Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: S03-030
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - TENTATIVE PLAT REVIEW

Plan Number - S03-030
Review Name: RESUBMITTAL - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2004 MARILYN KALTHOFF START PLANS SUBMITTED Completed
03/23/2004 MARILYN KALTHOFF PIMA COUNTY WASTEWATER Approv-Cond CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380


April 16, 2004

TO: Warren Thompson, Stantec Consulting

THRU:


FROM: ____________________________________
representing the Pima County
Departments of Wastewater Management and Environmental Quality

SUBJECT: Sycamore Park, Blocks 1-4 (aka Kolb Road and Voyager, Blooks 1-3)
- Submittal
S03-030


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use:


If WPI Kolb and I-10, L.L.C. builds the 9750’ of qualifying off-site sewer line shown on Sewer Plan No. G-003-095, 390 lots within the area shown on this block plat will qualify for the Participating sewer connection fee rate, and the remainder of the lots built within the area shown on this block plat will qualify for the Non-Participating sewer connection fee rate pursuant to Pima County Code Title 13.20.040.B.

The Participating sewer connection rate will be granted to the lots when we receive the subdivision plats for each block. This will cause the first blocks to be developed to have the most lots granted the Participating sewer connection rate.

We will track the number of lots granted the Participating rate as each block is developed.

If this manner of assigning and tracking the lots given the Participating rate is not acceptable to the owner/developer, please have him or her meet with me to find a mutually acceptable alternative.

Sheet 5: The 290’ of 12” sewer line that runs from SMH #27 of G-2003-095 to Voyager Road was shown as proposed under sewer plan G-2003-095, but this sewer line was not shown on the set of plans for G-2003-095 that was provided to this office with the revised tentative plat.

Show it as part of G-2003-095, on the next submittal of the sewer improvement plans for G-2003-095.

Sheet 11: Sewer lines this large may turn no more than 60 degrees at any one manhole. Change the manner in which the 15” sewer line turns south to exit from the right of way.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you wish to discuss the above comments, please contact me at the phone number provided on the first sheet.
03/24/2004 JIM EGAN COT NON-DSD FIRE Approved The Tentative Plat is approved March 24, 2004.
03/25/2004 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: KOLB & VOYAGER BLOCK PLAT
(SYCAMORE PARK)
Block 1-4
S03-030

Tucson Electric Power Company (TEP) has no objection to the resubmittal of the City of Tucson tentative block plat, dated March 18, 2004.

The preliminary point where TEP will serve this project is from the existing facilities along Voyager Road and Pantano Road. As you are aware, there are existing electrical facilities within the boundaries of this subdivision. All relocation costs will be billable to the developer.



Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8479
Pager: (520) 218-6565
Fax: (520) 917-8400
03/25/2004 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S03-030 KOLB RD & VOYAGER/REVISED TENTATIVE PLAT
DATE: March 24, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct legal description on all Title Blocks per letter dated 12-23-03. There is a portion of this project in the southern half. Not all of this project is in the northern half.
Label “Spine Road” and “Spine Roadway” in a way that it doesn’t look like the name of the street.
Label approved interior street names on Final Plat.











jg
04/02/2004 LAITH ALSHAMI ENGINEERING REVIEW Denied RECEIVED: Tentative Plat (Block Plat), Landscape Plan and Drainage Report on March 23, 2004

The subject submittal has been reviewed. We offer the following comments:

Drainage Report:

1. Verify that the increase of the water surface elevation at cross sections 115 and 116 will not cause an adverse impact on the upstream properties (provide the analysis and the 10-year and 100-year floodplain delineation.
2. It is not clear why 15.5 cfs was used to size the curb opening at CP #11. Figure 4 shows Q100 = 23.6 cfs at CP #11. Additionally, Your response #18 states that CP #14 has 4.4 cfs. The COT peak estimator sheets and Figure #4 do not show CP #14. Clarify.
3. It is still not clear where the scupper sizing calculations are, including for concentration points #4C, #5, #15B.

4. The report still uses Q100 of 107.3 cfs to rate the swale between Kolb Road and Voyager RV Park. Revise as necessary.
5. Provide the design calculations for erosion control measures at the outlets of all proposed scuppers and culverts.
6. The proposed streets hydraulic rating shows incorrect Q100's at concentration points 6A, 15B, 15C and 15D. Revise as necessary.
7. The hydraulic rating for the swale at CP #3 uses Q100 = 32 cfs. COT flood peak estimator shows Q100 at CP #3 = 19.1 cfs. Explain the discrepancy or revise.

