Plan Number: S04-190
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S04-190
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/01/2005 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: VACTOR RANCH
Lots 108-126
S04-190

Tucson Electric Power Company (TEP) has no objection to the tentative plat
submitted for review June 21, 2005.

As you are aware, there are existing electrical facilities within the
boundaries of this subdivision. All relocation costs will be billable to
the developer.

TEP will provide a preliminary electrical design on the Approved Tentative
Plat within fifteen (15) working days upon receipt of the plat. Additional
plans necessary for preparation of the design are: building plans including
water, electrical, landscape, sidewalk and paving plans. Also, submit the
AutoCAD version of the plat on a CD or email to lcastillo@tep.com
<mailto:lcastillo@tep.com> . Should you have any questions, please contact
me at (520) 917-8745.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
07/05/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Craig Gross DATE: June 23, 2005
Planning Administrator FROM: Paul Machado
Engineering Division

SUBJECT: Vactor Ranch, 7300 E. Vactor Ranch Trail
Tentative Plat S04-190 (Second Review)
T13S, R15E, Section 32

RESUBMITTAL REQUIRED: Tentative Plat.

The Tentative Plat (TP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. The titles on sheets 2, 3 and 4 should match sheet no. 1. Also the book number in the title block is repeated. IE: Bk.BK.____at M&P at PG._____.
3. Re-label all commons areas in the following manner and this must be reflected on the Final Plat also. A keynote explaining the labels will be sufficient, ie.:
Common Area "A" - Streets
Common Area "B" - Drainage/Recreation Facilities
Common Area "C" - Recreation Facilities
Common Area "D" - Drainage Facilities
Common Area "E" - Landscaping
The commons areas are labeled differently according to note 7 and the title block, correct as required. Explain how the basins are going to be used recreationally?
4. Per condition no. 6, an archeological assessment and survey must be performed before any grading or ground modification takes place.
5. Show the proposed pad grades for each lot.
6. The neighborhood meeting as specified per condition no. 10 shall be adhered to.
7. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. This comment was directed to the drainage swale next to lots 119 and 120.
8. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. List whether the datum is NVGD 1929 or NAVD 88.
9. Show administrative address on plat. Label as "Administrative Address" Previous comment.


Drainage Report:
1. The DR has been accepted conditionally for tentative plat purposes. The following comments must be addressed prior to the acceptance of the DR and the issuance for the grading permit.
2. Provide details of the retention basin, including cross-sections and dimensions. Per previous comment.
3. Show the project address on the cover of the Drainage report. Per previous comment.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7300 E. Vactor Ranch CDRC 2
07/07/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this TP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
07/07/2005 JOE LINVILLE LANDSCAPE REVIEW Denied The following comments constitute the first review of the landscape and native plant preservation plan. Additional comments may be forthcoming pending review of any changes requested by other agencies.

1) Submit a native plant preservation plan that complies with the provisions of LUC 3.8 and DS 2-15.0
Aditional comments may apply pending receipt of the requested document.

2) The RCP must be in conformance with the design policies and criteria of the General Plan and any of its components, including any applicable adopted area and neighborhood plans.

The following standards from the Sabino Canyon-Tanque Verde Neighborhood Plan apply.

A) Grade differential between new and existing development or the natural grade to be kept to a minimum. Finished floor elevation for surrounding properties is to be provided on grading plans. Where the grade differential between existing adjacent finished floor and proposed finished floor is greater than two feet, applicant must notify adjacent property owners prior to submittal of grading plan to Development Services.
See also DS 11-01.8.1.

B) Minimize graded areas on new development sites to preserve wildlife habitats and mature riparian and native, desert vegetation. C9-96-01 also requires that all attempts be made to preserve existing trees and to transplant trees only as a last resort.

3) Revise the native plant preservation plan to preserve and, only as a last resort, transplant all trees with a caliper of four inches or greater. C9-96-01

4) Preserve additional trees adjacent to Lot 19 per C9-96-01 condition #3. Existing vegetation along the margins of drainageways are to be preserved-in-place.

5) Demonstrate how the common areas are handicap accessible. Provide proposed grades and existing grades for the adjoining sidewalk areas. C9-96-01

6) The native plant preservation plan requires revision to include a summary of the disposition of each protected species and a schedule for the color-coded flagging. Refer to DS 2-15.0 for additional plan requirements. The landscape plan must also include the summary per DS 2-15.3.4.B.2.

7) An irrigation plan is required. Revise Landscape Note 5 on sheet 1 of the landscape plan. Provide a preliminary irrigation plan including the source of irrigation water, system specifications, design, and layout (Development Standard 2-
06.5.4.A and 2-06.5.4.B).

8) Revise the landscape plans to eliminate conflicts with utility easements. LUC 3.7.2.6.B
Show utility easements on the landscape plans.
DS 2-07.2.2.E

9) Revise the native plant preservation plan to identify the common areas in accordance with the tentative plant.

10) The native plant preservation application submitted is not approved. The document is used for applications in Pima County jurisdiction subject to PCC Sec. 18.72 only.

11) The landscape and native plant preservation plans when approved will be archived in black and white. Revise the documents to insure that symbols and other plan features will be distinguishable upon reproduction in black and white.
07/07/2005 FRODRIG2 PIMA COUNTY WASTEWATER Denied July 1, 2005

To: Paul Nzomo, P.E., Coronado Engineering & Development, Inc.

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tim Rowe, P.E. (520-740-6563), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Vactor Ranch, Lots 108-126 and Common Area A
Tentative or Preliminary Plat - 2nd Submittal
S04-190

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



Sheet 2: Item 7 of my January 20, 2005 review letter was not adequately addressed. Please show the manhole numbers shown on Pima County Wastewater Management section or base maps, for the two existing public sewer manholes that will be the two points of connection to the public sewer system.

Sheet 2: Sewer line S-3 may not connect to MH1 as shown, as this requires the wastewater to turn more than 90 degrees at this manhole. Add another manhole to the design in the private cul-de-sac, so that the wastewater will turn no more than 90 degrees where it turns at MH1.

Sheet 3: Revise the proposed SW invert elevation for EX MH1 and the proposed NW invert elevations for EX MH2 to show that this connection will be made via PC/COT Standard Detail 301. The bases of the existing manholes may not be cored.

Sheet 3: The invert elevation for EX MH1 and the slope and length shown for proposed sewer line S-1 does not produce an invert elevation anything close to the invert elevation shown for MH1. The invert elevation shown for MH2 is the same as its rim elevation. The manhole and rim elevations shown for MH 4 indicate sewer line S-4 will have insufficient cover. The invert elevations shown for EXMH2 and MH5 indicate that sewer line S-5 will run uphill. Please revise the sewer design data as necessary.

4. We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $78.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter
07/09/2005 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: S04-190
Vactor Ranch, 108-126, and Common Area "A"
Tentative Plat - Residential Cluster Project

TRANSMITTAL: 07/09/05

DUE DATE: July 6, 2005

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is December 22, 2005.

2. Please address the following items related to the location map. DS 2-03.2.1.D

A. Draw and label the City of Tucson / Pima County jurisdictional limits. Previous Comment was not completely addressed: The City's jurisdictional limits will be shown, if within the mapped area.

3. Please submit a separate response letter that that lists or demonstrates how all the rezoning conditions have been met. The response letter should be specific to each rezoning condition even if several of the conditions have been met as a result of the previous Phase of Vactor Ranch.

Previous Comment: Per the rezoning map, this site has gone through a rezoning and any rezoning conditions that were authorized at the time of rezoning are still applicable. Provide with the next submittal package a copy of the rezoning conditions as approved by Mayor and Council and a separate response letter that states how all the rezoning conditions will been met. The conditions must be listed on the tentative plat verbatim. The rezoning case C9-96-01 must be listed in the lower right corner of all sheets. Additional comments may be forthcoming on this issue. DS 2-03.2.2.B.3

4. All existing easements that are to be abandoned must be abandoned prior to approval of the tentative plat. The recordation data of each existing easement to be abandoned must be listed on the tentative plat.

Previous Comment: All proposed or existing easements must be drawn and labeled on the plat. The location, purpose, width and recordation information of existing easements must be labeled on the plan. DS 2-03.2.3.C. and DS 2-03.2.4.J

5. Cross-section 2/3 must include reference to the width of the Common Areas as approved per the previous plat. Also clarify if the cross section applies to Vuelta Rancho Mesquite roadway. If so list the street name under the cross section detail.

Previous Comment: The existing or proposed curb and sidewalk locations for both Vactor Ranch Trail and Vuelta Rancho Mesquite roads must be drawn, labeled, and dimensioned. DS 2-03.2.3.D

6. This comment has not been fully addressed. Visitor parking must be provided for the entire subdivision as proposed. Lots 119 through 126 do not appear to be within 150 feet of the parking spaces provided in the new interior street. Per cross-section 2/3 on street visitor parking or parking lanes are not allowed on either side of Vactor Ranch or Vuelta Rancho Mesquite roadways. How will the visitor parking be provided for these units. Additional comments may be forthcoming and possibly an application for approval/support by the CDRC committee for development standard modification request for this development standard may be required prior to approval of the tentative plat.

Previous Comment: Parking on both sides of the street is required. Draw a cross section that depicts the construction and dimensions of the proposed street. Also the existing streets on which the boundary lots have frontage must be designed to provide on street parking. On street parking spaces must be provided within 150 feet of the property lines of the proposed boundary lots. The distance is not determined as the crow flies. It is determined based on the route necessary to get to from the parking spaces to the lots. Draw the requested detail drawings for the street cross section and depict the parking spaces based on an 8'x23 parking space. DS 2-03.2.3.G

7. Previous comment was not addressed. Address as requested.

Depict and label the perimeter boundary building setback based on the adjacent zoning and the street perimeter building setbacks. The street perimeter building setbacks from the existing street is to be based on the greatest of 21 feet or the height of the structure.

Draw lot typical detail drawings for an interior lot and for a corner lot and depict and label the interior and street building setbacks inclusive of the principal structure and garage. List the proposed building heights of the structures. DS 2-10.3.1.A. and .B

8. Address the following items under the RCP data text block. DS 2-10.3.1.A - .D

a. The allowed lot coverage under the RCP designator RCP-9 is 75%. Please revise the coverage note under the RCP data text block. Previous comment: Revise the site coverage calculations based on the correct RCP designator.

b. Because this subdivision is a continuation of or final phase of the previously approved Vactor Ranch subdivision the building setbacks may be 3' from the property line for all new lots abutting the existing Vactor Ranch subdivision. Remove or revise the note listing the rear building setback of 10-foot or ¾ hgt of the structure.

c. The front street building setback for lots 110 through 116 may be based on the allowed building setback as listed in LUC section 3.2.6.5. The ADT of the interior street is less than 140.

9. This item must be addressed and prior to approval of the tentative plat. The requested documents must be provided to the Department of Urban Planning and Design for review and approval. Please provide documentation from the DUPD confirming approval.

Previous Comment: If the project is less than four (4) acres in size, by gross area, submit drawings, photographs, or a combination of both, showing how the architectural compatibility requirements of Sec. 3.6.1.4.A.3 of the LUC will be met. Ds 2-10.3.2.C

This site is less than 4 acres and must comply with this development standard. Submit the required documents as requested.

10. Please clarify if the existing CC&R's will be amended to except the annexation of the re-subdivision of Block "A". The submitted document does not provide the information required. Also an amended title sheet or sheets indicating the lots and common areas must be listed in the CC&R's. Submit a copy of the previously recorded CC&R's for review with the next submittal or during final plat review period.

