Plan Number: S03-001
Parcel: Unknown

Address:
8200 E STELLA RD

Review Status: Completed

Review Details: RESUBMITTAL - TENTATIVE PLAT REVIEW

Plan Number - S03-001
Review Name: RESUBMITTAL - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/25/2004 LAITH ALSHAMI ENGINEERING REVIEW Denied SUBJECT: Lakeside Ridge
S03-001, T14S, R15E, SECTION 28

RECEIVED: Tentative Plat, Landscape Plan and Drainage Report on May 19, 2004

The subject project has been reviewed. We offer the following comments:

Drainage Statement:

The Drainage Statement is acceptable for Tentative Plat purposes only. Additional information may be required with the Grading Plan.

Tentative Plat:

The Tentative Plat shall be recommended for approval pertaining to Engineering and Floodplain subject to the following:

1. Show all the parcel boundary information (D.S. 2-03.2.3.B).
2. It appears that some set survey monuments do not fall on the property lines especially on the Eastern Property Line. Clarify and revise as needed (D.S. 2-03.2.3.A).
3. Add a general note, which states that the depicted FEMA and 100-year floodplain, which impact the areas where lots are proposed, shall be removed (based on the approved CLOMR and LOMR, which will be submitted once the project is completed) or contained within the proposed drainage facilities once they are constructed and completed. Additionally, add a note that requires the Developer to acquire a Floodplain Use Permit, with the Grading Plan, for any proposed work in the said 100-year floodplain, which would result in the floodplain containment. The purpose of this comment is clarify on the plat that floodplain use permits will not be required for the impacted individual lots when they come in for permitting.

Landscape Plan:

The Landscape Plan is acceptable pertaining to Engineering and Floodplain.


RESUBMITTAL REQUIRED: Revised Tentative Plat
06/04/2004 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this T.P.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov