Plan Number: S03-017
Parcel: Unknown

Address:
107 W PASTIME RD

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S03-017
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/14/2003 JIM EGAN COT NON-DSD FIRE Denied 1. Provide a General Note on the plan stating: "No on-street parking is permitted. Approved Fire Lane signs shall be provided on both sides of the private drive in accordance with Section 503 of the Tucson Fire Code."
2. Indicate Fire Lane signs located on both sides of drive on Section A/1.
07/15/2003 JIM TATE ENGINEERING REVIEW Denied TO: Craig Gross; CDRC Coordinator
DATE: July 15, 2003

SUBJECT: Engineering review of the Earlybird Subdivision Tentative Plat. The activity number is S03-017.

SUMMARY: The Tentative Plat and Drainage Report were received by Engineering on July 14, 2003. Engineering has reviewed the received items and does not recommend approval of the Tentative Plat or the Drainage Report.

RESUBMITTAL REQUIRED: TP, DR

GENERAL COMMENTS

1. The Drainage Report was reviewed for Tentative Plat purposes only.

2. Please include the Assurance Package with the Final Plat submittal. This package must include the original Third Party Trust, the original Amendment to Trust, a copy of the Trust Agreement, a copy of the Deed, and a Title Report.

3. Include a copy of the CC&Rs with the Final Plat submittal. The specific maintenance notes specified in the Standards Manual for Drainage Design and Floodplain Management, SMDDFM, 14.3.2 must be included on the Final Plat or in the CC&Rs. The term "owner" in the maintenance notes is to be replaced with "Homeowners Association".

4. Please provide a copy of the boundary closure calculations with the Final Plat submittal.

5. A Grading Plan and Permit will be required. Proposed grading in excess of 5,000 yards is designated "engineered grading" and a soils engineering report is required with the Grading Plan submittal. IBC Chapter 36, Section 9. The Soils Report must also address the requirements detailed in the Standards Manual for Drainage Design and Floodplain Management, SMDDFM, 14.2.6.

6. Proposed fills in excess of two feet above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property require the procedure outlined in IBC Chapter 36 Section13.1. This process must be complete prior to Grading Plan approval.

7. Proposed developments disturbing areas exceeding 1 acre are subject to NPDES requirements. Contact Patricia Gilbert, 791-5550 for submittal requirements. The NPDES submittal must accompany the Grading Plan submittal.

The next submittal must address the following items:

TENTATIVE PLAT

1. Show the contour interval by the north arrow. DS 2-03.2.1.4

2. Place the subdivision case number (S03-017) in the lower right corner of the plat next to the title block. DS 2-03.2.2.B.1

3. Provide a note stating, "Total miles of new private streets are ______". DS 2-03.2.2.D.1.b

4. Provide basis of elevation based on City of Tucson datum (indicate City of Tucson field book number and page). DS 2-03.2.3.F

5. It is not clear on the plan if there is existing or proposed curb on Pastime Road. Label and dimension. DS 2-03.2.3.D

6. For the retention basins list top elevation, bottom elevation, 100-yr. peak WSEL, and weir invert elevation. Show 100-yr peak ponding limits. DS 2-03.2.4.L

7. Provide proposed ground elevation at different points on each lot for reference to future grading and site drainage. DS 2-03.2.4.L.4

8. The proposed basin slope is 1.5:1 with no bank protection. Provide the soils report stating that this steep slope does not require protection.

9. The sight visibility triangle near side dimension is incorrect. A local to local near side dimension should be 180 ft. DS 3-01.5.3

10. The Drainage Report states that two type 2 sidewalk scuppers are required at the basin outlet. The plan only shows one. Correct.

11. Show and label the basin weir location and length (30 in.). Specific details of drainage structures will be required on the Grading Plan.

DRAINAGE REPORT

1. Provide a detailed Detention/Retention Basin Maintenance Checklist and Schedule. Standards Manual for Drainage Design and Floodplain Management, 2.3.1.6.C.1

James C. Tate, P.E.
Civil Engineer
07/18/2003 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S03-017 EARLYBIRD SUBDIVISION/TENTATVIE PLAT
DATE: July 15, 2003



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct Title Block to read: A Re-Subdivision of a portion of 4N of Pastime Acres…

Correct Dkts, Pg 37 to Bk 5, Pg 37.

Label approved interior street name on Final Plat.

What address is being used by the existing homes? Note: Any existing addresses will be changed and will be addressed from the interior roadway when the Final Plat has been approved and recorded.
07/18/2003 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S03-017
LANDMARK ENGINEERING, INC.
EARLYBIRD SUBDIVISION
07/22/2003 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 3950 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


Telephone: 520-884-3879
Fax: 520-770-2002
WR#109817 July 22, 2003



Mr. Henry Jacobson
Landmark Engineering, Inc.
300 N. Main Avenue, Suite #104
Tucson, Arizona 85701

Dear Mr. Jacobson:

SUBJECT: Earlybird Subdivision
Lots 1-6
S03-017

Tucson Electric Power Company (TEP) has no objection to the Tentative Plat stamped July 9, 2003.

This Company will probably provide this project with electrical service from the two poles, numbers 133 and 135, as shown on the enclosed sketch. As you are aware, there are existing electrical facilities within the boundaries of this subdivision. All relocation costs will be billable to the developer.

TEP will provide an electrical design on the Approved Tentative Plat within fifteen (15) working days upon receipt of said approved plat. Please make note that this Company designs their facilities within the streets on the north and east sides, which would be the east side in this case. A complete set of building plans, including water, electrical, paving, and driveway placements, should be provide to this Company prior to the start of the design.

Should you have any questions, please contact me at (520) 884-3879.

Sincerely,



S. Glynda Mastrangelo
Right-of-Way Agent
Land Management

sgm
Enclosure
cc: Craig Gross, City of Tucson
Daniel Waters
07/22/2003 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Case Number: S03-017
Project Name: Earlybird Subdivision
Estimated Traffic Generation: 38 trips
08/07/2003 DAN CASTRO ZONING REVIEW Denied COMMENTS
CODE SECTION/ DEVELOPMENT STANDARD

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is July 10, 2004.

2. Reference recorded subdivision plats by book and page numbers.
D.S. 2-03.2.1.D.2

3. This project has been assigned subdivision case number S03-017. Please note the subdivision case number in the lower right corner of each sheet on all plans.
D.S. 2-03.2.2.B.1

4. Under general note three (3), please note the applicable land use classification as it is listed under LUC Sec. 2.3.5.2.A. (i.e. Family Dwelling, "I", subject to: Sec. 3.5.7.1.F) If the lots are proposed for manufactured housing, please note the manufactured housing requirements as they are listed under L.U.C. 3.5.7.1.F on the tentative plat.
D.S. 2-03.2.2.B.5

5. Provide lot coverage calculations for lots 5 and 6. Lot coverage is comprised of total building area plus vehicular use area divided by the lot area.

6. a) Per D.S. 3-01.2, the proposed private drive must be designed with parking on both sides, unless parking is provided in common areas distributed throughout the subdivision, at a ratio of one (1) parking space per dwelling within the subdivision.
b) Per D.S. 3-01.6.2.C.2, vehicle parking is not allowed in the turnaround area. In addition, vertical curbing is required in the turnaround area, depressed curbs are not allowed. Access to the rear lots must be redesigned.
D.S. 2-03.2.4.G

7. A five (5) foot sidewalk is required on both sides of the street. Each lot must have pedestrian access to the Pastime Road right-of-way. Refer to Engineering and Traffic Engineering Sections for additional street improvement requirements.
D.S. 2-03.2.4.F

8. Per D.S. 3-05.2.4.A.5, tandem parking in the driveways does not count toward visitor parking.
D.S. 2-03.2.4.G

9. Note the exterior building wall heights for the existing manufactured homes and dimension the building setbacks from the face of the exterior building walls to the new property lines. Building setback requirements to the new property lines may not be verified for compliance until this information has been provided.
D.S. 2-03.2.4.M

10. If applicable, all existing and proposed easements on this site must be shown on the plat, including the type, width, recordation information, and whether they will be private or public. If an easement is to be recorded by final plat, please so state.
D.S. 2-03.2.4.J

11. The Final Plat may not be approved until the CC&R's are reviewed and approved by the Zoning Review Section. The CC&R's must meet criteria listed in L.U.C. 3.6.1.5.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
08/07/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S03-017 Earlybird Subdivision 08/05/03

() Tentative Plat
() Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: North Stone

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: August 7, 2003

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: JBeall 791-4505 DATE: 7/28/03
08/07/2003 JOE LINVILLE LANDSCAPE REVIEW Approved NPPO exception
08/08/2003 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

RICK LYONS
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: August 7, 2003


RE: Assessor’s Review and Comments Regarding Tentative Plat
S03-017 Earlybird Subdivision T131325 (106-02)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal. Please make the following additions/corrections in the final plat.
Add the section, township and range to the title block.
Add the number of miles of new road, public or private, to the general notes, even if that number is 0.
Add a section tie.
Add adjacent subdivisions.
Remove the hatching and add the dimensions and bearings for Common Area “A”; add the square footage for the common areas.
Add the road information for Pastime Road.
If there are any questions, please contact Susan King at 740-4391.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.





Susan C. King
08/11/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved no comments
08/11/2003 TIM ROWE PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
September 22, 2003

TO: Henry Jacobson, Landmark Engineering

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Earlybird Subdivision, Lots 1-5 and Common Areas A & B
Tentative Plat - 1st Submittal
S03-017



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. Mr. Robert Decker of PCWWM Planning Services may be contacted regarding this matter at 520-740-6625.

2. Lots 1-4 are located wholly or partially within an old sewer improvement district, and these lots would qualify for Participating sewer connection fee rates. Lots 5 & 6 are located wholly outside the old sewer improvement district, and these lots would qualify for Non-Participating sewer connection fee rates.

3. Add the subdivision plat case number, S03-017, to the title block of each sheet. This number should be shown larger or bolder than the cross reference numbers.

4. Show the plan number, I-768, for the existing 8" sewer line in Pastime Road.

5. The section of new private sewer line running under the proposed retention basin is unacceptable. Arizona Adminstrative Code (AAC) R18-9-301.B requires the private sewers to be designed to minimize inflow and infiltration. Extend the private sewers out to the public sewer line in Pastime Road under the private drive.

6. Subject to the above, the tentative plat is hereby approved. The required corrections may be shown on the Mylars.

If you wish to discuss the above comments, please contact me at 740-6563.




Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr

Copy: Project
08/11/2003 CRAIG GROSS COT NON-DSD REAL ESTATE Approved no objections
08/11/2003 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this T.P.

1. Label dimensions of the SVT's (ie 20x110)
2. Show no parking signs in the street section.
3. Show locations of no parking signs along the drive and in the hammerhead.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)