Plan Number: S05-101
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: OTHER SUBDIVISION REVIEW

Plan Number - S05-101
Review Name: OTHER SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/30/2005 JIM EGAN COT NON-DSD FIRE Approved
07/06/2005 JCLARK3 ENV SVCS REVIEW Approved * No known landfill within 1000 feet of this development.
* Lot split for individual residences.
* Approved for APC's curbside service off of Mission Road and Borrego Street. APC's are to be placed and removed from the curbside collection area on the day of service.
* The lot that has the 12 foot frontage will require the Apc's to be placed in the driveway or on the adjoining property. The width meets zoning requirements.
07/07/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S05-101
HILLS-BURRO ADDITION
07/08/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-101 HILLS-BURRO ADDITION/OTHER SUBDIVISION REVIEW
DATE: 7/07/05



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

The Location Map scale should be 3”= 1 mile. Please correct.

Delete 5220 S. Missiondale from Location Map.

Delete all street directions on Location Map.

Number lots numerically (1-5).

Include lots 1-5 on Title Block.

Spell out street of Borrego St.

Recorded Deeds with legal descriptions will need to be provided in order to issue addresses.
07/11/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-101 Hills-Burro Addition

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other: Record of Survey

CROSS REFERENCE: N/A

NEIGHBORHOOD PLAN: 12th Avenue/ Valencia Area Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: July 27, 2005

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: vf 791-4505 DATE: July 7, 2005
07/18/2005 JOE LINVILLE LANDSCAPE REVIEW Approved
07/25/2005 FRODRIG2 PIMA COUNTY WASTEWATER Denied July 25, 2005

TO: Peter Ellison

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Hills-Borro Addition Lot 1 Lot Split
Record of Survey – 1st Submittal
S05-101


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the Santa Cruz Interceptor. Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. Contact Robert Decker, PCWWM Planning Services, at (520) 740-6625 regarding this matter.

Based on the evaluation of project G-295, this project would qualify for Participating sewer connection fee rates.

ALL SHEETS. Add the project number, S05-101, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Show the existing public sewer to which this project is connecting, along with the size and Pima County plan number.

Show how this project will be sewered, including size, length and slope of the sewers, along with any necessary private sewer easements.

Add the following General Note

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.

Add the following General Note

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY
WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
07/27/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied DATE: 27 July 2005

SUBJECT: Proposed Record of Survey -
Hills-Borro Addition (S05-101)

Engineering Division does not recommend approval of the proposed Record of Survey at this time. A meeting with the applicant is requested regarding this proposed Land Division.

Please contact me at 791-5550 ext. 1189 or via email at Doug.williams@tucsonaz.gov

Doug Williams
Sr. Eng. Associate
Engineering Division
Development Services Dept
07/27/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied DATE: 27 July 2005

SUBJECT: Proposed Record of Survey -
Hills-Borro Addition (S05-101)

Engineering Division does not recommend approval of the proposed Record of Survey at this time. A meeting with the applicant is requested regarding this proposed Land Division.

Please contact me at 791-5550 ext. 1189 or via email at Doug.williams@tucsonaz.gov

Doug Williams
Sr. Eng. Associate
Engineering Division
Development Services Dept
07/28/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this Record of Survey.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
07/29/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: Hills-Burro Addition
S05-101

Tucson Electric Power Company has reviewed and approved the plans submitted
for review June 28, 2005. It appears that there are no conflicts with the
existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location
of the existing facilities.

In order to apply for electric service, call the New Construction Department
at (520) 770-2062. Submit a final set of plans including approved site,
offsite and electrical load plans. Include a CD with the AutoCAD version of
the plans. If easements are required, they will be secured by separate
instrument. Your final plans should be sent to:

Mike Kaiser
Design/Build - DB 102


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
07/29/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
07/29/2005 DAN CASTRO ZONING REVIEW Denied PROJECT:
Hills-Boro Addition Lots 1-5
S05-101
Record of Survey (1st Review)
TRANSMITTAL: July 29, 2005



COMMENTS
1. An applicant has one (1) year from the date of submittal to obtain approval of a record of survey that complies with zoning and other development requirements in effect at the time of application. This record of survey must be approved and recorded on or before June 27, 2006.

2. General note one (1) states that all public infrastructure is fully improved yet the plan shows a new five (5) foot wide sidewalk. To meet the land survey exception, one of the criteria required, is for all street frontages to have existing sidewalks and curbs. At this point, a record of survey will not be allowed for the proposed split and a subdivision plat will be necessary to continue the subdivision process. Please contact the Engineering Section reviewer for this project to discuss possible option/s. One possible option may be the construction of the public sidewalks prior to record of survey review and approval. (D.S. 2-03.11.1.C)

3. The first line of the title block must read, "Record of Survey". (D.S. 2-03.11.7.F.1)

4. The number of proposed lots is to be noted in the title block. (D.S. 2-03.11.7.F.3)

5. The title block shall include a brief legal description. (D.S. 2-03.11.7.F.4)


6. Place the words "Book____Page____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation.

7. List the names, address, and telephone numbers of the primary owners of the site. (D.S. 2-03.11.8.A.1)

8. This project has been assigned subdivision case number S05-101. Please note the case number in the lower right hand of the plan next to the title block. (D.S. 2-03.11.8.B.1)

9. Revise general note three (3) as follows: "Existing zoning is R-2". (D.S. 2-03.11.8.B.2)

10. Revise general note five (5) as follows: "The number of lots is five". (D.S. 2-03.11.8.B.3)

11. Identify each proposed lot by number. The plan currently uses letters. (D.S. 2-03.11.12.D)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180.
08/04/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: July 26, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: S05-101 Hills-Burro Addition: Other Subdivision ReviewOther Subdivision Review(6-28-05)

CC: Craig Gross
Patricia Gehlen



Staff has no comments.






Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
08/08/2005 CRAIG GROSS OTHER AGENCIES PIMA ASSN OF GOVTS Passed
08/08/2005 CRAIG GROSS ZONING-RECORDATION REVIEW Passed
08/08/2005 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed