Plan Number: S04-046
Parcel: Unknown

Address:
5113 E LEE ST

Review Status: Completed

Review Details: RESUBMITTAL- OTHER SUBDIVISION REVIEW

Plan Number - S04-046
Review Name: RESUBMITTAL- OTHER SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2004 MARILYN KALTHOFF START PLANS SUBMITTED Completed
08/23/2004 MKALTHO1 ZONING REVIEW Approved CDRC TRANSMITTAL



TO: Plans Coordination Office
Development Services Department







PROJECT: Lee Terrace Lots 1-3
S04-046
Final Plat




FROM: Dan Castro
Senior Planner


FOR: Patricia Gehlen
Principal Planner
Zoning Review Section
Development Services Department

TRANSMITTAL: August 20, 2004




The Zoning Review Section approves the final plat for this subdivision. Should there be any changes requested by other CDRC members, however, the Zoning Review Section approval is void, and we request copies of those changes to insure that those changes do not affect zoning requirements.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.


I:/finalplat2004/S04-046fnplappr.doc
08/23/2004 JIM TATE ENGINEERING REVIEW Denied TO: Craig Gross; CDRC Coordinator DATE: August 23, 2004

SUBJECT: Engineering review of the Lee Terrace Final Plat. The activity number is
S04-046.

SUMMARY: The Final Plat was received by Engineering on August 23, 2004. Engineering has reviewed the received item and does not recommend approval.

RE-SUBMITTAL REQUIRED: FINAL PLAT, SITE PLAN

SUBMITTAL REQUIRED: ASSURANCES, CC&Rs

GENERAL COMMENTS

1. The Drainage Report was reviewed for Final Plat purposes only.

2. Include the Assurance Package or post bond with the next Final Plat submittal

3. Include a copy of the CC&Rs with the next Final Plat submittal. DS 2-03.6.6

4. A Grading Plan and Permit will be required if proposed fill exceeds 50 yd. The Site Plan does not show finish grades. Determination of Grading Permit requirements will be determined when grades are provided. IBC Chapter 36

The next submittal must address the following items:

FINAL PLAT

1. The Assurances must be signed by, "City of Tucson Development Services Department Engineering Administrator". The submitted plat says, "City of Tucson Engineer Development Services Engineering Administrator". PREVIOUS REVIEW COMMENT

2. At least one corner of the subdivision must be tied by course and distance to a section corner, a quarter section corner, or an established City or County survey monument. The plat must include a description of that corner marker. Corner tie recordation information is to be provided on the plat. It is preferred that the tie be to a section monument. The tie must be readily retraceable (bearings and distances). PREVIOUS REVIEW COMMENT

3. Show the distance and bearing between all monuments used. DS 2-03.6.5.C.5 Numerous monuments are shown on the plat that do not tie by bearing and distance to the proposed subdivision. PREVIOUS REVIEW COMMENT

4. All easement lines must have a bearing and distance. DS 2-03.6.5.B
PREVIOUS REVIEW COMMENT

SITE PLAN

1. Per DSMR Engineering approval conditions, "The private street must be constructed in accordance with DS 3-01.3.3.A.4. Vertical curbs are required and the pavement must be concrete." The plan is showing an asphalt street and wedge curb. Change the plan. PREVIOUS REVIEW COMMENT

2. Show sight visibility triangles for the intersection of the private street to Lee Street. DS 2-02.2.1.A.10 PREVIOUS REVIEW COMMENT

3. Show proposed FFE and finish grades. Provide enough information to determine that the drainage will be in accord with the Drainage Report. Provide several finish grades on each lot.
PREVIOUS REVIEW COMMENT

4. Dimension from street center line to existing and proposed curbs and sidewalks. Sidewalks must be 4 ft. wide and 3 ft. from back of curb. DS 3-01 PREVIOUS REVIEW COMMENT

James C. Tate, P.E., CFM
Civil Engineer
09/09/2004 FRODRIG2 ZONING-DECISION LETTER REVIEW Denied
09/09/2004 FRODRIG2 ZONING-RECORDATION REVIEW Denied May not be recorded until record of survey is approved.