Plan Number: S05-043
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL- OTHER SUBDIVISION REVIEW

Plan Number - S05-043
Review Name: RESUBMITTAL- OTHER SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/20/2005 JIM EGAN COT NON-DSD FIRE Approved S05-043 is approved May 20, 2005.
05/26/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond May 26, 2005

TO: Antony C. Tsang
A. C. Tsang Engineering Group, Inc.

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: LeCocq/Blacklidge Apartments
Subdivision Exception – 2nd Submittal
S05-043


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


A private Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents has been sent to your office. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve the Mylars of the development plan.

Show the rim and invert elevations of the cleanout.

Delete General Note 9. It is a duplicate of General Note 21.

Add the following General Note

ANY RELOCATION, MODIFICATION, ETC., OF THE EXISTING UTILITIES AND/OR PUBLIC IMPROVEMENTS REQUIRED BY THIS DEVELOPMENT WILL BE AT NO EXPENSE TO THE PUBLIC.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative plat.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
05/27/2005 PATRICIA GILBERT ENGINEERING REVIEW Approv-Cond TO: Patricia Gehlen; CDRC Coordinator DATE: May 27, 2005

SUBJECT: Engineering review of the Lecocq/Blacklidge Apartments, Record of Survey. The activity number is S05-043.

SUMMARY: The Record of Survey was received by Engineering on May 19th, 2005. Engineering has reviewed the received items and recommends conditional approval of the Record of Survey.

RECORD OF SURVEY CONDITIONALLY APPROVED


RECORD OF SURVEY COMMENTS

The mylar must address the following item:

1. Remove the verbiage, "Parcel 3" located within the sidewalk area adjacent to building 2.
05/31/2005 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
Lecocq/Blackledge Apartments Record of Survey
S05-043

TRANSMITTAL: May 31, 2005
DUE DATE: June 4, 2005

1. The adjacent zoning to the west is C-1 and the required setback to the west property line is equal to the height of the exterior structure wall. The building setback of 12.16 feet shown on the drawing does not meet this requirement if the building height is 13 feet as stated on the plan. Revise setback to west lot line and provide elevation drawings to demonstrate how all required setbacks are met. Add the adjacent zoning on all sides of the project site to the record of survey drawing.
LUC 3.2.6.4

2. The legal descriptions for each parcel must be included on the plan since they describe the required cross access easements. In addition to stating ingress-egress, utilities and pedestrian cross access, these legals must also specify cross-parking in their descriptions of easements. Revise to show full legals with easements described on the drawing.

3. Parcel 3 is labeled in two separate lots on the drawing. Revise to be correct and for clarity provide a density calculation for each lot indicating that the maximum density of 15 units per acre in the R-2 zone is not exceeded.

If you have any questions about this transmittal, please call Peter McLaughlin (520) 791-5608.
05/31/2005 JCLARK3 ENV SVCS REVIEW Approv-Cond * Since there is not sufficient space provide on site for the collection vehicle to turnaround safely, the developer was informed that a direct service metel dumpster could not be provided. Mteal service could be provided where the dumpster is on casters and would have to be rolled out for setvice. This is known as a roll-out service and would require an additional service charge.
06/04/2005 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-043 LECOCO/BLACKLIDGE APARTMENTS/REVISED OTHER SUBDIVISION
DATE: June 2, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1: Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved
Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima
County Addressing prior to assignment of addresses.

2: All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.














jg
06/07/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this other subdivision review.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
06/08/2005 CRAIG GROSS ZONING-RECORDATION REVIEW Denied
06/08/2005 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed