Plan Number: S04-181
Parcel: Unknown

Address:
687 S BONANZA AV

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S04-181
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/30/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Craig Gross DATE: June 30, 2005
Planning Administrator

SUBJECT: 687 S. Bonanza Ave., Desert Enclave
Final Plat S05-181 (First Review)
T14S, R15E, Section 14

RESUBMITTAL REQUIRED: Final Plat.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Final Plat:

1. Please provide North arrow and scale per D.S. 2-02.2.1.
2. Please include a response letter to the comments along with the corrected copies of the FP.
3. Submit the Subdivision Improvement Assurances for review.
4. The title block of the plat must match the Subdivision Assurances verbatim.
5. Show the symbol on the legend for the standard monument detail 103 on the centerline of the proposed streets per D.S. 2-03.6.5.6.
6. Please re-label all common areas that may be used in a dual and/or single use capacity per D.S. 2-03.6.4.C. For example, a Ret./Det. Basin may also be used as a recreation facility or only as a drainage facility or drainage channel and this must be reflected on the Final Plat. A key note explaining the labels could be used in conjunction with the labels, ie.:
Common Area "A" - Streets
Common Area "B" - Drainage/Recreation Facilities
Common Area "C" - Recreation Facilities
Common Area "D" - Drainage Facilities
Common Area "E" - Landscaping
7. Show sight visibility triangles per D.S. 2-02.2.1.10.
8. Correct the mile of new public street on general note 3 per D.S. 2-03.6.2.C.
9. Show the "Certification of Survey" verbatim per D.S. 2-03.6.3.A.
10. Show a 1' no access esmt. along the west property line of lots 13 and 14 and the Common Area "C" between the two lots.
11. Please submit a copy of the subdivision boundary closure calculations.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/687 S. Bonanza Ave. FP
07/07/2005 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-181 DESERT ENCLAVE/FINAL PLAT
DATE: 7/06/05



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Delete Desert Enclave Drive adjacent to lots 13 & 14. Karst (change the suffix to Place or Court) can be adjacent to lots 8-13 and Caldera (change the suffix to Place or Court) can be adjacent to lots 14-19.







es
07/25/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
07/25/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond July 25, 2005

TO: Greg Carlson, P.E.
Greg Carlson Engineering, LLC

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Desert Enclave, Lots 1-28 and Common Areas A-C
Final Plat – 1st Submittal
S04-181


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


A public Sewer Service Agreement for the proposed number of residential lots has been sent to your office. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve the Mylars of the final plat.

SHEET 1. Add the following two General Notes

THE LANDSCAPING WITHIN ALL PUBLIC SEWER EASEMENTS SHOWN HEREON SHALL BE IN ACCORDANCE WITH THE PLANTING GUIDELINES OF PC/COT STANDARD DETAIL WWM A-4.

NO PERMANENT STRUCTURES (I.E., MASONRY WALLS, FENCES, ETC.) MAY BE CONSTRUCTED ON OR THROUGH THE PUBLIC SEWER EASEMENTS SHOWN HEREON WITHOUT SEPARATE WRITTEN CONSENT OF THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

The signed copy of the tentative plat for this project requires certain information that was shown on its last submittal prior to approval. Please revise the following:

Sheet 2. Show the southern border of the existing public sewer easement.
Sheet 4. Show the invert elevations for all newly proposed manholes.
Sheet 4. Show the southern border of the existing public sewer easement.
Sheet 4. Two newly proposed manhole 2s are shown. Revise the layout to show one newly proposed manhole 2 and one newly proposed manhole 1.

Upon completing these revisions, please resubmit a signed copy of the tentative plat.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
07/27/2005 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
Desert Enclave
S04-181
Final Plat

TRANSMITTAL: July 27, 2005
DUE DATE: July 25, 2005


1. Remove the linear footage from general note 3 as it is not correct and does not correspond to the distance shown in miles. DS 2-03.6.2.C


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
08/09/2005 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: DESERT ENCLAVE
Lots 1-28
S04-181

Tucson Electric Power Company (TEP) has received the final plat submitted
for review June 24, 2005. This Company is unable to approve the plat at
this time.

TEP is in the process of completing the preliminary electrical design to
determine our easement requirements. The design should be completed
approximately August 9, 2005. The designer for the project is Frank
Grijalva he can be reached at (520) 918-8361.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
08/10/2005 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)
Sahuarita, Az. 85629

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: July 22, 2005


RE: Assessor’s Review and Comments Regarding Final Plat
S04-181 Desert Enclave T141514 (133-39)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

x Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Jessica Shettleroe
08/11/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 11, 2005

Greg Carlson, P.E.
Greg Carlson Engineering, LLC
1521 East Broadway Blvd.
Tucson, AZ 85719

Subject: S04-181 Desert Enclave Final Plat

Dear Greg:

Your submittal of June 24, 2005, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Final Plat (addressing, wastewater, TEP, engineering, zoning, DSD)



ASSURANCES TO BE SUBMITTED TO THE CDRC OFFICE

Should you have any questions, please call me at 791-5608.

Sincerely,


Patricia Y. Gehlen
CDRC Manager





All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 624-4197