Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/17/2004 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond November 17, 2004

TO: Christopher Brozek, AICP, PE

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Enchanted Hills Townhomes, Lots 1-75 and Common Areas A-C
Final Plat – 1st Submittal
S04-065


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 1. Delete the last sentence of the fifth paragraph of the Dedication.

SHEET 1. Add the following text to the Dedication

COMMON AREAS AND PRIVATE EASEMENTS AS SHOWN HEREON ARE RESERVED FOR THE PRIVATE USE AND CONVENIENCE OF ALL OWNERS OF PROPERTY WITHIN THIS SUBDIVISION AND ARE GRANTED AS EASEMENTS TO PIMA COUNTY AND ALL UTILITY COMPANIES FOR THE INSTALLATION AND MAINTENANCE OF ABOVEGROUND AND UNDERGROUND UTILITIES AND PUBLIC SEWERS.

A public Sewer Service Agreement for the proposed number of residential lots has been sent to your office. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve the Mylars of the final plat.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
11/17/2004 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

RICK LYONS
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: November 16, 2004


RE: Assessor’s Review and Comments Regarding Final Plat
S04-065 Enchanted Hills Townhomes T141327 (119-22)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.







Susan King
11/17/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-065 ENCHANTED HILLS TOWNHOMES/FINAL PLAT
DATE: NOVEMBER 16, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***















jg
11/23/2004 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: ENCHANTED HILLS TOWNHOMES
Lots 1-75
S04-065

The Final Plat for the subject project will meet this Company's easement
requirements.
Please forward any resubmittals of the final plat to this office.

Electric service will be provided to this subdivision in accordance with the
rules and regulations approved by the Arizona Corporation Commission.

Please contact me at (520) 917-8745 if you have any questions.




Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8745
Cell Phone: (520) 904-2668
Fax: (520) 917-8700
11/23/2004 FRODRIG2 COT NON-DSD REAL ESTATE Approved No objection
12/02/2004 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond DATE: December 2, 2004
TO: Craig Gross; CDRC Coordinator
SUBJECT: San Marcos Terrace Final Plat Submittal Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S03-004

SUMMARY: The Final Plat, CC&R's, and assurance package were received by Engineering on October 20, 2004. Development Services Department Engineering Division has done a review of the received items and does not recommend approval at this time. These comments may be addressed on a mylar submittal, with CDRC's permission.

FINAL PLAT COMMENTS:
1) City of Tucson Development Standards (DS) Section No.2-03.8.1.A: Provide seals and signatures of Engineer and Surveyor on mylar submittal for approval.
2) DS Sec.2-03.7.1.B: If engineering information is provided on the final plat, the seal and signature of the responsible engineer is also required. For the Certification of Engineering, add that the basin setback information also has been prepared by the engineer of record, or clarify verbiage for the engineering information.
3) DS Sec.2-03.6.4.E: Show the required basin setback offset from the 100-year ponding limits within the lots adjacent to the basins.
4) DS Sec.2-03.6.4.G&H: For the south and east boundary, designate a 1 foot no-vehicular access easement.
5) DS Sec.2-03.6.5.C.3: Provide the boundary closure calculation sheet.
6) DS Sec.2-03.7.1.B: Provide a copy of the signed original CC&R's.
7) DS Sec.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until the financial assurances are approved. Address the following comments for the assurance package:
a) Add activity number "S04-065" to the exhibits.
a) Provide Exhibit "A" (property description) for the AMENDMENT TO TRUST / THIRD PARTY TRUST.
b) Provide Exhibit "A" (property description) for the AGREEMENT TO CONSTRUCT SUBDIVISION IMPROVEMENTS / THIRD PARTY TRUST.
c) Provide Exhibit "B" (the assurable item list) for the AGREEMENT TO CONSTRUCT SUBDIVISION IMPROVEMENTS / THIRD PARTY TRUST.
d) The description of the basin should reflect function of the basin as a "detention / retention basin"; revise the
i) title block,
ii) cover of CC&R's,
iii) cover page of the AGREEMENT TO CONSTRUCT, and
iv) cover page of the AMENDMENT TO TRUST.
e) Assure that the descriptions of the common areas of the Final Plat title block match the CC&R's descriptions of the subdivision common areas and the descriptions in the assurance paperwork. Please be aware that the legal office may reject the assurance paperwork if the verbiage does not match exactly the verbiage on the Final Plat's Title Block.
f) Add "Exhibit "C"" to the top of the first page of the Trust Agreement.
b) There may be opportunity to make a December Mayor and Council date if all items are addressed and other divisions approve; otherwise the "2004" dates on the first sheet would need to be updated.
8) DS Sec.10-02.2.3.1.1.B: A copy of the final draft of the Drainage Report will be needed. Make sure that the administrative address and subdivision case number is added to the cover.

For resubmittal, provide a revised Final Plat, an copy of the original signed CC&R's, boundary closure calculation sheet, copy of current title report, revised assurance exhibits, any other revised assurance documents, and a copy of the Drainage Report. The next submittal should address all the above items. If you have questions or would like to set up a meeting, call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
12/03/2004 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Plans Coordination Office
Development Services Department

PROJECT: S04-65
Enchanted Hills Townhomes, Lots 1-75 and Common Areas "A", "B", and "C"
Final Plat

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Zoning Review Section

TRANSMITTAL: November 3, 2004

DUE DATE: November 6, 2004

COMMENTS:

The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.

1. Draw and label on the location map the COT/Pima County limits. DS 2-03.6.1.D.4

2. Please review the Certification of Survey paragraph and revise to state verbatim as per D.S. 2-03.6.3.A

3. Please place the "APPROVAL" text block over the Recordation text block. DS 2-03.6.3.D

If you have any questions about this transmittal, please call David Rivera at (520) 791-5608.

C\planning\cdrc\finaplat\S04107fpca
12/08/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed