Plan Number: S03-001
Parcel: Unknown

Address:
8200 E STELLA RD

Review Status: Completed

Review Details: CDRC - TENTATIVE PLAT REVIEW

Plan Number - S03-001
Review Name: CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2003 FERNE RODRIGUEZ START INITIALIZE THE WORKFLOW Completed
01/10/2003 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
February 26, 2003

TO: John Evans,, JAE Consulting Engineering

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Lakeside Ridge, Lots 1-68
Tentative Plat - 1st Submittal
S03-001



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. There is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

2. Based on the preliminary sewer layout as shown on the referenced tentative plat, this project would qualify for Non-Participating sewer connection fee rates. However, a final determination of this status cannot be made until approval of the sewer construction plans and/or preparation of the sewer service agreement.

3. The tentative plat is hereby approved, subject to the following:

4. All Sheets: Add the subdivision plat case number, S03-001, to the title block of each sheet. This number should be shown larger or bolder than the cross reference numbers.

5. Sheets 3 & 4: Label the existing sewer line in Lakeside Ridge Loop with its size (8") and plan number (I-65-17)

6. Sheets 2 & 4: Label the existing public sewer easement for existing sewer line I-65-17 with it’s width, type (public or private), additional uses, and recording information.

7. Sheets 3 & 5: What appear to be existing private cleanouts have been shown on Lots 64, 62, 60, 58, 56, 54, 53, & 52. If that’s what these are, and they are to be abandoned, they should be deleted.

8. Sheet 5: Label the existing sewer line in Sarnoff Drive with its size (15") and plan number (G-73-17).

9. The required revisions may be shown on the Mylars of the tentative plat that will be submitted to the CDRC for signature. A resubmittal of bluelines is not necessary.

If you wish to discuss the above comments, please contact me at 740-6563.

Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr
Copy: Project
01/14/2003 JIM EGAN COT NON-DSD FIRE Denied Provide a note on the plan: "Additional fire hydrants shall be provided by the developer in accordance with Tucson Fire Code and COT Water Standards.
01/30/2003 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S03-001
JOHN EVANS & ASSOCIATES
LAKESIDE RIDGE
02/06/2003 KAY MARKS PIMA COUNTY ADDRESSING Denied PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
201 N. Stone Ave, 1st Floor
Tucson, Arizona 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO : CITY PLANNING
FROM : KAY MARKS, ADDRESSING OFFICIAL
SUBJECT : S03-001 LAKESIDE RIDGE/TENTATIVE PLAT
DATE : February 3, 2003


***********************************************************************************************************

The above referenced project has been reviewed by this Division for all matters pertaining to street naming/ addressing, and the following matters must be resolved prior to our approval:

Change “Sarnoff Road” to ‘Sarnoff Drive,” “Sarnoff Drive” to “Camino Seco” and “17-4” to “54-19” on Location Map.

Change “Lakeside No. 1 Bk 23, Pg 60” to “Bk 16, Pg 66” on pgs. 2 and 3.

Change “Sarnoff Road” to “Sarnoff Drive” on pg. 3.
02/06/2003 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information for Subdivision and Development Pima Association of Governments
Review Requests
Transportation Planning Division

CASE #: S03-001 177 N. Church Avenue, Suite 405

NAME: Lakeside Ridge Tucson, AZ 85701
Phone: (520) 792-1093
DATE: 2/3/2003
STREET NUMBER 1
Nearest Existing or Planned Major Street Pantano Rd (Golf Links to Escalante)
Is improvement planned as part of the 5-Year Transportation
Improvement Program? No
Year:
Planned Action:
Existing Daily Volume – Based on Average Daily Traffic 8,900
Existing Daily Capacity- Level of Service “E” 39,000 Existing Number of Lanes: 4
Future Daily Volume - Adopted Plan System Completed 25,300
Future Daily Capacity - Level of Service “E” 39,000 Future Number of Lanes: 4
Estimated Traffic Generation for Proposed Development 651
(Expressed in Average 24 Hr. Vehicle Trips)
Present Bus Service (Route, Frequency, Distance) Route 37, 30 minutes, 0 miles
Existing or Planned Bikeway None
Remarks:
STREET NUMBER 2
Nearest Existing or Planned Major Street
Is improvement planned as part of the 5-Year Transportation
Improvement Program? No
Year:
Planned
Existing Daily Volume – Based on Average Daily Traffic 0
Existing Daily Capacity- Level of Service “E” 0 Existing Number of Lanes: 0
Future Daily Volume - Adopted Plan System Completed 0
Future Daily Capacity - Level of Service “E” 0 Future Number of Lanes: 0
Present Bus Service (Route, Frequency, Distance)
Existing or Planned Bikeway
Remarks:
02/06/2003 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering does not recommend approval of this T.P.

1. Sheet 1, general note 6 should read John Evans, RLS vice RLR
2. sheet 1, general note 25, egress is misspelled
3. Sheet 1, general note 26j should read "...75 feet in length AND 3 feet..." vice a
4. Sheet 1 - add general note 28 to read "All non-signalized intersection street names must have E-W bock number addresses for E-W roadways and N-S block number addresses for N-S roadways."
5. Sheet 1, ROW section, missing arrow head from leftmost travel lane dimension line
6. Sheet 1, ROW section - show location of No Parking sign in section.
7. Sheet 5, Near side SVT from Lakeside View Drive is only required to be 180' vice 260'. 260 is acceptable as it is conservative.
8. In general, when determining which side of the street is to be designated as "no parking," we prefer to choose the side of the street that has the larger portion of side yards so that the residents may have their guests park directly in front of their houses. Therefore, we would prefer to have the designated visitor parking adjacent to lots 18 & 54 removed from the plans. This will still leave 26 designated visitor parking spots which still exceeds your requirement by your calculations.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dkelch1@ci.tucson.az.us
02/07/2003 LAITH ALSHAMI DEVELOPMENT SERVICES ENGINEERING Denied SUBJECT: Lakeside Ridge
S03-001, T14S, R15E, SECTION 28

RECEIVED: Tentative Plat, Landscape Plan and Drainage Statement on January 10, 2003

The subject project has been reviewed. We offer the following comments:

Drainage Report:

1. Provide an offsite watershed map and analyze the impact of offsite runoff on this development (i.e. analyze offsite watersheds other than Atterbury Wash's).
2. Provide an onsite watershed map with all relevant information.
3. It is not clear how the discharge at concentration point 1 for developed condition is disposed of. Verify that this discharge does not create any negative impact in the vicinity.
4. The HEC 2 analysis is not acceptable. It does not use the Atterbury Wash FEMA Model to determine the impact of the proposed development on the floodplain and drainage in the area. Revise as necessary.
5. Clarify where the HEC 2 cross-sections begin and end.
6. Use comments cards in the HEC 2 analysis.
7. Provide HEC 2 cross-sections plots.
8. Show on the drainage plan both existing and future 100-year floodplain.
9. The proposed grate inlet may not be bicycle safe. Revise.
10. Provide spillways and energy dissipaters at the discharge points into the Atterbury Wash. Privede design calculations.
11. Provide Erosion Hazard setback calculations.
12. Verify that the proposed development will have all weather access.
13. Rezoning Condition #4 requires completing a Conditional Letter of Map Revision (CLOMR) or a Letter of Map Revision (LOMR). The project review will be difficult to continue without the CLOMR. Submit a CLOMR application to FEMA as soon as possible.

