Plan Number: S05-098
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S05-098
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/20/2006 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: LA ESTANCIA DE TUCSON

Lots 1-340

S05-098



Tucson Electric Power Company (TEP) has reviewed the final plat
submitted June 16, 2006. TEP is unable to approve the plat at this
time. TEP is waiting on plans for design completion, the design is
necessary to determine all easement requirements.



Please submit the approved tentative plat for preliminary electrical
design completion. Additional plans necessary for preparation of the
design are: building plans including water, electrical, landscape,
sidewalk and paving plans. Also, submit the AutoCAD version of the plat
on a CD or email to lcastillo@tep.com <mailto:lcastillo@tep.com> .



In your request for this design please let us know of any phasing of
this project.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
07/03/2006 LAITH ALSHAMI ENGINEERING REVIEW Approv-Cond Laith Alshami, Engineering and Floodplain Review, 07/03/2006

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: La Estancia De Tucson 1-330
S05-098, T15S, R15E, SECTION 18

RECEIVED: Final Plat and Assurances on June 16, 2006

The subject submittal has been reviewed. The Final Plat is conditionally approved subject to showing the following on the Final Plat Mylar:

1. Demonstrate how the subject development ties into the basis of bearing. Verify compliance with the requirements of D.S. 2-03.6.5.A.
2. The Final Plat Mylar shall reflect the abandonment of the Easement described in Keynote 6 of the approved Tentative Plat.
3. Add a general note, which states that all lots that are impacted by the 20' water easement, shown on Sheet 10/21, shall not be permitted until proper abandonment verification is submitted to the City

Assurances:

The Assurances Package is missing the following information:

1. A copy of the Trust Agreement.
2. A copy of the Warranty Deed.
3. A recent copy of the Title Report.
4. The legal description in Exhibit "A" in the Original Third Part Trust Agreement and the Amendment shall match the Title description in the Final Plat Mylar Title Block.


RESUBMITTAL REQUIRED: Revised Final Plat and Assurances
07/17/2006 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond July 14, 2006

To: Michelle Dodroe, Castro Engineering Corp.

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J.Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: La Estancia De Tucson
Lots 1-330 & Common Areas "A" & "B" and Blocks A, B, C, D, and E
Final Plat - 2nd Submittal
S05-098

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Sheet 2: Delete the future lot numbers that appear on Block “D”.

Sheet 18: The north end of the existing 15” private sewer easement does not appear to extend to the public sewer easement or appear to close. Please explain.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
07/18/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-098 LA ESTANCIA DE TUCSON/REVISED FINAL PLAT
DATE: July 17, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

On Final Mylar:
Shade the project on the Location Map all the same color.
Spell out all street suffixes except on Location Map.
Put See Sheet 6 in the correct location on pg 4.


***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***


jg
07/21/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approv-Cond >>> Manny Padilla 07/20/06 12:38 PM >>>
Patricia, I have just reviewed revised tentative plat S05-098 lots 1-664, phase I. I have also reviewed final plats S05-098 lots 1-340 Phase I, final plat S06-67 lots 341-418 Phase I, and final plat S06-071 lots 411- 664 Phase I. All part of La Estancia Phase I development. Roger agrees these four plats do not require a resubmittal to DUPD staff. However, all four plats have two common issue that can be addressed by DSD. These two issues are related to the attached wording and map provided by the applicant to DUPD staff.
07/25/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Tentative and Final....no further comments except to note that right of way is not abandoned by plat as noted on the tentative. The right of way will be deeded to the developer simultaneously with the recording of the plat. Real Estate needs to be kept informed of the projected M&C date so we can schedule the street vacations for consideration by M&C at the same meeting.
07/26/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 26, 2006

Wocky Redsar
Castro Engineering Corp.
3580 West Ina Road, Suite 200
Tucson, AZ 85741

Subject: S05-098 La Estancia de Tucson - Phase I Final Plat

Dear Wocky:

Your submittal of June 16, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Final Plat (Wastewater, TEP, Real Estate, Community Planning, Engineering, DSD)







Should you have any questions, please call me at 791-5608 ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager