Plan Number: S05-110
Parcel: Unknown

Review Status: Completed

Review Details: OTHER SUBDIVISION REVIEW

Plan Number - S05-110
Review Name: OTHER SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/08/2005 JIM EGAN COT NON-DSD FIRE Denied 1. Fire hydrant required.
2. A minimum 20 feet wide, paved, fire appratus access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of all proposed structures. An app0roved turnaround is required for dead-end access roadways.
07/15/2005 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* Lot split for two new single family residence.
* Approved for APC service off Adelaide Drive. APC's are to be placed and removed from the collection area on the day of service.
07/18/2005 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-110 CATALINA POULTRY ACRES UNIT 2 / OTHER SUBDIVISION REVIEW
DATE: JULY 15, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

Note: Provide copies of recorded deeds prior to address assignments.


***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
07/22/2005 JOE LINVILLE LANDSCAPE REVIEW Approved
07/29/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
08/04/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: August 4, 2005

SUBJECT: Engineering review of the Catalina Poultry Acres Unit 2, Record of Survey. The activity number is S05-110.

SUMMARY: The Record of Survey was received by Engineering on July 7th. Engineering has reviewed the received items and recommends conditional approval of the Record of Survey.

RESUBMITTAL REQUIRED: RECORD OF SURVEY


RECORD OF SURVEY COMMENTS


1. Each sheet will measure 24" x 36" and include a two (2) inch margin on the left side and one-half (½) inch margins on the remaining sides. Currently the left margin scales to 1 ½ ". Revise the plan to show a 2" margin on the left side. DS 2-03.11.7.B.

2. Place the words "Book ____ Page ____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation.

3. The first line of the title block must read, "RECORD OF SURVEY". DS 2-03.11.F.1.

4. The number of the proposed lots is to be noted in the title block. Revise. DS 2-03.11.7.F.3.

5. Be advised that the title of the Record of Survey does not need to include, "Unit No. 2, Lot 9," since it is included in the legal description. The title can include the verbiage, "Unit No. 2, Lot 9" however the number of lots must be included in the title block. When revising the plan ensure the title block is clear and meets the requirements of DS 2-03.11.7.F

6. The north arrow and scale should be placed together on each sheet, preferably in the upper right corner of the drawing. Revise as necessary. DS 2-03.11.7.G.

7. Change general note number 5 to read, ""The number of lots is ____."

8. It is acknowledged that the name, address and telephone number of the primary owners of the site is in the first paragraph of the dedication section however it is recommended for clarity of the plan to show it as it's own note. DS 2-03.11.8.A.1.

9. Place the S(YR.)-___ Land Survey Exception case number in the lower right hand corner of the plan next to the title block. DS 2-03.11.8.B.1.

10. Under the "Record of Survey" section replace the word, "Map" with "Record of Survey." DS 2-03.11.9.A.

11. Include a "5X5" box around the recording data verbiage. DS 2-03.11.9.C.

12. Provide the existing recordation data for the roads. Indicate if public or private. DS 2-03.11.11.B.

13. Indicate if the proposed 22' access and utility easement is public or private. DS 2-03.11.12.A.

14. There are two distances located on the south side of the project, 665.26' and 606.96'. However this is not a beginning/end point for the distances. Revise the survey as necessary.
08/04/2005 FRODRIG2 PIMA COUNTY WASTEWATER Denied August 2, 2005

TO: Teresa Rosano
Ibarra Rosano Design Architects

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Catalina Poultry Acres Unit 2, Lot 9
Record of Survey – 1st Submittal
S05-110


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the South Rillito West (South Line) Interceptor. Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

Based on the evaluation of historical sewer improvement district maps, this project would qualify for Participating sewer connection fee rates.

ALL SHEETS. Add the project number, S05-110, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Add the following General Notes

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

ANY WASTEWATER DISCHARGED INTO THE PUBLIC SANITARY SEWERAGE SYSTEM SHALL MEET THE REQUIREMENTS OF THE INDUSTRIAL WASTE ORDINANCE (PIMA COUNTY ORDINANCE NO. 1991-140, AS AMENDED).

Add the following General Note and fill in the blanks appropriately

THIS PROJECT HAS ____ PROPOSED AND ____ EXISTING WASTEWATER FIXTURE UNIT EQUIVALENTS, PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E).

