Plan Number: S05-196
Parcel: Unknown

Address:
1246 E 16TH ST

Review Status: Completed

Review Details: RECORD OF SURVEY REVIEW

Plan Number - S05-196
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied There are no real estate action items here unless the developer decides to purchase the undeveloped right of way abutting its project as suggested months ago. If, however, the undeveloped right of way is not sold to the abutting owners, the developer should be required to improve the right of way to TDOT's satisfaction.

One option or mechanism to accomplish the improvements, with TDOT's approval, may be through an improvement district with the other abutting property owner participating in the improvement. Otherwise, a bond and assurances should be issued.

It should also be noted that the other abutting property owner has and is constructing units along the east side of Mountain (1320 E 16th and 610 S. Highland). Since these are likely site plans that Real Estate will not see, please apply the same conditions to these properties as stated above for S05-196.
01/04/2006 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Needs Review COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES



January 4, 2006
Liz Farkas
Rob Paulus Architect, LTD.
116 East Congress Street
Tucson, AZ 85701

Subject: S05-196 16th and Mountain Record of Survey

Dear Liz:

Your submittal of October 26, 2005, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Record of Survey (wastewater, real estate, engineering, zoning, addressing, DSD)









Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 622-8334
01/06/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied see comments under recordation
10/26/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/28/2005 JOE LINVILLE LANDSCAPE REVIEW Approved
10/28/2005 JIM EGAN COT NON-DSD FIRE Approved The plan is approved October 28, 2005.
11/01/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: 16th & Mountain

S05-196



Tucson Electric Power Company has reviewed and approved the plans
submitted October 26, 2005.



In order to apply for electric service, call the New Construction
Department at (520) 770-2062. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Mike Kaiser

Design/Build - DB 102

Tucson Electric Power
Company

P. O. Box 711

Tucson, AZ 85702



Please call me at (520) 917-8745, should you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
11/07/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S05-196
ROB PAULUS ARCHITECT, LT
16TH & MOUNTAIN
*********************************************************************
Confidentiality and Nondisclosure Notice: This email transmission
and any attachments are intended for use by the person(s)/entity(ies)
named above and may contain confidential/privileged information.
Any unauthorized use, disclosure or distribution is strictly
prohibited. If you are not the intended recipient, please contact the
sender by e-mail, and delete or destroy all copies plus
attachments. Neither the State nor the Arizona Department of
Transportation and/or its employees shall be liable for violations of
law, or damages resulting from your dissemination or use of this
email transmission if you are not the intended recipient.
*********************************************************************
11/08/2005 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* Residential lot split. Refuse service to be Automated Plastic Containers (APC) which will be picked up off 16th Street. Residents to place and remove the APC's from the collection area on the day of service. Screen storage area should be provided on the individual lot.
11/09/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-196 16th & Mountain 11/07/05

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(xxxxx) Other – Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Arroyo Chico

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY:

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 11/07/05
11/10/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-196 16TH & MOUNTAIN RECORD OF SURVEY REVIEW
DATE: 11/09/05



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Delete all street directions.

Add street name to Manlove and Avenue to Santa Rita on Location Map.

Correct Location Map scale.

Delete 1246 E. 16th St.

Spell out Avenue of Santa Rita Ave.

Recorded deeds with legal descriptions will need to be provided in order to issue addresses.
11/14/2005 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Denied November 10, 2005

To: Liz Farkas, Rob Paulus Arch.

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tim Rowe, P.E. (520-740-6563), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: 16th and Mountain - Record of Survey
Record of Survey - 1st Submittal
S05-196

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. This project will be tributary to the Roger Road Wastewater Treatment Facility via the Aviation Corridor to Santa Cruz Interceptor Sewer. Treatment and conveyance capacity within the downstream public sewer system exists for this very small project.

1. The applicable sewer connection fee rate cannot be determined at this time. The determination of applicable rate will need to be done at the time of issuance of building permits.

1. All Sheets: Add the subdivision exception case number, S05-196, to the title block of each sheet. This number should be shown larger or bolder than any cross reference numbers. No wastewater review fees will be charged for sheets where this is the only required revision.

1. My examination of the amended plat for the Manlove Addition, recorded at Book 3, Page 12, M&P does not confirm that the any of the easements shown on the Record of Survey and identified in Exhibits A-E were granted by that document. Advise / revise as necessary.

If these easement are proposed easements, the COT CDRC will require that they be granted by separate instrument, and the phrase PER DOCKET _______, PAGE _______ will need to be added to the labels for each of the easements. The blanks in these labels will need be filled in with the appropriate recording information before the Record of Survey can be recorded.

1. If Parcels B and C will share a private sewer line that connects to the public sewer system, a Joint Use and Maintenance Agreement must be prepared, reviewed and approved by PCWMD Development Services Section staff, and recorded, prior to the issuance of building permits for those parcels. Add a General Note that states:

PRIOR TO THE ISSUANCE OF BUILDING PERMITS FOR PARCELS B AND C, A JOINT USE AND MAINTENANCE AGREEMENT SHALL BE RECORDED FOR ANY SHARED PRIVATE SEWER LINE(S). PRIOR TO RECORDATION, THE REQUIRED AGREEMENT SHALL BE REVIEWED AND APPROVED BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

1. We will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

County Ordinance 2003-29 went into effect on April 11, 2003. This ordinance requires that a wastewater review fee be paid for each submittal of the Record of Survey. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER ) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
11/15/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: November 15, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: S05-196 16th & Mountain: Record of Survey Review


Staff has no comments.
11/15/2005 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved 29 estimated trips in a 24 hr period.
11/22/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this ROS.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
11/28/2005 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: Michael St.Paul
Planner Technician

PROJECT:
S05-196
1246 East 16th Street
Record of Survey
TRANSMITTAL:
November 25, 2005

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This review is for a Record of Survey, which is a subdivision exception, in the C-3 Zone (DS 2-03.11 and LUC Sec 2.5.5.2.F.1). The proposed use is a single family residence (SFR) on each lot. The Development Designator is "S" and the Perimeter Yard Indicator is CC (LUC Sec 3.2.3.1.D and 3.2.6.4).

2. There is limited access to proposed lots B and C. Therefore please provide a note, under "General Notes," that says: "Parcels B and C shall be limited to one single family residence (SFR) on each parcel." You may also include parcel A to insure consistency of your development, if you like.

3. The Record of Survey number is S05-196. Please place this information in the space you have provided above the title block.

4. Please provide the number of proposed lots (3) in the title block (DS 2-03.11.7F.3).

5. Please provide the phrase "a resubdivision of" before "Manlove Amended Lots 10 & 11 Blk 15…" (DS 2-03.11.F.4).

6. This Record of Survey was approved for submittal with the stipulation of being submitted with a Development Standards Modification Request (DSMR), but there is no DSMR provided; nor is there any apparent reason for a DSMR. Please tell us about this mysterious DSMR?
12/19/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: December 19, 2005

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: 16th and Mountain
Record of Survey S04-196 (First Review)
T14S, R14E, Section 18

RESUBMITTAL REQUIRED: Record of Survey

The Record of Survery has been reviewed by the Engineering Division and we do not recommend approval at this time. The following review comment must be addressed.

1. In accordance with the draft development standard for Records of Survey, a five foot sidewalk must be provided along the 16th Street frontage before the record of survey can be approved.

If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate