Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: S05-052
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S05-052
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/13/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: BARRIO PANTANO

S05-052



Tucson Electric Power Company (TEP) has received the final plat
submitted for review April 11, 2006. TEP is unable to approve the plat
at this time.



An electrical design to determine our easement requirements will be
provided on the Approved Tentative Plat with fifteen (15) working days
upon receipt of the plat. Additional plans necessary for preparation of
the design are: building plans including water, electrical, landscape,
sidewalk and paving plans. Also, submit the AutoCAD version of the plat
on a CD or email to lcastillo@tep.com <mailto:lcastillo@tep.com> .
Should you have any questions, please contact me at (520) 917-8745.




Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
04/24/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied April 21, 2006

To: Kent A. Delph, P.E., Delph Engineering, Inc.

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Barrio Pantano
Lots 1-57 and Common Areas "A"-"D"
Final Plat - 1st Submittal
S05-052

The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of residential lots. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the final plat.

Sheet 1: In the DEDICATION block, PRIVATE STREETS, DRAINAGEWAYS AND COMMON AREAS need to all be set-aside as easements. Revise the 4th paragraph, 1st sentence so that after the word SUBDIVISION it states:

AND ARE GRANTED AS EASEMENT TO CITY OF TUCSON, PIMA COUNTY AND ALL UTILITY COMPANIES FOR ACCESS, INSTALLATION AND MAINTENANCE OF PUBLIC SEWERS, ABOVE GROUND AND UNDERGROUND UTILITIES AND DRAINAGE.

Sheet 1: The onsite sewers are public. The only private sewers in this subdivision are the House Connection Sewers (HCS) that belong to and are the responsibility of each individual lot owner. Revise the DEDICATION block, 4th paragraph, last sentence, so that:

The PRIVATE SEWERS element is removed from the list of responsibilities that the ASSOCIATION will accept control, maintenance and liability for.

We will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
04/26/2006 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-052 BARRIO PANTANO/FINAL PLAT
DATE: APRIL 26, 2006




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Label approved interior street names.

NOTE: You will need 2 street names. One will be a “Loop” road beginning at the entrance adjacent to lot 1, continuing through the subdivision and exiting adjacent to lot 34.

You will also need a street name at the entrance adjacent to lots 44 and 45.











jg
05/07/2006 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
Barrio Pantano
S05-052
Final Plat

TRANSMITTAL: May 7, 2006
DUE DATE: May 9, 2006


1. Add the title company name and trust number to the Beneficiary Block. DS 2-03.6.3.C

2. Revise the dates in the Dedication, Recording, and Approval Blocks to read "2006".

3. Tentative plat approval is required prior to final plat approval.

4. The minimum text size required is 12 point (.012") for microfilming purposes. Revise the lettering for the subdivision book and page numbers in the location map on sheet 1 of 3 to meet this minimum archiving standard. DS 2-03.6.1.C

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
05/09/2006 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor


115 N. Church Ave.


Tucson, Arizona 85701



BILL STAPLES

ASSESSOR










TO: CDRC Office

Subdivision Review

City of Tucson (FAX# 791-5559)



FROM: Gary Ault, Mapping Supervisor

Pima County Assessor's Office

Mapping Department



DATE: May 9, 2006





RE: Assessor's Review and Comments Regarding Final Plat

S05-052 Barrio Pantano T141521 (136-15)




* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *



X Plat meets Assessor's Office requirements.

_______ Plat does not meet Assessor's Office requirements.





COMMENTS: THANK YOU FOR YOUR SUBMITTAL.



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS
TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN
THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING
THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK
YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.







ROSANNA WERNER
05/10/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: May 10, 2006
CDRC/Zoning Manager

SUBJECT: Barrio Pantano, 7901 E. Golf Links Rd.
Final Plat S05-052 (First Review)
T14S, R15E, Section 21

RESUBMITTAL REQUIRED: Final Plat.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used:
· Title Report
· Special Warranty Deed
· Trust Agreement
· Amendment to Trust
· Agreement to Construct
Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.
3. The title block of the plat must match the Subdivision Assurances verbatim.
4. If the plat contains more than one sheet, a small index drawing of the site……..per D.S. 2-03.6.1.E.
5. If the subdivision is a resubdivision of a previously recorded plat…….. reference the plat per D.S. 2-03.6.1.H.3.
6. Provide the complete note per D.S. 2-03.6.2.C.
7. Indicate with a star symbol where the access to corner lots will per D.S. 2-03.6.4.G.
8. Show a 1' no access easement on the side of lots 8, 34, 44 and 57 per D.S. 2-03.6.4.H.
9. Show sight visibility triangles per D.S. 2-02.2.1.10.
10. Please submit a copy of the subdivision boundary closure calculations.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7901 E. Golf Links Rd. FP
05/11/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved S05-052 Barrio Pantano: Final Plat Review. No comments.
05/13/2006 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
05/15/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

May 15, 2006

Kent Delph
Delph Engineering
221 North Court #103
Tucson, AZ 85701

Subject: S05-052 Barrio Pantano Final Plat

Dear Kent:

Your submittal of April 11, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Final Plat (TEP, Wastewater, Addressing, Engineering, Zoning, DSD)






Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 882-6570