Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Plan Number - S05-134
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2006 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 09/25/2006 | KAROL ARAGONEZ | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Karol Aragonez Planner PROJECT: S05-134 Tres Pueblos Estates Tentative Plat TRANSMITTAL DATE: September 25, 2006 DUE DATE: October 17, 2006 COMMENTS: The Zoning Review Section approves the tentative plat for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements. 1. Once approval for the WASH ordinance is obtained the tentative plat can be approved. Place the WASH case number and any conditions of approval on the tentative plat. Provide a copy of the approval with mylars. D.S. 2-03.2.2.B.7 If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197. KAA S:\zoning review\karol\planning\cdrc\tentativeplat\S05-134tpr.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat and additional requested documents. |
| 10/09/2006 | JOE LINVILLE | LANDSCAPE | REVIEW | Approv-Cond | The Landscape Section recommends approval subject to approval of the WASH application (Watercourse, Amenities, Safety, and Habitat Ordinance, TCC 29). The tentative plat may not be approved prior to approval. Note the case number and date of approval on the tentative plat. |
| 10/12/2006 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | DATE: October 12, 2006 TO: Patricia Gehlen; CDRC Coordinator SUBJECT: Tres Pueblos II Subdivision Tentative Plat 4th re-submittal Engineering Review REVIEWER: Elizabeth Eberbach ACTIVITY NUMBER: S05-134 SUMMARY: The revised Tentative Plat, revised Drainage Report, Landscape documents, copy of the geotechnical documentation, and response letter were received by Engineering. The response letter stated that TDOT has informally approved the trail design and drainage structures, however no documentation was provided. There are other private drainage easement issues brought up in RICK email correspondence with TDOT and City attorney. Before Engineering can complete the review of the resubmittal for the Tentative Plat, issues regarding the 80' drainage easement in the Rodeo W.A.S.H. must be resolved. Depending on any revisions due to the resolutions of the easement issues, additional reviews by other entities may be needed. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |
| 10/12/2006 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approv-Cond | October 12, 2006 ACTIVITY NUMBER: S05-134 PROJECT NAME: Tres Pueblos Estes PROJECT ADDRESS: TUCSON BLVD/BILBY RD PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer Resubmittal Required: Traffic Engineering recommends a conditional approval of the Tentative Plat. The TIA recommends infrastructure improvements that are not reflected in the plat; therefore a PIA is required for the off-site improvements recommended in the Traffic Impact Analysis. If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov |
| 10/12/2006 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | DATE: July 16, 2007 TO: Patricia Gehlen; CDRC Coordinator SUBJECT: Tres Pueblos II Subdivision Tentative Plat counter Engineering Review REVIEWER: Elizabeth Eberbach ACTIVITY NUMBER: S05-134 SUMMARY: Revised Tentative Plat documents were reviewed at the counter 12JUL07 for the 80' drainage easement (which is indicated to be maintained by Pima County). This counter review was for this easement and SAC determination purposes only. DSD Engineering does not recommend approval of the Tentative Plat however, this comment letter provides DSD Engineering recommendation for the Tentative Plat to proceed to SAC for review of the proposed Rodeo W.A.S.H. encroachment. Additional CDRC review of the Tentative Plat is still required after the SAC meeting. At this time, it is important that the consultant provide a formal letter of request to CDRC in order to proceed to SAC. Call if you have any questions, 837-4934. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |
| 10/12/2006 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | DATE: December 6, 2007 TO: Patricia Gehlen, CDRC Manager SUBJECT: Tentative Plat mylar and W.A.S.H. Engineering Review SUBDIVISION: (S05-134) Tres Pueblos II (Este) ADDRESS: 5975 S Tucson Bl REVIEWER: Elizabeth Eberbach ACTIVITY NUMBERS: S05-134, T05SA00358 SUMMARY: The Tentative Plat mylar and W.A.S.H. report were reviewed. DSD Engineering recommends approval of the Tentative Plat mylars and accepts the W.A.S.H. Report. It is recommended that the W.A.S.H. exhibit "Drainage Details for Rodeo Wash at Tres Pueblos Este" be added in the mylar set with confirmation by Landscaping. Call if you have any questions, 837-4934. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |
| 10/16/2006 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF URBAN PLANNING & DESIGN Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S05-134 Tres Pueblos II 10/16/06 () Tentative Plat ( ) Development Plan () Landscape Plan ( ) Revised Plan/Plat ( ) Board of Adjustment () Other (Irrigation Plan) CROSS REFERENCE: C9-94-18 NEIGHBORHOOD PLAN: Kino Area Plan GATEWAY/SCENIC ROUTE: Tucson Blvd. (gateway) COMMENTS DUE BY: 06/28/06 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: ( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment ( ) Proposal Complies with Annexation or Rezoning Conditions ( ) RCP Proposal Complies With Plan Policies ( ) See Additional Comments Attached () No Additional Comments - Complies With Planning Comments Submitted on: 06/28/06 ( ) Resubmittal Required: ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Other – REVIEWER: D. Estolano 791-4505 DATE: 10/13/06 |
| 10/19/2006 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Approved | October 19, 2006 To: Luno Martinez, Rick Engineering Thru: Patricia Gehlen, CDRC Project Manager City of Tucson Development Services Department ____________________________________ From: Michael J.Harrington (520-740-6579), representing the Pima County Departments of Wastewater Management and Environmental Quality Subject: Tres Pueblos Este (PKA Tres Pueblos II) Lots 1-163 & Common Areas “A-1” thru “A-3” & “B-1” thru “B-4” Tentative Plat – 4th Submittal S05-134 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative plat. Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality. Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution. If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter CC: Project File |
| 10/31/2006 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES October 31, 2006 Luno Martinez Rick Engineering Company, Inc. 1745 East River Road, Suite 101 Tucson, AZ 85718 Subject: S05-134 Tres Peublos II Tentative Plat Dear Luno: Your submittal of September 20, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLUELINES MUST BE FOLDED 2 Copies Revised Tentative Plat (Engineering, DSD) 2 Copies Revised Landscape Plan (Engineering, DSD) 2 Copies All other items requested by Engineering Reviewer (Engineering, DSD) Should you have any questions, please call me at 791-5608, ext 1179. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 322-6956 |
| 10/31/2006 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES ***REVISED*** July 28, 2007 Luno Martinez Rick Engineering Company, Inc. 1745 East River Road, Suite 101 Tucson, Arizona 85718 Subject: S05-134 Tres Pueblos Este Tentative Plat Dear Luno: The above referenced plan has been CONDITIONALLY APPROVED by the Community Design Review Committee, subject to the revisions required on the mylars. Please submit the following documents for sign-off: 1 Reproducible Océ or Photo Mylar of the Plat, Landscape Plan and NPPO. 2 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and three (3) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. Please note that the final plat must be approved by Mayor and Council and recorded within one year of date of approval of the tentative plat per LUC 4.1.7.3. TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 322-6956 |