Tentative Plat:

1. Section 3/3 shows the "to be dedicated by the final plat" right of way as existing and recorded in DKT 11281, page 478. Clarify the discrepancy.
2. The Tentative Plat still does not appear to demonstrate compliance with Rezoning Conditions #14 and #33.
3. Cross section 5/3 does still shows wrong dimensions on the left side. Revise.
4. The plat must show the new Kolb Road Pavement between Spine Road and the south property line as required by Rezoning Condition #7
5. Cross-section 2/3 should show a median curb as required by Rezoning Condition #11. If Transportation Department granted a permission not to build the median curb, provide a written verification. Verify if the Developer will seek revising or eliminating Rezoning Condition #11.
6. It appears that the slope shown on cross-section 1/5 still does not match the information in the Drainage Report. Revise.
7. All proposed easements, including all drainage easements, are to be dimensioned and labeled as required by D.S. 2-03.2.4.J. Additionally, The sewer easement does not appear to have been included on sheet 10.
8. The response concerning the length of the "culvert at CP #8" implies that there is a proposed culvert at CP #8, but the Tentative Plat does not show the culvert, which is confusing. Clarify.
9. It appears that a lot of the culvert and scupper information (length and slope, etc) on the Tentative Plat does not match the information in the drainage report, which makes the review process tedious and lengthy. Ensure that the information in the drainage report and Tentative Plat match.
10. It appears that Spine Road still encroaches on the ERZ floodplain of North Fork Airport Wash Tributary at the intersection of Kolb Road and Spine Road. Eliminate the proposed encroachment or provide an acceptable justification in accordance with the ERZ requirements.
11. Provide written verifications for drainage solutions occurring outside the boundaries of the plat as required by D.S. 2-03.2.4.L.5.
12. Revise the Tentative Plat in accordance with the drainage report revisions.


Please be advised that due to the size and complexity of this project, additional comments may be offered on the next submittal.

Prepare a detailed response that explains the revisions that were made and references the exact location (by page or sheet number) in the drainage report and on the Tentative Plat where the revisions were made.


RESUBMITTAL REQUIRED: Revised Tentative Plat and Drainage Report
04/06/2004 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Submit landscape plans for the initial phase of development. Native plant mitigation, path locations, revegetation for basins and compliance with dust control provisions is to be included on the landscape plans.
DS 2-03.3.0

2) Show the natural landscape and public access easement required as a condition of rezoning. C9-03-01 #33

3) Retention basins are to landscaped per DS 10-01.1. Include planting plans for the proposed basins.

4) Per condition of rezoning case C9-03-01 "Existing mature vegetation along the perimeter of basins shall be preserved".
Revise the native plant preservation plan to comply, show all preserved plants on the landscape plans.

5) The location of the spine road cannot be approved until it is determined if the required path can be located within the 100 year floodplain of the Airport Wash Tributary without a variance to the ERZ regulations. C9-03-01

6) The proposed project is subject to review for overlay zone requirements, the Environmental Resource Zone (ERZ) applies, a separate application is required for that special review. ERZ review is submitted to the Zoning Review Section at DSD. These application packages may
be submitted at the same time as the tentative plat application is submitted to DSD. Refer to DS 2-13.0 for submittal requirements.
04/07/2004 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied DATE: April 07, 2004

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

SUBJECT: CDRC Transmittal, Project S03-030 Kolb Rd and Voyager: TP

CC: Craig Gross, Development Services


Staff has reviewed the development plan and has the following comments:
On the Block Plat, show the alignment of the public path along Airport Wash. A note maybe be included indicating the path alignment is subject to adjustment on further platting.

On Block Plat show a cross-section detailing path construction including the following specification: Decomposed granite trail: two(2) inch thickness, stabilized decomposed granite(1/4" minus) compacted to 95% over native subgrade compacted to 95%.




Please feel free to call me at 791-4873 x 215 if you have any questions.
04/07/2004 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved URBAN PLANNING AND DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S03-030 Kolb Road & Voyager 04/07/04

(X) Tentative Plat
() Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-03-01

NEIGHBORHOOD PLAN: Rincon Southeast Subregional Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 04/06/04

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 12/15/03








REVIEWER: msp 791-4505 DATE: 04/06/04
04/07/2004 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this T.P.:

1. Show the no parking signs in Planimetric view on the spine road on sheets 6, 8, 11, 12 as they are depicted in sections 4/3, 12/3.

2. Median is misspelled in section 2/6.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
04/09/2004 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Plans Coordination Office
Development Services Department

PROJECT: S03-030
Sycamore Park Block 1 - 4
Tentative Plat

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Zoning Review Section

TRANSMITTAL: April 9, 2004

DUE DATE: April 7, 2004

COMMENTS:

The Zoning Review Section approves the tentative plat for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements.

1. A portion of the road construction or road embankment still appears to be within the floodplain limits. See sheet 6, Kolb Road and the Spine Road T-intersection. See additional comments by the Engineering Review Section.

If you have any questions about this transmittal, please call David Rivera at (520) 791-5608.

C:\planning\cdrc\tentativeplat\S03030tpca.doc