Plan Review Detail
Review Status: Completed
Review Details: FINAL PLAT REVIEW
Plan Number - S04-152
Review Name: FINAL PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2005 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 04/19/2005 | KAY MARKS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S04-152 DESERT STONES/FINAL PLAT DATE: April 18, 2005 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: Change Wilmont to Wilmot on all applicable pages. Spell out all street suffixes except on Location Map. Include page numbers on pg. 2. Add suffixes to all new street names. Delete Diablo Sunrise Road adjacent to lot 1. This entire street should be Sentinal Stone with the correct suffix. jg |
| 04/26/2005 | DAN CASTRO | ZONING | REVIEW | Denied | COMMENTS 1. An applicant has one (1) year from the date of approval of the tentative plat to obtain approval and recordation of a final plat that complies with zoning and other development requirements in effect at the time of application. Since the tentative plat for this subdivision has not yet been approved, the approval date for this final plat may not be determined. In addition, the final plat may not be approved prior to approval of the tentative plat. Since the tentative plat has not yet been approved, any revisions made to the tentative plat which effect the final plat must also be made to the final plat. 2. Under the assurance block revise "Planning Director" to "Development Services Department Director." (D.S. 2-03.6.3.E) 3. Since the plat contains more than one (1) sheet, a small index drawing of the site showing the area represented on each sheet is to be placed on the first sheet. (D.S. 2-03.6.1.E) 4. The CC&R's must be revised as follows: On the cover sheet please reference all the subdivision information found in the title block located on each sheet of the final plat (i.e. subdivision name, number of lots, common areas, and RCP statement). If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. |
| 04/27/2005 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Ed Abrigo, Mapping Supervisor Pima County Assessor’s Office Mapping Department DATE: April 26, 2005 RE: Assessor’s Review and Comments Regarding Final Plat S04-152 Desert Stones T151519 (141-09) * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor’s Office requirements. _______ Plat does not meet Assessor’s Office requirements. COMMENTS: Thank you for your submittal. NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. Susan King |
| 04/29/2005 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 04/29/2005 SUBJECT: Desert Stones S04-152, T15S, R15E, SECTION 19 RECEIVED: Final Plat and CC & R's on April 01, 2005 The subject submittal has been reviewed. We offer the following comments: 1. All lettering and dimensions will be equivalent of twelve (0.12) point or greater in size (D.S. 2-03.6.1.C). 2. Revise the Certification of Survey to Match D.S. 2-03.6.3.A. 3. The DEDECATION Block is missing the Trust Number. 4. The BENEFICIARY Block is missing the Trust Number (D.S. 2-03.6.3.C). 5. Revise the ASSURANCES Block signature lines to include the "City of Tucson Development Services Department Director" and the "City of Tucson Development Services Department Engineering Administrator" (D.S. 2-03.6.3.E). 6. It is not clear what the 30' El Paso Natural Gas easement dimension describes on sheet 6/8. The length and the width of the easement appear to be greater than 30'. 7. The existing El Paso Natural Gas easement and the proposed Public Drainageway widths should be provided as required by D.S. 2-03.6.4.A. 8. Show the required setbacks from the proposed detention/retention basins as required by D.S. 2-03.6.4.E. 9. The description of Common Area "B" should include the proposed detention/retention basins. Revise the Title Block accordingly. 10. Show the limits of the 100-year floodprone area in a surveyable manner as required by D.S. 2-03.6.4.F. Contained runoffs can be indicated by a note. 11. Show detention/retention areas in a surveyable manner as required by D.S. 2-03.6.4.I. Showing the Common Area within which the basins are located is not sufficient. 12. Provide an index to the CC & R's. 13. It is not clear if the if Section 3.9 of the CC & R's includes the offsite drainage easement dedicated to this development to allow the channelization and the maintenance of the Old Rodeo Wash west of Wilmot Road. 14. The CC & R's should specifically address the maintenance of the Common areas and drainage facilities by the Home Owner's Association. The CC & R's should include a paragraph, which addresses the maintenance of the drainage structures in details (i.e. what facilities to be inspected and maintained, how, when, by whom, the detention/retention basin maintenance list, keeping records, and repair decisions, etc). This Office also recommends including the Drainage Facilities maintenance checklist in the CC & R's, as an exhibit, to allow the Home Owners Association access to it and facilitate their maintenance responsibilities. 15. Submit a copy of the Assurances with the next submittal as required by D.S. 1-04.0. Prepare a detailed response that explains the revisions that were made and references the exact location in the drainage report and on the Tentative Plat where the revisions were made. RESUBMITTAL REQUIRED: Revised Final, CC & R's and Assurances |
| 04/29/2005 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | April 28, 2005 TO: Pattie Davis MMLA Psomas THRU: Craig Gross City of Tucson, Development Services Department FROM: Dickie Fernández, E.I.T. Pima County Development Services Department Development Review Division (Wastewater) SUBJECT: Desert Stone, Lots 1-260 and Common Areas A & B Final Plat – 1st Submittal S04-152 The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. SHEET 1. Add the following paragraph to the Dedication as a public sewer easement is shown on this project WE HEREBY GRANT TO PIMA COUNTY AND ALL UTILITY COMPANIES ALL PUBLIC EASEMENTS AS SHOWN HEREON FOR THE PURPOSES OF ACCESS, INSTALLATION AND MAINTENANCE OF PUBLIC SEWERS AND UTILITIES AND OTHER USES AS DESIGNATED BY THIS PLAT. A public Sewer Service Agreement for the proposed number of residential lots will be prepared as soon as the trust company’s name and the trust number is provided. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve the Mylars of the final plat. We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents. The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter. For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above mentioned comments, please contact me. Sincerely, Dickie Fernández, E.I.T. Telephone: (520) 740-6947 Copy: Project |
| 05/03/2005 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Denied | SUBJECT: DESERT STONES Lots 1-260 S04-152 Tucson Electric Power Company (TEP) has reviewed the final plat submitted for review April 1, 2005. TEP is unable to approve the plat at this time. TEP is in the process of completing the preliminary electrical design for this subdivision and it will approximately be completed by May 17, 2005, at which time we will send you the easement requirements for the subdivision. Liza Castillo Right of Way Agent Land Management Tucson Electric Power Co. (520) 917-8745 lcastillo@tep.com <mailto:lcastillo@tep.com> |
| 05/03/2005 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Denied | Page 5 of 8 Obtain and Show Dk & Page of easement for Public Drainageway purposes through EPNG parcel. Page 6 of 8 Obtain and Show DK & Page of easement for right of way purposes through EPNG parcel. |
| 05/04/2005 | CRAIG GROSS | ZONING-DECISION LETTER | REVIEW | Completed |