Plan Number: S05-114
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S05-114
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/05/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: LA CIMA ESPLENDORA

Lots 1-57

S05-114



Tucson Electric Power Co. (TEP) approves the final plat submitted for
review January 22, 2008.

Please forward any resubmittals of the final plat to this office.



Electric service will be provided to this subdivision in accordance with
the rules and regulations approved by the Arizona Corporation
Commission.



Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo, Right of Way Agent
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
02/11/2008 LAITH ALSHAMI ENGINEERING REVIEW Approved Laith Alshami, Engineering and Floodplain Review, 02/11/2008,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: La Cima Esplendora
Formerly Escalante-Houghton
S05-114, T14S, R15E, SECTION 35

RECEIVED: Final Plat and CC & R's on January 22, 2008

The subject project has been reviewed. The Final Plat is acceptable and it is recommended for approval pertaining to Engineering and Floodplain Review. Please be advised of the following:

1. The Final Plat Mylar can not be processed until the assurance package is submitted for review and approved. The approved final plat might need to be revised based on the information in the assurances package submittal.
2. This Office recommends including the maintenance checklist in the CC & R's, as an exhibit, to allow the homeowners' association access to it and to facilitate their maintenance responsibility.


RESUBMITTAL REQUIRED: Final Plat Mylar and Assurances Package
02/12/2008 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-114 LA CIMA ESPLENDORA/REVISED FINAL PLAT
DATE: February 11, 2008



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.






***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***




jg
02/20/2008 FRODRIG2 COT NON-DSD REAL ESTATE Denied S05-114 La Cima Esplendora: Final Plat Review
-Two items concerning the two proposed 16' wide utility easements dedicated by this plat:
--Easements appear to be for electrical purposes only and the City has no interest committing to the easement.
--Request comments and assurance that subject easements will be abandoned prior any conveyance of ownership of parcels 15, 34, 33, 41, 42, 48 & 49.

Andy
(520) 837-6715
Real Estate Division

fax 791-5641
02/20/2008 FRODRIG2 COT NON-DSD REAL ESTATE Denied Ref.: S05-114

Laith/Patricia/Ferne
Michael Baker provided me the Mylars for my review and to confirm the requested changes were accomplished. I confirm the annotation "16 FT WIDE ELECTRICAL ESMT GRANT BY THIS PLAT SEE GENERAL NOTE 9" was accomplished. It is apparent assurances are provided that the Subject Easement will be abandoned prior conveyance of parcels 15, 33, 34 41, 42, 48 & 49.

Regards,
Andy Steuart
Property Agent
Real Estate Program
City of Tucson
201 N. Stone Ave. 6th Fl.
Tucson, Arizona 85701
(O) 520.837.6715
(F) 520.791.5641
andy.steuart@tucsonaz.gov
02/23/2008 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: S05-114 - RCP Development
Lots 1-57, Common Areas A, B, C
Final Plat

TRANSMITTAL DATE: February 23, 2008


DUE DATE: February 19, 2008

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.

2. Remove the name Kathleen Detrick from the approval block. Ms Detrick is no longer the City of Tucson Clerk.

3. Revise all text blocks that have the year "2007" to 2008.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

C\planning\cdrc\finaplat\S05114fpca.doc
02/29/2008 PGEHLEN1 PIMA COUNTY WASTEWATER Approved February 29, 2008

To: Michael John Baker
FSSB

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: La Cima Esplendora, Lots 1-57 & Common Area A, B & C
Final Plat -2nd Submittal(rev)
S05-114


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
03/03/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 3, 2008

Michael John Baker
Floerchinger, Sadler, Steele, Baker, Inc.
326 South Convent
Tucson, Arizona 85701

Subject: S05-114 La Cima Esplendora Final Plat

Dear Mike:

Your submittal of January 22, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Final Plat (Real Estate, DSD)









Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 628-1375
fpresubmittal
03/03/2008 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: February 20, 2008


RE: Assessor’s Review and Comments Regarding Final Plat
S05-114 La Cima Esplendora T141535

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.





Susan King
03/03/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES
***REVISED***

March 5, 2008
Michael John Baker
Floerchinger, Sadler, Steele, Baker, Inc.
326 South Convent
Tucson, Arizona 85701

Subject: S05-114 La Cima Esplendora Final Plat

Dear Michael:

The above referenced project has been CONDITIONALLY APPROVED by the Community Design Review Committee. Please make any necessary corrections and submit the following documents:

(2) Title reports current within the last thirty (30) days.
(1) Executed Final Plat Double Matte Océ or Photo Mylar.
(1) * Check in the amount of $8.50 per plat page for Mayor & Council distribution made payable to the local print company of your choice or provide an account number to charge.
(1) * Check in the amount of $55.00 per plat page for recorded plat distribution made payable to the local print company of your choice or provide an account number to charge.
(1) Check made payable to "Pima County Recorder" in the amount of $20.00 per plat page plus a $4.00 handling fee, along with CC&R fees if applicable. CC&R fees are $9.00 for the first 5 pages and $1.00 for each additional page.
(1) Executed and notarized CC&R's document (if applicable).

*Please do not combine the checks for the printing charges. They are processed at different times and require separate checks. An account number is also acceptable and you can include this information on your transmittal sheet when submitting the above listed items.

Assurances (if applicable) must be reviewed by the City Attorney's Office prior to being presented to the Mayor and Council. Plats, CC&R's and assurances must be approved at the same Mayor and Council Meeting. Please expect 7 - 8 weeks from the date submitted to the date scheduled for Mayor and Council approval.

PRIOR TO SUBMITTING THE MYLARS TO THE CDRC OFFICE, REAL ESTATE MUST REVIEW AND APPROVE THE MYLARS FOR CONDITIONS OF APPROVAL. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY)

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 628-1375