Plan Number: S03-007
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - TENTATIVE PLAT REVIEW

Plan Number - S03-007
Review Name: RESUBMITTAL - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2003 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/30/2003 FRODRIG2 PIMA COUNTY WASTEWATER Approved PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
July 30, 2003

TO: Steve Magelli, OPW Engineering, LLC

THRU: Craig Gross, City of Tucson Development Services

FROM: Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Division (Wastewater)
SUBJECT: Silverbell Trails, Lots 1-42 and Common Areas A-D
Tentative Plat - 2nd Submittal
S03-007



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. Pima County Wastewater Management Department hereby approves the above-referenced Tentative Plat as submitted.

If you wish to discuss the above comments, please contact me at 740-6586.




Subhash Raval, P.E., Division Manager
Pima County Development Review & Technical Services Division (Wastewater)


SR/SR/dk
Copy: Project
08/07/2003 ELIZABETH EBERBACH ENGINEERING REVIEW Denied SUBJECT: Silverbell Trails Tentative Plat 3rd Submittal Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S03-007

SUMMARY: The revised Tentative Plat, revised Drainage Report, Landscape Plans, exhibit to title report, and response letters were received by Engineering on July 30, 2003. Development Services Department Engineering Division has done a review of the received items and does not recommend approval at this time. The Drainage Report was reviewed for Tentative Plat purposes only.

DRAINAGE REPORT COMMENT:
1) DS Sec.10-02.10.9.2: Since there is potential for outlet control due to presence of junction box at proposed grate and the shallow grade of proposed 200 foot culvert, provide hydraulic grade line study on the system from outlet at east side of Silverbell Road to basin weir.

TENTATIVE PLAT COMMENTS:
2) A proposed grated inlet is shown as being within the public right-of-way. After discussion with Steve Tineo at Permits and Codes, this location is not acceptable due to maintenance considerations and should be placed outside of the right-of-way. It was discussed at the meeting on 14JUL03, that a grated inlet was to be considered and that the placement of the inlet would be acceptable within the 30-foot buffer easement if the inlet was natural colored. Show relocation of grated inlet on plan view. Also, provide detail on Landscape Plans, showing location, dimensions and color.
3) DS Sec.2-03.2.4.L.4: Provide more clarification of Typical Lot Drainage Flow Details on sheet 3. Specifically, clarify typical elevation at grade breaks shown on these details. Also further clarification regarding size and spacing for wall openings may be provided at grading plan submittal review.
4) DS Sec.2-03.2.4.K: In order for Tentative Plat approval, the revised geotechnical report must be submitted and accepted. As stated from previous comments, clarify or provide geotechnical engineering information specific to the project site that was not be included in the initial geotechnical report submittal:
a) Provide discussion regarding existing soils conditions of the site and the viability of project. As stated in response letter and as seen from site visit, a number of utility services appear to be on site, yet geotechnical report states that none were seen. Explain discrepancy in revised geotechnical report;
b) Specifically, identify any potentially hazardous geotechnical areas including soils conditions at locations of any existing on-site private sewer disposal systems, viability of project with any recommendations for removal of any contaminated soils. As stated previously, it appears from a field investigation that there is evidence of well and leach fields on site; with one leach field at the location of the proposed basin. In summary, provide geotechnical addenda, or revised geotechnical report, confirming feasibility of project with regards to removal of any contaminated soils near proposed basin location. Provide discussion regarding specific geotechnical recommendations for feasibility of disposal of any contaminated soils.
c) Provide description of soil constraints for structural design of foundations and walls, including minimum distance from foundations to drainage swales and minimum slope grades adjacent to building pads or foundations;

5) Clarify discrepancy in detail on sheet 3 in which the culvert is labeled as "2-24"CMP" and the plan view on sheet 2 shows "2-24"RCP". RCP is required in public right-of-way.

The next submittal should address all the above items. Submit revised Tentative Plat, revised geotechnical report with any addenda, and revised Drainage Report. You may schedule a meeting with me to go over these comments or call me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services Department
08/08/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved APPROVED - SAME AS PREVIOUS COMMENTS
08/13/2003 DAN CASTRO ZONING REVIEW Approved
08/13/2003 JOE LINVILLE LANDSCAPE REVIEW Approved Approved. No additional comments

Joe Linville
Landscaping REview