Previous Comment: If copies of the CC&R's are available at this time submit copies with the next tentative plat submittal. DS 2-10.3.2.E

11. Address the following items related to the LUC RCP criteria.

a. When the RCP site area is less than four (4) acres, architectural design of the RCP must be compatible with, or complementary to, the design characteristics of those existing single-family detached or attached structures along the same block frontage and the block frontage across the street. If the RCP is proposed on a corner lot, then its design will also be compatible with, or complementary to, the design characteristics of existing residential development on the opposite lot corners. Architectural compatibility will be in compliance with design criteria in applicable adopted neighborhood or area plans.

b. Barrier-free accessibility for the elderly and physically disabled shall be provided to twenty-five (25) percent of the ground floor units and all common use areas, including parking areas, within the project. A detail drawing that demonstrates how the barrier free accessibility will be accomplished must be added to the drawing. The lots that will be barrier free must be listed as a general note or under the RCP data text block

c. Parking spaces required for visitors will be uniformly distributed throughout the project and may be located in parking areas or on streets designed with designated parking lanes. Additional parking spaces located on individual lots will not be considered to satisfy this requirement, as these spaces are located on private property and cannot be used by the guests of other residents.

d. If common parking areas are provided within the site area, they must meet the following requirements.
1. All parking areas shall comply with the vehicular use area requirements of Sec. 3.3.0.
2. No more than sixty (60)-parking spaces shall be located in any single outdoor parking area. Such parking areas will be separated by a minimum of thirty (30) feet, utilizing buildings and landscaping or just landscaping. The same PAAL may provide access to two (2) or more parking areas.
3. Every RCP shall have a pedestrian circulation system connecting all elements of the RCP to all units. The system shall be physically separated from the vehicular circulation system, except where the system intersects a PAAL or street.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

DGR C:\planning\cdrc\tentativeplat\S04190tp2.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat and CC&R's and additional requested documents
07/11/2005 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S04-190 Vactor Ranch 07/08/05

( x ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-96-01

NEIGHBORHOOD PLAN: Sabino Canyon - Tanque Verde N.P.

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: 07/06/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( x ) Resubmittal Required:
( x ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: Eric Anderson 791-4505 DATE: 07/06/05

Department of Urban Planning and Design
Vactor Ranch: S04-190

1. To increase appearance, shade and longevity diversity please provide some longer living trees, including evergreens that are in the Low Water Use Drought Tolerant List. This can include pines, or other evergreen trees, and oaks. Also, to increase the opportunity as a semi-active common area, please provide grass in common area A and do not locate any vegetation that has thorns at maturation in the common areas.

2. Please locate canopy trees along the rear portions of lots 108 and 109, along the sidewalk.
































DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S04-190 Vactor Ranch 01/05/05

( x ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-96-01

NEIGHBORHOOD PLAN: Sabino Canyon - Tanque Verde N.P.

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: 01/19/05

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( x ) Resubmittal Required:
( x ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: E. Anderson 791-4505 DATE: 01/05/05

Department of Urban Planning and Design
Vactor Ranch: S04-190

1. The tentative plat has an associated rezoning case (C9-96-01). The rezoning case has 16 conditions. Numerous relate to the Department of Urban Planning and Design's review. None of the rezoning conditions that the Department of Urban Planning and Design needs to review are addressed in the one page tentative plat submittal. Please address all the rezoning conditions.

2. Please list all the rezoning conditions on the tentative plat.
07/18/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: July 14, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, S04-190 Vactor Ranch: Resubmittal: Development Plan

CC: Craig Gross
Patricia Gehlen, Development Services


Approved.






Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov
07/19/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 19, 2005

Paul Nzomo
Coronado Engineering
1010 N. Finance Center Dr, #200
Tucson, AZ 85710

Subject: S04-190 Vactor Ranch Tentative Plat

Dear Paul:

Your submittal of June 21, 2004, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Tentative Plat (zoning, engineering, landscaping, community planning, wastewater, DSD)

5 Copies Revised Landscape Plan (zoning, landscaping, engineering, community planning, DSD)

2 Copies Revised Drainage Report (engineering, DSD)

2 Copies Revised NPPO (landscaping, DSD)

3 Copies Revised CC&R's (engineering, zoning, DSD)

Should you have any questions, please call me at 791-5608.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/