Plan Number: S05-030
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S05-030
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/13/2005 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-030 DOS RIOS / REVISED TENTATIVE PLAT
DATE: JUNE 13, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1: Spell out all street suffixes except on Location Map.

2: Change Braddock Street to Drive, Lane, Road, Trail or Way.

3: Change Kirtley Place to Drive, Lane, Road, Trail or Way.

4: Label Lakota Drive on pg. 4.
06/13/2005 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S05-030 DOS RIOS/REVISED TENTATIVE PLAT
DATE: JULY 7, 2005




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

APPROVED ON THE CONDITION THAT:
SPELL OUT ALL STREET SUFFIXES EXCEPT ON LOCATION MAP.
CHANGE BRADDOCK STREET TO DRIVE, LANE, ROAD, TRAIL OR WAY.
CHANGE KIRTLEY PLACE TO DRIVE, LANE, ROAD, TRAIL OR WAY.
LABEL LAKOTA DRIVE ON PG. 4

***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***








jg
06/14/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Where natural washes cannot be maintained, a mitigation plan shall be established with emphasis being placed on earthen or naturally appearing channels with landscaping and texture/color added to bank protection materials. The design of earthen channels will be encouraged in order to allow for a more permeable surface which permits reintroduction of the water into the groundwater system, allowing for the reintroduction of native plant species which promotes a natural, partially soil-stabilized system". Revise as necessary to incorporate natural materials and landscaping within Common Area 'B'. THE TENTATIVE PLAT INCLUDES NO REFERENCES TO DESIGNS AND METHODS USED TO RECREATE NATURALLY APPEARING CHANNELS DECRIBED IN THE LANDSCAPE COMMENT RESPONSE LETTER.

2) Note the slope ratios for rentention basins on the landscape plans. DS 2-07.2.2.B

3) Provide verification, in writing of any City Engineer approval to locate required landscaping the public right-of-way. LUC 3.7.2.4.A.3

4) Revise the irrigation note 1 on sheet L-1.

5) Revise the note on sheet L-7 regarding drainage.

RESUBMITTAL OF ALL PLANS IS REQUIRED
06/15/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approved June 15, 2005

TO: Wocky Redsar
Castro Engineering Corp.

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Cantera, Lots 1-143, Blocks A & B and Common Areas A-C
Tentative Plat – 2nd Submittal
S05-030


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project is hereby approved as submitted.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
06/22/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: June 22, 2005
TO: Patricia Gehlen; CDRC Coordinator
SUBJECT: Dos Rios Tentative Plat 2nd Submittal Engineering Review
LOCATION: T15S R14E Section 10
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S05-030

SUMMARY: The revised Tentative Plat, revised Landscape sheets, Geotechnical Engineering Evaluation, infiltration testing geotechnical letter, Collapsible Soils Geotechnical submittal, Pima County Regional Flood Control document, Sierra Pacific Letter, Cultural Resource Letter, TIA, response letters, and revised Drainage Report were received by Engineering on June 9, 2005. Engineering has reviewed the received items and does not recommend approval of the Development Plan or the Drainage Report at this time. The Drainage Report was reviewed for Development Plan purposes only.

DRAINAGE REPORT COMMENTS:
1) DS Sec.10-02.12.5: Storm waters must be accepted and released from developments essentially at the same locations, and with the same magnitudes, as encountered under existing conditions. The drainage scheme must be modified to show storm waters released at the same locations and with the same magnitudes as existing conditions. Provide cross section near lot 90, where existing floodplain indicates receipt of potential flow; an interceptor drainage design is needed at this location. Revise detail J/3 to show full cross section of channel. Also show on plan view the drainage easement that will be necessary to accommodate this assurable item.
2) DS Sec.10-02.1.5.1 & -14.3.4: Show 15-ft.wide basin maintenance access ramp with maximum ramp slope is 15%; clarify drainage maintenance access for Basin 1. Explain whether there will be a barrier or gated entrance for Basin 2 maintenance access and show location of access to Basin 2.
3) DS Sec.10-02.10.6.9: Response letter indicates that this was complied yet the calculation sheet in appendix did not reflect update. Use the Standards Manual for Drainage Design and Floodplain Management for appropriate scupper clogging factors.

TENTATIVE PLAT COMMENTS:
4) DS Sec.10-02.14.2.6, & 10-01.3.5.1: Percolation tests show infiltration rates for Basin 1 to be inadequate and therefore the bleed pipes are crucial for the drainage to function. Show that the invert elevations (for both basins) are low enough to bleed off and that the outlet invert elevations must be high enough to not cause backwater or other adverse conditions. Also use 24" diameter minimum pipe with 6" plate.
5) DS Sec.11-01.8.1.A: Proposed fill on lot 44 is in excess of two feet above existing grade in the outer one hundred feet of the developing site adjacent to residentially zoned property and will require the procedure outlined in this section. This process must be complete prior to Grading Plan approval.
6) DS Sec.11-01.9: Where proposed right-of-way abuts property line, provide cross sections depicting existing and proposed topography and grades showing that slope runout is provided and in conformance with 2-foot slope setbacks. For the wall depicted in details A/6 and B/6, the wall and footer as well as construction trench area should be within the property limits, otherwise, notarized permission from adjacent property owner is necessary, with sheet 6 revised to show a docket page for surveyable construction / maintenance easement for this wall.