Show the existing public sewer, its size and the Pima County plan number.

Show any existing and/or proposed private sewers all the way to the point of connection with the existing public sewer. If there are proposed private sewers, show the length, size and slope, as well as labeling the sewers as “proposed private sewer” or “new private sewer”. If the private sewers are existing, label them as “existing private sewer”.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
08/04/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: CATALINA POULTRY ACRES UNIT 2, LOT 9
S05-110


Tucson Electric Power Company has reviewed and approved the plans submitted
for review July 7, 2005. It appears that there are no conflicts with the
existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location
of the existing facilities.

In order to apply for electric service, call the New Construction Department
at (520) 770-2062. Submit a final set of plans including approved site,
offsite and electrical load plans. Include a CD with the AutoCAD version of
the plans. If easements are required, they will be secured by separate
instrument.

Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
08/04/2005 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this Record of Survey:

1. Tucson City Code Chapter 25 Section 38 requires a minimum driveway separation of 12'. This plan as submitted does not provide for this necessary separation. The minimum driveway width for residential properties is 10'. Should the developer wish to only provide a 10' access easement to the proposed lots B & C, this will satisfy the driveway separation requirement and still meet the minimum access required to the rear two lots.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
08/04/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: July 27, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: S05-110 Catalina Poultry Acres Unit 2: Other Subdivision Review(7-7-05)

CC: Craig Gross
Patricia Gehlen



Staff has no comments.






Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
08/04/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-110 Catalina Poultry Acres Unit 2 08/04/05

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Craigin-Keeling

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 8/04/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: DCE 791-4505 DATE: 8/2/05
08/12/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed
08/12/2005 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved 29 ESTIMATED DAILY TRIPS IN 24 HR PERIOD.
08/16/2005 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S05-110
Catalina Poultry Acres Unit 2
Record of Survey

TRANSMITTAL: 08/16/05

DUE DATE: 08//4/05

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a record of survey. If, at the end of that time, the record of survey plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey plat is August 3, 2006.

2. Per DS 2-03.11.1.C. The plan does not indicate any existing sidewalks in the right of way. It is a requirement for a Record of Survey that all street frontages must have existing sidewalks. The sidewalks must be installed prior to final approval of the Record of Survey. Provide documentation for verification of sidewalks having been installed.

3. Per DS 2-03.11.5 Resubmittal. Should a resubmittal be required to address CDRC comments, the applicant will submit a detailed letter of explanation with the resubmittal packet. The letter will address each comment as presented in the CDRC response letter and discuss revisions made to the plans arising from these comments. Sufficient copies of the letter will be included in the resubmittal to attach to each blueline print submitted. Any revisions made in addition to those requested in the CDRC response letter must be specifically addressed.

4. Per DS 2-03.11.7.E. Place the words "Book ____ Page ____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation.

5. Per DS 2-03.11.7. F, & .F.3 A title block with the following information is to be provided approximately in the lower right corner of the first page of the Record of Survey.
3. The number of proposed lots is to be noted.

6. Per DS 2-03.11.8.A.1 Provide the name, address, and telephone numbers of the primary owners of the site. This information is provided in the dedication block note #1 but should be in a separate block for clarity purposes.

7. Per DS 2-03.11.8.B.1 The Land Survey Exception case number assigned to this project is S05-110. Place the Land Survey Exception case number in the lower right hand corner of the plan next to the title block. The S file number has been provided and should be added to the drawing on subsequent submittals.

8. Per DS 2-03.11.12.E E. The driveway indicated can only access two units. Clearly indicate that only one single-family residence per lot will be constructed. Accessing three or more units off a single access point requires the development of a street or PAAL. The development of a street or PAAL requires a plat.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, tentative plat, final plat, CC&R's and additional requested documents.
08/17/2005 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Denied see comments
08/17/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 17, 2005

Teresa Rosano
Ibarra Rosano Design Architects
2849 East Sylvia Street
Tucson, AZ 85716

Subject: S05-110 Catalina Poulrty Acres Unit No.2 Lot 9 Record of Survey

Dear Teresa:

Your submittal of July 7, 2005, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Record of Survey (Fire. Traffic, Engineering, Zoning, Wastewater, DSD)




Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 795-8699