Plan Number: S04-152
Parcel: Unknown

Address:
7855 S WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S04-152
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/02/2005 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-152 DESERT STONE/REVISED FINAL PLAT
DATE: 9/02/05



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1.) Change Hidden Places Lane to Loop.

2.) Label Grayhawk Ranch Road on pg. 1.

3.) Change Diablo Sentinal to Sentinal Stone Drive on pg. 4.

4.) Change lot 149 to 152 on pg. 5.
09/02/2005 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-152 DESERT STONES/REVISED FINAL PLAT
DATE: 9/23/05



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project with the condition that all items listed on Comment Letter dated 9/02/05 are corrected on Mylar.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***






es
09/06/2005 LAITH ALSHAMI ENGINEERING REVIEW Approv-Cond Laith Alshami, Engineering and Floodplain Review, 09/06/2005,

SUBJECT: Desert Stone
S04-152, T15S, R15E, SECTION 19

RECEIVED: Final Plat and CC & R's on August 29, 2005

The subject submittal has been reviewed. The Final Plat is recommended for a conditional approval subject to the following:

1. The CC & R's index page numbers appear to be incorrect. Revise.
2. It appears that the CC & R's do not address the maintenance responsibility of the offsite drainage easement dedicated to this development to allow the channelization and the maintenance of the Old Rodeo Wash west of Wilmot Road. Revise as necessary.


SUBMITTAL REQUIRED: Final Plat Mylar and revised CC & R's
09/09/2005 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: DESERT STONE
Lots 1-260
S04-152

The Final Plat for the subject project will meet this Company's easement
requirements.
Please forward any resubmittals of the final plat to this office.

Electric service will be provided to this subdivision in accordance with the
rules and regulations approved by the Arizona Corporation Commission.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
09/12/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
09/13/2005 DAN CASTRO ZONING REVIEW Approved
09/30/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approved September 29, 2005

To: Pattie Davis, MMLA

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tim Rowe, P.E. (520-740-6563), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Desert Stones, Lots 1-260 and Common Areas A and B
Final Plat - 2nd Submittal
S04-152

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



Sheets 1, 3, 6, 7 & 8: Sheets 3, 6, 7 & 8 of this plat shows a large public drainageway being created through this subdivision, but the 5th paragraph of the Dedication on Sheet 1 indicates that the title to all drainageways will be vested in an association of individual lot owners.

If the intent of this plat to create a public drainageway, take both of the following actions:

Revise the 2nd paragraph of the Dedication to read:

WE, THE UNDERSIGNED, DO HEREBY DEDICATE AND CONVEY TO THE PUBLIC ALL RIGHTS OF WAY SHOWN HEREON, INCLUDING ALL PUBLIC STREETS AND PUBLIC DRAINAGEWAYS, AND GRANT ALL PUBLIC EASEMENTS SHOWN HEREON TO THE PUBLIC AND ALL UTILITY COMPANIES FOR THE PURPOSES OF ACCESS, INSTALLATION AND MAINTENANCE OF PUBLIC SEWERS, UTILITIES, AND OTHER USES AS DESIGNATED BY THIS PLAT.

Revise the 1st sentence of 5th paragraph of the Dedication to read:

TITLE TO THE LAND OF ALL COMMON AREAS AND PRIVATE DRAINAGEWAYS AS SHOWN HEREON WILL BE VESTED IN AN ASSOCIATION OF INDIVIDUAL LOT OWNERS . . .

If this large drainageway is to be private drainageway or common area, it needs to be identified as such on Sheets 3, 6, 7 & 8.

Sheet 2: Label the common areas, and show all of the easements using dashed, rather than solid lines on this sheet.

Sheet 7: If the drainageway is to be public drainageway, the 20' public sewer, water and pedestrian easement granted to by this plat (identified by Keynote 7) may be omitted.

We have sent to your office under separate cover three originals of a Sewer Service Agreement for the proposed number of residential lots. Once the three originals of the Agreement have been signed by the Owner of Record, and notarized, they must be returned to this office to satisfy the necessary requirements needed to approve the final plat.

We will require a revised set of bluelines, and a response letter, addressing these comments. This office will expedite the review of the next submittal, but only if the cover letter accompanying the next submittal clear indicates THE REVIEW OF THIS FINAL PLAT IS TO BE EXPEDITED PER TIM ROWE'S SEPTEMBER 29TH REVIEW LETTER. Additional comments may be made during the review of these documents.

County Ordinance 2003-29 went into effect on April 11, 2003. This ordinance requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the third ( 3rd ) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER ) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
09/30/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond `COMMUNITY DESIGN REVIEW COMMITTEE
CITY OF TUCSON - DEVELOPMENT SERVICES

September 30, 2005

Pattie Davis
MMLA
800 East Wetmore Road, #110
Tucson, AZ 85719

Subject: S04-152 Desert Stone Final Plat

Dear Pattie:

The above referenced project has been CONDITIONALLY APPROVED by the Community Design Review Committee. Please make the any necessary corrections and submit the following documents:

(2) Title reports current within the last (30) days.
(1) Executed Final Plat Double Matte Océ or Photo Mylar.
(1) * Check made to "Reproductions, Inc." in the amount of $8.50 per plat page for Mayor & Council distribution.
(1) * Check made to "Reproductions, Inc." in the amount of $55.00 per plat page for recorded plat distribution.
(1) Check made to "Pima County Recorder" in the amount of $20.00 per plat page plus a $4.00 handling fee, along with CC&R fees if applicable. CCR fees are $9.00 for the first 5 pages and $1.00 for each additional page.
(1) Executed and notarized CC&Rs (if applicable).

*Please do not combine the checks for "Reproductions, Inc.". They are processed at different times and require separate checks. An account number is also acceptable.

Assurances (if applicable) must be reviewed by the City Attorney's Office prior to being presented to the Mayor and Council. Plats, CCR's and assurances must be approved at the same Mayor and Council Meeting. Please expect 3 -4 weeks from the date submitted to the date scheduled for Mayor and Council approval.

MYLARS MUST BE REVIEWED AND APPROVED BY PIMA COUNTY WASTEWATER PRIOR TO SUBMITTAL TO CITY OF TUCSON CDRC OFFICE.

Sincerely,


Patricia Gehlen
CDRC Manager
All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
09/30/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approved October 11, 2005

To: Pattie Davis, MMLA

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tim Rowe, P.E. (520-740-6563), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Desert Stones, Lots 1-260 and Common Areas A and B
Final Plat Mylars – 1st Submittal
S04-152

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat Mylars as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.



If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File