Submit revised Tentative Plat, revised Drainage Report, any permission letters, and detailed response letter. Call me at 791-5550, extension 2204, to discuss comments or to schedule a meeting to go over comments before resubmittal.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
06/23/2005 DALE KELCH COT NON-DSD TRAFFIC Approved >>> Dale Kelch 06/23/2005 4:38:19 PM >>>
Traffic Engineering recommends APPROVAL of this TP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
06/23/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-030 Dos Rios 06/23/05

(XXXX) Tentative Plat
() Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – NPPO Plan

CROSS REFERENCE: C9-04-15

NEIGHBORHOOD PLAN: General Plan

GATEWAY ROUTE:

COMMENTS DUE BY: 6/23/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(XXXX) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(XXXX) Resubmittal Required:
(XXXX) Tentative Plat
() Development Plan
() Landscape Plan
(XXXX) Other – Elevations and Color Palette

REVIEWER: DCE 791-4505 DATE: 06/22/05
Urban Planning and Design Comments
S05-030 Dos Rios

Because this is a Residential Cluster Project (RCP), it must be in conformance with Section 3.6.1 of the Land Use Code as well as the design policies and criteria of the General Plan, and any of its components, including
the Design Guidelines Manual.

Rezoning condition #8 states “all residential building elevations visible from Alvernon Way and Benson Highway shall incorporate five-sided architectural detail to provide a visually interesting streetscape.”

Elevations submitted do not illustrate what type of individual enhancement (window pop outs, edge treatment, color variation, etc.) will be added to the sides and back of units visible from Alvernon Way and Benson Highway. Please visit the Urban Planning and Design’s website link to view “The Sonoran Desert Color Palette for Building Exteriors”: http://www.ci.tucson.az.us/planning/sonorandesertcolors.pdf, which features a palette of diverse Sonoran Desert Colors. The handout was created to showcase and promote the incorporation of all Sonoran Desert colors into the base and/or accent colors of building design.


Please provide elevations illustrating how these requirements will be satisfied.
06/23/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S05-030 Dos Rios 7/26/05

(XXXX) Tentative Plat
() Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
(XXXX) Other – NPPO Plan

CROSS REFERENCE: C9-04-15

NEIGHBORHOOD PLAN: General Plan

GATEWAY ROUTE:

COMMENTS DUE BY: N/A

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(XXXX) No Additional Comments*- Complies With Planning Comments Submitted on: 6/23/05
*Applicant hand-delivered revised elevations.

() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan

REVIEWER: DCE 791-4505 DATE: 07/25/05
07/01/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Real Estate is in the process of vacating Atrim Loop under RES 2005-030.
Contact Real Estate at least 1month in advance of the date the Final Plat is agendized for Mayor and Council. The vacation of Atrim Loop must be done simultaneously with the approval of the final plat.
07/01/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Conditional approval: Contact real estate at least one month before final plat is scheduled on M&C agenda. The vacation of Antrim Loop must be on the same agenda.
07/09/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 9, 2005

Wocky Redsar
Castro Engineering Corp.
3580 West Ina Road, Suite 200
Tucson, AZ 85741

Subject: S05-030 Dos Rios Tentative Plat

Dear Wocky:

Your submittal of June 9, 2005 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

5 Copies Revised Tentative Plat (landscape, zoning, engineering, community planning, DSD)

5 Copies Revised Landscape Plan (engineering, community planning, landscape, Zoning, DSD)

2 Copies Revised Drainage Report (engineering, DSD)

2 Copies Elevations (community planning, DSD)

Should you have any questions, please call me at 791-5608, ext 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 293-2115
07/09/2005 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: S05-030
Dos Rios, Lots 1- 143 and Common Areas "A" - "C"
Tentative Plat

TRANSMITTAL: 07/09/05

DUE DATE: June 23, 2005

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is March 27, 2006.

2. This comment was not fully addressed. Will existing easements as platted per the previous subdivision plat be abandoned by separate instrument, if so list the recordation data on the plat and submit copies of the documents indicating the abandonment.

Previous Comment: If applicable indicate the location of all existing easements. Clarify if existing easements on site are to be abandoned by separate instrument. DS 2-03.2.3.C

3. The dimension for the east 75-foot R/W as depicted on the cross section for Alvernon Way and the other dimensions do not add up. I acknowledge that the R/W from the centerline of Alvernon to the property line is greater than 75 feet but the dimension as depicted does not work. Please revise as required or clarify the discrepancy.

Previous Comment: Please review and revise the street cross section detail drawing for Alvernon Way. The right of way numbers don't seem to work. Also please draw, label, and dimension on the plan the future curb and sidewalk for both Alvernon Way and Benson Hwy. DS 2-03.2.3.D

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

DGR C:\planning\cdrc\tentativeplat\S05030tp2.doc
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: tentative plat, and additional requested documents.