Plan Number: S04-024
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S04-024
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/01/2004 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: DESERT POINT ESTATES
Lots 1-76
S04-024

Tucson Electric Power Company (TEP) has received the final plat for review
dated September 28, 2004. This Company is unable to approve the plat at
this time.

An electrical design to determine our easement requirements will be provided
on the Approved Tentative Plat with working days upon receipt of the plat.
At the customer's request, a design can be provided prior to the Approved
Tentative Plat, however, once a design is provided, any design changes may
be billable to the developer.

Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8745
Cell Phone: (520) 904-2668
Fax: (520) 917-8700
10/01/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-024 DESERT POINT ESTATES/FINAL PLAT
DATE: 9/30/04



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through the Pima
County Subdivision Coordinator. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
10/21/2004 FRODRIG2 PIMA COUNTY WASTEWATER Denied October 21, 2004

TO: Wocky Redsar
Castro Engineering

THRU: Craig Gross
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Desert Point Estates, Lots 1-76 and Common Areas A-C
Final Plat – 1st Submittal
S04-024


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 1. Revise the third paragraph of the Dedication to read

WE HEREBY GRANT TO THE PUBLIC AND ALL UTILITY COMPANIES ALL PUBLIC EASEMENTS AS SHOWN HEREON FOR THE PURPOSES OF ACCESS, INSTALLATION AND MAINTENANCE OF PUBLIC SEWERS AND UTILITIES AND OTHER USES AS DESIGNATED BY THIS PLAT.

SHEET 2. Delete key note 5 throughout the layout.

A public Sewer Service Agreement for the proposed number of residential lots has been sent to your office. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve the Mylars of the final plat.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
10/26/2004 ELIZABETH EBERBACH ENGINEERING REVIEW Denied SUBJECT: Desert Point Estates Final Plat Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S04-024
LOCATION: T15S R14E Section 10

SUMMARY: The Final Plat marked "preliminary", and the draft of the CC&R's were received by Engineering on September 29, 2004. Engineering has reviewed the received items. Engineering Division does not recommend approval of the Final Plat at this time. Please address the following comments.

FINAL PLAT COMMENTS:
1) City of Tucson Development Standards (DS) Section No.2-03.6.6: The draft of the Covenants, Conditions, and Restrictions appear acceptable; please submit original signed copy.
2) DS Sec.2-03.6.5.C.3: Provide boundary closure calculation sheets for both portions of the project.
3) DS Sec.2-03.6.5.C.1.a: For the basis of bearing, provide reference to a record of survey or a recorded plat.
4) DS Sec.2-03.6.5.A: At least one corner of the subdivision needs to be tied by course and distance to one of the quarter / section corners or an established City or County survey monument.
5) DS Sec.2-03.9.3.B: Remove "preliminary…" notation from sheets; the plat will contain the signature and seal of the land surveyor.
6) DS Sec.2-03.7.1.B: If engineering information is provided on the final plat, the seal and signature of the responsible engineer is also required.
a) DS Sec.2-03.6.4.E: Show required drainage setbacks from ponding limits in the basins to structures.
b) DS Sec.2-03.6.4.F: Show the limits of the 100-year floodprone area for Earp Wash, if applicable, in a surveyable and readily retraceable manner with frequent ties to intersecting lot lines for all flows of 100 cfs or more.
7) DS Sec.2-03.6.4.G: Provide dimensions for SVT's on plan view for clarification of location of sight visibility triangles.
8) DS Sec.2-03.6.4.H: Show no-vehicular access easements where applicable, ie. on lots 36 - 40 on sheet 2 and lots 38 - 48 on sheet 3.
9) DS Sec.2-03.9.3.J: Since this project is not served by Tucson Water but by Ray Water Company, provide a copy of certification letter from the Arizona Department of Water Resources since the project is not served by the City of Tucson Water Department. Add a general note to the Final Plat regarding certification on assured water supply. Provide on the Final Plat appropriate signatures from Ray Water Co. indicating the same.
10) DS Sec.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until the financial assurances are approved. Provide the following portions of the assurance package:
a) an original copy of the Agreement to Construct
b) an original copy of the Amendment to Trust
c) an copy of the original Trust Agreement
d) all associated assurance exhibits
e) a copy of the current Title Report
f) copy of a sample warranty deed
11) For this and future projects, please provide three 8½" by 11" location map sheets for assurance submittals that go to Mayor & Council. Typically, these are similar to an enlarged location map on Final Plats.
12) DS Sec.2.4.K & IBC Chap. 36 Sec.13.1: Please provide status of differential grading.

For resubmittal, address the above comments and provide the revised Final Plat, the original CC&R's, closure calculations, and assurance package, with response letter. If you have any further questions, or would like to set up a meeting, you may call me at 791-5550 extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
10/27/2004 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

RICK LYONS
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: October 22, 2004


RE: Assessor’s Review and Comments Regarding Final Plat
S04-024 Desert Point Estates T151410 (140-32)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.








Susan King
10/28/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
10/28/2004 CRAIG GROSS COT NON-DSD REAL ESTATE Approved no comments.
10/28/2004 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
Desert Point Estates
S04-024
Final Plat

TRANSMITTAL: October 28, 2004
DUE DATE: October 28, 2004


1. Remove the "Preliminary" stamps from the plat.
DS 2-03.11.8.B.1

2. Portions of page 19 of the draft Covenants Conditions & Restrictions did not copy correctly and the page is illegible. Please provide a clean copy of the CC&r's. DS 2-03.6.6

3. Because the project is served by Ray Water Company rather than City of Tucson Water Dept, provide a copy of certification letter from the Arizona Department of Water Resources . Add a general note to the Final Plat stating certification of assured water supply. Provide on the Final Plat appropriate signatures from Ray Water Co. indicating the same. DS 2-03.11.12.A

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
10/28/2004 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
Desert Point Estates
S04-024
Final Plat

TRANSMITTAL: October 28, 2004
DUE DATE: October 28, 2004


1. Remove the "Preliminary" stamps from the plat.
DS 2-03.11.8.B.1

2. Portions of page 19 of the draft Covenants Conditions & Restrictions did not copy correctly and the page is illegible. Please provide a clean copy of the CC&r's. DS 2-03.6.6

3. Because the project is served by Ray Water Company rather than City of Tucson Water Dept, provide a copy of certification letter from the Arizona Department of Water Resources . Add a general note to the Final Plat stating certification of assured water supply. Provide on the Final Plat appropriate signatures from Ray Water Co. indicating the same. DS 2-03.11.12.A

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.