 represent?

8: Recorded deeds with legal descriptions will be required in order to assign
addresses.

9: Change Sentinal Peak Rd. to Sentinel Peak Road on pg. 1.
12/22/2005 JOE LINVILLE LANDSCAPE REVIEW Denied The native plant preservation plan requires revisions due to the grading proposed north of the future home location on lot 2. Preservation in plce may not be feasible within the requirements of the code due to the proposed pad development.

In order to meet the requirements the existing grade would have to be retained for 1.5 times the dripline radius of the trees. Revise as necessary.
12/22/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: December 21, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: S05-222 Vasquez Plat: Tentative Plat Review


Staff has no comments.
12/23/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: VASQUEZ PLAT

S05-222



Tucson Electric Power Company (TEP) has reviewed the plans submitted
November 30, 2005. TEP is unable to approve the plans at this time.
There are existing electrical facilities within the boundaries of this
project. In order for TEP to approve the plans, the facilities and
easement recording information must be depicted on the plans.



Enclosed is a copy of a TEP facility map showing the approximate
location of the existing facilities.



Please resubmit two revised bluelines to the City of Tucson for TEP's
review. You may contact me at (520) 917-8745 if you have any questions.




Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
12/23/2005 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Estimated daily traffic in 24 hr period - 38
12/28/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: January 4, 2006
CDRC/Zoning Manager

SUBJECT: Vasquez Plat, 150 S. Sentinel Peak Rd
Subdivision Plat S05-222 (First Review)
T14S, R13E, Section 14

RESUBMITTAL REQUIRED: Subdivision Plat and Drainage Report.

The Subdivision Plat (SP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Subdivision Plat:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. This project, because of the existing basin and access requirements does not seem feasible in its current layout. At this time, the DR comments must be addressed first prior to any other issues from engineering can be addressed.

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. This review was performed for Tentative Plat purposes only. Final review and acceptance will be at the grading plan stage.
3. All weather access must be provided per SMDDFM chap. 11.01.
4. Provide stage storage relationship relating to basin encroachments.
5. 100-year ponding limits and the future 100-year floodplain are shown to be going through lot 2 residence site. Please address.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/150 S. Sentinel Peak Rd.cdrc
12/29/2005 DALE KELCH COT NON-DSD TRAFFIC Denied >>> Dale Kelch 12/28/2005 11:21:30 AM >>>
Traffic Engineering REJECTS this TP:

1. List the name, ROW width, recordation data, type and dimensioned with of paving, curbs, curb cuts and sidewalks. (DS 2-03.2.3.D). Only the name is listed for Sentinal Peak Road.

2. Show and label as to size (ie 20x110) both existing and future SVTs (DS 2-03.2.4.M). If the existing and future SVTs are coincident, label it as both existing and future. Provide these at the new access point to the Development.

3. General note 6 states that this will be a private road. Will this road provide access to the 2 new structures as well as the existing structure? If this is the case, private roads still need to meet public street sections. Provide a cross-section for the proposed road. Local streets must be designed with parking on both sides of the street, unless parking is provided in common areas distributed throughout the subdivision, at a ratio of one parking space per dwelling within the subdivision. (DS 3-01.2.4.D). If this new access is meant to only provide access to the new structures, then it may be a mere driveway. If this is the intent, show where the new and distinct access to the existing structure will be bearing in mind the separation requirements for driveways as stated in Ch25-38 of Tucson City Code.

4. If this is going to be a road then the new proposed street appears to be greater than 150' in length. A turnaround will be required. (DS3-01.6.2.B)

5. What are sections 1-5 meant to depict on this plan set? Where are the sections?

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov