Plan Number: S05-078
Parcel: Unknown

Address:
8445 S KOLB RD

Review Status: Completed

Review Details: OTHER SUBDIVISION REVIEW

Plan Number - S05-078
Review Name: OTHER SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/18/2005 JIM EGAN COT NON-DSD FIRE Approved
05/23/2005 JCLARK3 ENV SVCS REVIEW Approv-Cond * No known landfill with in 1000 feet of this development.
* Split of property for commercial development. Refuse service will be evaluated at the time the development plan is submitted.
06/04/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-078 NEW WAREHOUSE / OTHER SUBDIVISION REVIEW
DATE: JUNE 2, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Include the entire legal description on all Title Blocks.
06/07/2005 FRODRIG2 PIMA COUNTY WASTEWATER Denied June 7, 2005

TO: Claude Lopez
Hardrock Concrete Placement, Inc.

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Iota on Wieding, Lot 1
Lot Split/Record of Survey – 1st Submittal
S05-078


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the Santa Cruz Interceptor. Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. Contact Robert Decker, PCWWM Planning Services, at (520) 740-6625 regarding this matter.

Based on the evaluation of historical sewer improvement district maps, this project would qualify for Participating sewer connection fee rates.

ALL SHEETS. Add the project number, S05-078, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

SHEET 1. Show all the required general notes as described in the Pima County tentative plat/development plan requirements. This information may be found at http://www.pimaxpress.com/SubDivision/Default.htm.

SHEET 2. Show the proposed and/or existing on-site sewers. For proposed sewers, show the length, size and slope, as well as manhole/cleanout rim and invert elevations.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
06/10/2005 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S05-078
1445 E Wieding Rd.
Record of Survey

TRANSMITTAL: 06/10/05

DUE DATE: June 14, 2005

COMMENTS:


1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a record of survey. If, at the end of that time, the record of survey plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey plat is May 16, 2006.

2. Section 2-03.11.7.D.2, DS, (1Location Map)Identify conditions with in the square mile area, such as land surveys, major streets, watercourses, and railroads. Reference recorded land survey plats by book and page numbers. If applies.

3. Section 2-03.11.8.B.4, DS List the gross area of the existing parcel prior to the split. Clearly indicate the original size of the lot as well as the square footage of both lots after the split.

4. Clearly indicate that both lots are undeveloped.

5. Section 2-03.11.8.B.1, DS, Place the S05-078 Land Survey Exception case number in the lower right hand corner of the plan next to the title block.

6. Section 2-03.11.8.B.3, DS, The number of lots indicated is incorrect. It should be 2 lots not 1. Change the number of the second lot from 203 to Lot 2. Also change the Title Block line 2 to read "IOTA on Wieding , Lots 1&2".

7. There is a misprint in Section 2-03.11.11.D, DS, It should read "All zoning classifications, on and adjacent to the project shall be indicated on the drawing with any zoning boundaries clearly indicated." Please indicate on the plan the zoning of the property as well as adjoining property.

8. Section 2-03.11.7.D.2, DS, Change the beginning of the brief legal description located at the lower right hand corner to read "A Resubdivision of Lot 203 of Los Ranchitos Number 5 etc."

9. Provide legal descriptions for both lots 1 and 2.

10. Ad a General Note #11 to read: "A separate site plan review and approval will be required for new Lots 1 and 2".

If you have any questions about this transmittal, please call Terry Stevens @ (520) 791-5608 ext. 2000.
06/13/2005 JOE LINVILLE LANDSCAPE REVIEW Approved
06/14/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: June 14, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, S05-078 New Warehouse: Other Subdivision Review

CC: Craig Gross
Patricia Gehlen, Development Services


Staff has no comments.







Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
06/14/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied Engineering Division has no adverse comments at this time. Approval may be recommended upon completion of addressing all other review comments. Site and Grading plan review comments under DSD Activity numbers T05CM00691 and T05BU00351 must be fully addressed prior to any permit issuance.
06/15/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this record of survey.


D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
06/15/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: NEW WAREHOUSE
S05-078

Tucson Electric Power Company (TEP) has reviewed the plans submitted for
review May 17, 2005. TEP is unable to approve the plans at this time.
There are existing electrical facilities along Weiding Road. In order for
TEP to approve the plans, the facilities must be depicted on the plans.

Enclosed is a copy of a TEP facility map showing the approximate location of
the existing facilities. The existing pole #54 may be in conflict with the
proposed driveway. All cost associated with the relocation of the
facilities in conflict will be billable to the developer.

Please resubmit two revised bluelines to the City of Tucson for TEP's
review. You may contact me at (520) 917-8745 if you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
06/17/2005 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved 57 estimated trips in 24 hour period.
06/17/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
06/17/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-078 New Warehouse 06/16/05

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(xxxxx) Other – Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: Kino

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 06/14/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: DCE 791-4505 DATE: 06/13/05
06/28/2005 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S05-078
WIEDING ROAD
06/29/2005 PATRICIA GEHLEN ZONING-RECORDATION REVIEW Denied see comments from reviewers
06/29/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

June 29, 2005

Claude Lopez
Hardrock Concrete Placement, Inc.
6360 South Del Moral
Tucson, AZ 85706

Subject: S05-078 New Warehouse/IOTA Record of Survey

Dear John:

Your submittal of May 17, 2005, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Record of Survey (engineering, zoning, TEP, addressing, wastewater, DSD)

3 Copies Revised CC&R's (engineering, zoning, DSD)

Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/