Plan Number: S04-028
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - TENTATIVE PLAT REVIEW

Plan Number - S04-028
Review Name: RESUBMITTAL - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/28/2004 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plans to designate decomposed granite in Common Area "B" and the adjacent right of way area along Drexel Road. LUC 3.7.2.7, LUC 3.7.2.4.A.3
11/04/2004 FRODRIG2 PIMA COUNTY WASTEWATER Approved November 3, 2004

TO: William Daniels, E.I.T.
Gregor & Grenier Engineering, Inc.

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Acacia Lane, Lots 1-8 and Common Areas A & B
Tentative Plat – 2nd Submittal
S04-028


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project is hereby approved as submitted.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
11/12/2004 DAN CASTRO ZONING REVIEW Denied COMMENTS
CODE SECTION/ DEVELOPMENT STANDARD

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is March 10, 2005.

2. All subdivision improvements and lots must be located outside the future right-of-way. Common Areas A and B and lot 8 are located in the future right-of-way area. In addition, the future curb is incorrectly located ten (10) feet in front of the future right-of-way line. The correct location shall be eleven (11) feet in front of the future right-of-way line.
D.S. 2-03.2.1.C

3. List the following information as a general note: DSMR case number, date of approval, modifications granted, and conditions imposed.
D.S. 2-03.2.1.D.2

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
11/12/2004 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this TP:

1. The symbol used for the new no parking signs is incorrect. The symbol as depicted is for existing signs. Use the correct symbol for new signs IAW SDPI SD 100.

2. The driveway spacing between lots 6/7 and 7/8 appear to not meet the spacing requirements of Chapter 25 of Tucson City Code. Minimum spacing is 12'.

3. Add a general note to read “All non-signalized intersection street manes must have E-W block number addresses for E-W roadways and N-S block number addresses for N-S roadways.”

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
11/16/2004 LOREN MAKUS ENGINEERING REVIEW Denied DATE: November 16, 2004
TO: Craig Gross; CDRC Coordinator
SUBJECT: Acacia Lane Tentative Plat Engineering Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: S04-028

SUMMARY: The Tentative Plat, Landscape Plan, and Hydrology Report were reviewed by Engineering on November 16, 2004. Engineering does not recommend approval at this time. The Drainage Report was reviewed for Tentative Plat purposes only.


TENTATIVE PLAT COMMENTS:
1) Revise the future right-of-way to account for intesection widening at Sixth Avenue and Drexel Road. The width of the Drexel Road right of way from the centerline of Sixth Avenue and continuing 300 feet along Drexel should be 130 feet. Starting at 300 feet from the centerline the edge of the right-of-way should taper to the ultimate width of 100 feet.
2) Revise the Tentative Plat to show dedication of the future right-of-way. Show that all required amenities such as the drainage basin, access road, and lot lines will be located outside of the future right-of-way area.
3) Revise the Landscape Plan and Drainage Report as necessary to agree with the revise Tentative Plat.

Submit the revised Landscape Plans, and revised Tentative Plat. The next submittal should address all the above items. To set up a meeting, call me at 791-5550, extension 1161.

Loren Makus, EIT
Senior Engineering Associate
Engineering Section
Development Services
11/18/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed