04/03/2006 MARILYN KALTHOFF START ASSURANCES RECEIVED Completed
04/05/2006 LAITH ALSHAMI ENGINEERING FOR ASSIGNMENT Completed To: Patricia Gehlen DATE: April 14, 2006
CDRC/Zoning Manager

SUBJECT: 7300 E. Vactor Ranch Trail
Final Plat Assurances S05-190 (Second Review)
T13S, R15E, Section 32

RESUBMITTAL REQUIRED: Final Plat Assurances.

The Final Plat assurances cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat Assurances:

1. Please include a response letter to the comments along with the corrected copies of the assurances.
2. The Amendment to the CCR's does not contain conditions for retention basin and/or drainageway maintenance. Revise as required or submit an additional amendment.
3. The Pre-annexation and Development Agreement is not for Vactor Ranch. The submitted development agreement is for the property owned by Wycozona, L.L.C. and is approximately 173 acres.
4. The Amendment to trust - third party agreement, the Agreement to construct subdivision improvements - third party trust and/or references to the final plat do not match the title of the final plat. The documents and final plat title must match verbatim.
5. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7300 E. Vactor Ranch Tr. Assur.2
04/14/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: April 14, 2006
CDRC/Zoning Manager

SUBJECT: 7300 E. Vactor Ranch Trail
Final Plat Assurances S05-190 (Second Review)
T13S, R15E, Section 32

RESUBMITTAL REQUIRED: Final Plat Assurances.

The Final Plat assurances cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat Assurances:

1. Please include a response letter to the comments along with the corrected copies of the assurances.
2. The Amendment to the CCR's does not contain conditions for retention basin and/or drainageway maintenance. Revise as required or submit an additional amendment.
3. The Pre-annexation and Development Agreement is not for Vactor Ranch. The submitted development agreement is for the property owned by Wycozona, L.L.C. and is approximately 173 acres.
4. The Amendment to trust - third party agreement, the Agreement to construct subdivision improvements - third party trust and/or references to the final plat do not match the title of the final plat. The documents and final plat title must match verbatim.
5. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7300 E. Vactor Ranch Tr. Assur.2
04/14/2006 TAMI ACHONG ENGINEERING ASSURANCES RECEIVED/SENT TO CITY ATTORNEY Denied To: Patricia Gehlen DATE: April 14, 2006
CDRC/Zoning Manager

SUBJECT: 7300 E. Vactor Ranch Trail
Final Plat Assurances S05-190 (Second Review)
T13S, R15E, Section 32

RESUBMITTAL REQUIRED: Final Plat Assurances.

The Final Plat assurances cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat Assurances:

1. Please include a response letter to the comments along with the corrected copies of the assurances.
2. The Amendment to the CCR's does not contain conditions for retention basin and/or drainageway maintenance. Revise as required or submit an additional amendment.
3. The Pre-annexation and Development Agreement is not for Vactor Ranch. The submitted development agreement is for the property owned by Wycozona, L.L.C. and is approximately 173 acres.
4. The Amendment to trust - third party agreement, the Agreement to construct subdivision improvements - third party trust and/or references to the final plat do not match the title of the final plat. The documents and final plat title must match verbatim.
5. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7300 E. Vactor Ranch Tr. Assur.2