Tentative Plat:

1. Provide the correct S (yr)-______ subdivision case number according to D.S. 2-03.2.2.B.1.
2. Add the word "Proposed" to the new zoning in General Note #1.
3. Show a NO PARKING sign on the Public ROW Section on sheet 1 of 5.
4. A lot of the information on the Tentative Plat (TP) is overlapping. Revise as necessary.
5. Provide the parcel boundary information as required by D.S. 2-03.2.3.B.
6. The Major Streets and Routes shows Stella right of way to be 64 feet. The TP shows the right of way 90 feet. Clarify.
7. Verify compliance with the differential grading requirements.
8. It is not clear what the delineation consisting of a solid line, three dots and solid line represent. Include this symbol in the Legend.
9. Show all existing easements and provide their recordation information, locations, widths and their purpose as required by D.S. 2-03.2.3.C. (if applicable).
10. Verify compliance with Rezoning Conditions 4 through 10. Demonstrate compliance on the TP.
11. Show if applicable all proposed easement as required by D.S. 2-03.2.4.J.
12. All survey monuments should be shown and described as either found or set (D.S. 2-03.2.3.A). Additionally, Provide survey monuments for all proposed lots.
13. Provide proposed drainage structures as required by D.S. 2-03.2.4.L.2 and 3.
14. Revise the Tentative Plat according to the Drainage Report revisions.

Landscape Plan:

1. Show water-harvesting basins.
2. Show existing and future sight visibility triangles and verify compliance with D.S.3-01.5.1.



RESUBMITTAL REQUIRED: Revised Tentative Plat, Landscape Plan and Drainage Statement
02/07/2003 PETER MCLAUGHLIN DEVELOPMENT SERVICES ZONING Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner


PROJECT:
Lakeside Ridge RCP
S03-001
Tentative Plat

TRANSMITTAL: February 7, 2003
DUE DATE: February 7, 2003



1. An applicant has one (1) year from the date of application to obtain approval of a tentative plat that complies with zoning and other development requirements in effect at the time of application. This tentative plat must be approved on or before January 9, 2004.
LUC 4.1.7.1

2. Fill in the S03-001 number near the title block in the lower right hand corner of all sheets of the plat, landscape and NPPO plans.
DS 2-03.2.2.B.1

3. Revise general note 1 to read "Proposed zoning is R-1 RCP-4". List the rezoning case number (C9-01-11) as part of general note 26.
DS 2-03.2.2.B.3

4. Revise all references to Sarnoff Road to read Sarnoff Drive.
DS 2-03.2.2.B.9

5. Add a general note stating that this RCP-4 development is subject to LUC Sec 3.6.1 and Sec. 3.5.7.1.E and .F.
LUC 2.3.4.2.A.3

6. The project location map must be revised to show Camino Seco along the east section line rather than Sarnoff Drive.
DS 2-03.2.1.D.2

7. Show the location and dimension widths of any existing or proposed easements. Add the recordation information by docket and page numbers for all easements, or state that they will be "by final plat".
DS 2-03.2.3.C
DS 2-03.2.4.J

8. LUC 3.6.1.4.A.9 requires that mechanical equipment be screened from adjacent exterior streets and from adjacent existing residential development. Screening shall be architecturally integrated with the overall design of the RCP. Add a general note stating how the mechanical equipment will meet this requirement.
LUC 3.6.1.4.A.9

9. Demonstrate compliance with rezoning condition g. regarding handicap access provided from Stella Lane and label the required bike rack and vegetative buffer. Revise this rezoning condition to be worded correctly.

10. Demonstrate compliance on the drawing with rezoning condition h. regarding the requirement for 10-foot landscape buffers along Sarnoff Dr. and Stella Rd. and 5-foot high masonry wall along Sarnoff. Demonstrate compliance with rezoning condition j. regarding variations in the wall alignment.

11. Label and dimension sidewalks to be provided along Sarnoff and Stella. Rezoning condition b. requires sidewalks which are six feet wide.

12. LUC 3.6.1.4.A.5 requires that 25% of all units be provided with barrier-free accessibility. Please provide a general note so stating and list which units will be barrier-free. Also, provide a drawing detailing how accessibility will be accomplished.
LUC 3.6.1.4.A.5
DS 2-10.3.1.D

13. General note 27 indicates a variance has been applied for. Please provide the variance case number, date of approval, what the variance was granted for and any conditions imposed as part of the general note. DS 2-03.2.2.B.6

14. Add a lot typical to the drawing which indicates building setbacks for perimeter yards, street perimeter yards and interior lot lines. Street yard perimeter setback is required to be "the greater of 21 feet or (H) measured from the outside edge of nearest adjacent travel lane." MS&R building setback is the greater of 21 feet or (H) measured from back of future curb location. Include setbacks for garages/carports which are 18 from property line, 19 feet from back of sidewalks.
LUC 3.2.6.5
LUC 3.6.1.4.D.2

15. Add a general note stating that the project is designed to meet LUC Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone. DS 2-03.2.2.B.7

16. Add a general note to the plat, which details the requirements for completion of project amenities and site improvements as stated in LUC 3.6.1.4.H. LUC 3.6.1.4.H

17. A copy of proposed CC&R's must be provided to the Zoning Review Section for review and approval prior to approval of the final plat. The CC&R's must meet the criteria of LUC 3.6.1.5 and DS 2-03.6.6.
DS 2-10.3.2.E

18. All requested revisions must be made to tentative plat, landscape & NPPO plans.
DS 2-07.2.1.A

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
02/10/2003 JOE LINVILLE DEVELOPMENT SERVICES LANDSCAPE Denied 1) Provide verification, in writing, of City Engineer (TDOT) approval of landscaping within the Stella Road and Sarnoff Drive right of way areas. LUC 3.7.2.9

2) Revise the tabulations on sheet L3 to identify the landscape borders required by condition of rezoning. C9-01-19

3) Indicate the grading limits on Sheet L3. DS 2-07.2.2.B.4

4) Revise the plans as necessary to comply with conditions of the rezoning case C9-01-19, including six-foot wide sidewalks along Stella Road and Sarnoff Drive.

5) Include the CDRC Case Number S03-001 on all plans. Also include related case numbers for reference. DS 2-07.2.1.B.h

6) Per LUC 3.7.4.2.A "Reclaimed water is to be used in new and expanded development in accordance with the adopted Mayor and Council Water Policies and other applicable state and local requirements." Reclaimed water may be available/required for this project. Contact Tucson Water and Parks and Recreation for additional information.

7) Designate decomposed granite or other suitable material for the Sarnoff Drive landscape border. LUC 3.7.2.7

8) The project is subject to TCC Chapter 29 Article VII as ammended by the variance request. The Landscape section requests a plant/habitat inventory (Sec. 29-15) which includes a mapping of all woody vegetation having a basal diameter in excess of two inches and a mitigation plan (Sec 29-16) including a plan for preservation and maintenance.

RESUBMITTAL OF THE TENTATIVE PLAT, LANDSCAPE PLAN, NATIVE PLANT PRESERVATION PLAN AND PLANT HABITAT INVENTORY AND MITIGATION PLAN IS REQUIRED.
02/13/2003 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 3950 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


Telephone: 520-884-3879
Fax: 520-770-2002
WR#100435 February 12, 2003



Mr. John A. Evans
John A. Evans & Associates Inc.
9180 E. Placita Senna
Tucson, AZ 85749

Dear Mr. Evans:

SUBJECT: Lakeside Ridge
Lots 1-68
S03-001

Tucson Electric Power Company (TEP) has no objection to the Tentative Plat submitted for review on January 15, 2003.

The preliminary point where TEP will serve this project is from an overhead pole line within Stella Road. Enclosed is a copy of TEP’s facility map showing the approximate locations and unit numbers of the existing facilities.

As you are aware, there are existing electrical facilities within the boundaries of this subdivision. Transformer unit numbers 306, 371 and 372, are existing from a prior land split, and will require removal. All relocation costs will be billable to the developer.

TEP will provide an electrical design on the Approved Tentative Plat within fifteen (15) working days upon receipt of the plat. at the customer’s written request, a design can be provided prior to the Approved Tentative Plat; however, once a design is provided, any design changes will be billable to the developer.

Should you have any questions, please contact me at (520) 884-3879.

Sincerely,



S. Glynda Rothwell
Right-of-Way Agent
Land Management

sgr
cc: C. Gross, City of Tucson
James C. Summerset
02/13/2003 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: February 12, 2003

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks, Parks and Recreation

RE: CDRC Transmittal, Project S03-001 Lakeside Ridge


CC: Craig Gross, Development Services


Staff has reviewed and has the following comments. Plans must clearly show and label the following:
25 ft wide path corridors to be dedicated along both sides of the Atterbury Wash
A shared-use asphalt path at least 10 ft wide in east path corridor
Safety railing for path
Handicap access to path from Stella Road
Bike rack
Reclaimed water shall be provided for the irrigation system in the path corridors
02/19/2003 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved COMPREHENSIVE PLANNING TASK FORCE COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S03-001 Lakeside Ridge 1/16/03

(X) Tentative Plat
() Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-01-11

NEIGHBORHOOD PLAN: South Pantano Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 2/06/03

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY THE COMPREHENSIVE PLANNING TASK FORCE, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(X) Proposal Complies with Annexation or Rezoning Conditions
(X) RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on:







REVIEWER: MSP DATE: 2/16/03
02/19/2003 MARILYN KALTHOFF COT NON-DSD REAL ESTATE Approved
02/20/2003 ED ABRIGO PIMA COUNTY ASSESSOR Approved
03/11/2003 TIM ROWE PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
DEVELOPMENT SERVICES DEPARTMENT
DEVELOPMENT REVIEW DIVISION
201 N. Stone Avenue, 2nd Floor
Tucson, Arizona 85701-1207

CARMINE DEBONIS, JR. Phone: (520) 740-6586
Director FAX: (520) 740-6380
February 26, 2003

TO: John Evans,, JAE Consulting Engineering

THRU: Craig Gross, City of Tucson Development Services

FROM: Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division

SUBJECT: Lakeside Ridge, Lots 1-68
Tentative Plat - 1st Submittal
S03-001



We have reviewed the above-referenced project on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

1. There is currently capacity in the existing downstream sewerage system for this development. This response is not to be construed as a commitment for conveyance capacity allocation, but rather an analysis of the existing sewerage system as of this date.

2. Based on the preliminary sewer layout as shown on the referenced tentative plat, this project would qualify for Non-Participating sewer connection fee rates. However, a final determination of this status cannot be made until approval of the sewer construction plans and/or preparation of the sewer service agreement.

3. The tentative plat is hereby approved, subject to the following:

4. All Sheets: Add the subdivision plat case number, S03-001, to the title block of each sheet. This number should be shown larger or bolder than the cross reference numbers.

5. Sheets 3 & 4: Label the existing sewer line in Lakeside Ridge Loop with its size (8") and plan number (I-65-17)

6. Sheets 2 & 4: Label the existing public sewer easement for existing sewer line I-65-17 with it’s width, type (public or private), additional uses, and recording information.

7. Sheets 3 & 5: What appear to be existing private cleanouts have been shown on Lots 64, 62, 60, 58, 56, 54, 53, & 52. If that’s what these are, and they are to be abandoned, they should be deleted.

8. Sheet 5: Label the existing sewer line in Sarnoff Drive with its size (15") and plan number (G-73-17).

9. The required revisions may be shown on the Mylars of the tentative plat that will be submitted to the CDRC for signature. A resubmittal of bluelines is not necessary.

If you wish to discuss the above comments, please contact me at 740-6563.

Tim Rowe, P.E., Development Review Engineer (Wastewater)
Pima County Development Review Division


TR/tr
Copy: Project