Plan Number: S04-183
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S04-183
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2005 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: January 11, 2005


RE: Assessor’s Review and Comments Regarding Final Plat
S04-183 La Paloma Charter School T141506 (133-16)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.







Susan King
01/11/2005 FRODRIG2 PIMA COUNTY WASTEWATER Denied January 10, 2005

TO: Linda Trowbridge
Gregor & Grenier Engineering

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: La Paloma Charter School, Blocks 1 & 2
Final Plat – 1st Submittal
S04-183


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 1. Add the following General Note

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

As the tentative plat did not provide the number of wastewater fixture unit equivalents which would determine if a sewer service agreement is necessary, this final plat may not be approved. Therefore, we will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents. The next submittal of this project will be the 2nd submittal. No payment is required with your next submittal.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,




Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
01/14/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: LA PALOMA CHARTER SCHOOL
S04-183

Tucson Electric Power Company (TEP) has reviewed and approved the tentative
and final plats for this project. Enclosed is a copy of TEP's facility map
showing the approximate location of existing facilities.

In order to apply for electric service, call the New Construction Department
at (520) 770-2062. Contact the Project Manager, Marc Romito for any project
scheduling questions, he can be reached at (520) 917-8732. Also, submit two
(2) final sets of plans including site, off-site improvement and electrical
load plans. If easements are required, they will be secured by separate
instrument.

Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8745
Cell Phone: (520) 904-2668
Fax: (520) 917-8700
01/19/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: January 19, 2005

To: Craig Gross
Planning Administrator
FROM: Loren Makus, EIT
Engineering Division

SUBJECT: La Paloma Charter School
Final Plat S04-183 (First Review)
T14S, R15E, Section 06

RESUBMITTAL REQUIRED: Final Plat, Assurances, CC&Rs

The Final Plat has been reviewed by the Engineering Division and we do not recommend approval at this time. The following review comments must be addressed.
1. Show retention/detention areas in a surveyable and readily retraceable manner. (DS 2-03.6.4.I)
2. Provide a complete assurances package. The plat cannot be scheduled for Mayor and Council approval until the assurances have been approved by the DSD Engineering Administrator. (DS 2-03.7.1.G)
3. As in the Tentative Plat, clarify how the retention requirements will be provided when block 2 of the plat is developed.

Submit a revised Final Plat and assurances package. Include a detailed response letter, detailing how each comment has been addressed.
If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
02/02/2005 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
02/02/2005 CRAIG GROSS COT NON-DSD REAL ESTATE Approved no comments
02/02/2005 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner
FOR: Principal Planner

PROJECT:
La Paloma Charter School
S04-183
Final Plat

TRANSMITTAL: February 2, 2005
DUE DATE: February 2, 2005

1. Add the subdivision case number (S04-183) to the lower right hand corner of the final plat. DS 2-03.6.1.K

2. Revise all dates in the Recording Block to read "2005".
DS 2-03.6.2

3. Tentative Plat approval is required prior to final plat approval.
DS 2-03.6
LUC 4.1.7.3

3. Remove general note 1 as this is a tentative plat note. DS 2-03.6.2

4. Remove all of the zoning indicators from sheets 2 of the final plat. DS 2-03.6.1.H

5. Provide a copy of CC&R's for the subdivision. DS 2-03.6.6

6. Reference recorded subdivision plats by book and page numbers in the location map. DS 2-03.6.1.D.2

7. Add the title company name and trust number to the Beneficiary Block. DS 2-03.6.3.C


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
12/17/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/20/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-183 LA PALOMA CHARTER SCHOOL/FINAL PLAT
DATE: 12/20/04



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***