Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: S05-180
Parcel: Unknown

Address:
2364 E DREXEL RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S05-180
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/30/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S05-180
Tres Pueblos Norte
Tentative Plat Resubmittal

TRANSMITTAL DATE: January 30, 2007

DUE DATE: February 13, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per DS 2-03.2.4.F streets are to be indicated as either public or private with proposed names if available. Please provide this information on the plan view.
DS 2-03.2.4.F

2. Building setbacks along Drexel Road and Tucson Boulevard will be the greater of the MS&R setback (21' or height measured from future curb) or interior RCP setback of three (3) feet from the property line, whichever is greater. It appears that the MS&R setback will provide the greatest setback for lots along Drexel Road (lots 1-11 and 39) and the interior RCP setback of three (3) feet will be the greatest for lots along Tucson Boulevard (lots 11-19). Please revise matrix and plan view.


If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197.

KAA S:\zoning review\karol\planning\cdrc\tentativeplat\S05-180tprtp.doc


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat and additional requested documents.
02/01/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
02/06/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size per DS 2-05.2.1.A. Revise the landscape plan (L1 and any others) to comply.

2) Revise the landscape plan to include provisions for dust control in disturbed portions of ADJACENT RIGHT-OF-WAY areas per LUC 3.7.2.4.A.4. The minimum depth is to be 2" per DS 2-06.5.2.C.

3) The project is subject to the provisions of the Watercourse, Amenities, Safety, and Habitat Ordinance, TCC 29. Approval of the plat is conditioned upon approval of the WASH application. Note the case number and date of approval on the tentative plat.

4) Revise the landscape plans to clearly show the limits of grading. DS 2-07.2.2.B.5
Correct the line weight to match the legend and/or call out the line.

5) Revise the native plant preservation and landscape plans to delineate the resource area/Protected Riparian Area.
DS 2-13.0, TCC 29-116

RESUBMITTAL OF ALL PLANS IS REQUIRED.
02/13/2007 FRODRIG2 COT NON-DSD REAL ESTATE Denied S05-180 Tres Pueblos Norte: Resubmittal - CDRC - Tentative Plat Review - Request keynote #6 be changed to read " "1' No Vehicle Access by Final Plat."
03/07/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond TO: Patricia Gehlen; CDRC Coordinator
SUBJECT: Tres Pueblos IV Subdivision Tentative Plat 2nd re-submittal Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S05-180

SUMMARY: The revised Tentative Plat, revised Drainage Report, revised Landscape documents, drainage easement document, GRC geotechnical report, and response letters were reviewed. Development Services Department Engineering Division has done a review of the received items and recommends conditional approval. The Drainage Report was reviewed for Tentative Plat purposes only. Address the remaining items as conditions of approval of the Tentative Plat.

TENTATIVE PLAT CONDITIONS OF APPROVAL:
1) DS Sec.3-01.1.1: On sheet 3, provide clarification within a common area and the 80-ft Private Drainage Easement that will be a Recreational Trail and there will be a public access easement provided for the area incorporating the 50-ft Study Area and connecting trails to public right-of-way. Specifically,
a) Tie in the public access easement from both ends of recreational trail to the public right-of-ways. Clarify width of public access easement across common areas.
b) Label as Public Recreational Trail Access Easement.
2) DS Sec.10-02.2.3.1.6 A.4.d: On sheet 2, redraw leader lines adjacent to lots 33 and 34 for setbacks for basins to assure minimum 10-ft dimension between structures and any proposed basins or drainageways per geotechnical recommendations.
3) DS Sec.2-03.2.4.F: Clarify portions of new sidewalk and H/C ramps to be installed and label widths of sidewalks, as well as clarify existing sidewalk, along frontage of project along Drexel and Tucson Blvd.
4) DS Sec.2-03.2.4.L.5: Verification is required when any drainage solution occurring outside the boundaries of the plat is constructed with adjacent owners' permission. Additional notarized documentation of that approval will be submitted with the drainage report, if Dkt /pg of temporary construction easement / drainage maintenance easement for the proposed drainage improvements along west property boundary are not supplied at Tentative Plat stage.
5) Per D.S. 2-03.2.4.K: Per geotechnical Letter dated September 14, 2006, identify 1 to 2 feet setback from swale to foundation for sideyard drainage section detail on sheet 3.
6) DS Sec.2-03.2.4.F: Provide section for trail or access way along south side of development labeling material of path (compacted earth per W.A.S.H. submittal or otherwise).

LANDSCAPE PLAN CONDITIONS OF APPROVAL:
7) DS Sec.3-01.Fig18: Remove trees from the following areas:
a) From sight visibility triangles shown on sheets L5(along Tucson Boulevard), L2 and L4 (southwest of lot 40) to assure that no trees will obstruct the sight visibility area.
b) Remove trees from Common Area A-3 between access trail and top of basin ramp for maintenance vehicle access.

Submit separate copy of the title report, revised Tentative Plat, revised Landscape Plan sheets, response letter, and any other supporting documentation such as the authorization for west offsite drainage improvement. If you have questions or would like to set up a meeting, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
03/09/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 9, 2007

Luno
Rick Engineering Company
1745 East River Road #101
Tucson, AZ 85718

Subject: S05-180 Tres Pueblos IV Tentative Plat

Dear Luno:

Your submittal of January 17, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

5 Copies Revised Tentative Plat (Real Estate, Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plan (Engineering, Landscape, Zoning, DSD)

2 Copies Revised NPPO Plans (Landscape, DSD)

2 Copies Title Report (Engineering, DSD)


SINCE THE WASH OVERLAY APPLICATION HAS BEEN WITHDRAWN, PLEASE DO NOT ADD THE CASE NUMBER OR DATE OF APRPOVAL TO THE TENTATIVE PLAT.




Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 322-6956