Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DS19-30
Parcel: 13809002B

Review Status: Completed

Review Details: DEV STDS MODIFICATION REVIEW

Permit Number - DS19-30
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2019 SBEASLE1 START PLANS SUBMITTED Completed
12/12/2019 MARTIN BROWN FIRE REVIEW Reqs Change Please provide dimensions regarding hammerhead tee at south end of project. Refer to figure D103.1 (in appendix D) of the 2018 International Fire Code for dimension requirements.
Please indicate on plans that "No Parking-Fire Lane" signs will be installed at both ends of the hammerhead tee.
12/12/2019 ZELIN CANCHOLA TRAFFIC TRAFFIC Approved
12/16/2019 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change TSMR RETURNED FOR CORRECTIONS NOTICE
See details below - a resubmittal is required.

Permit/Activity Number: DS19-30
Include this number on all future correspondence.

Project Description: Trinity, TSMR: 10-01.6.2.C.2 (road access).

Fees Due: $ 676.50
Note: We require a payment before we can accept your next submittal.
Please pay the total fees:
(Online Payments are not available for these "DS19..." permit numbers)
1. In person at the City Permit Counter (Mon-Fri, 8:00 AM to 2:00 PM)
2. By mail - a check payable to the City of Tucson (address is below),
include the Activity Number

To view documents and Reviewer's comments: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on "Review Details"

Submit the following items to the Filedrop.
In the Project Description field, enter the Activity Number.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Any other documents requested by review staff
3) Name your 2nd submittal documents accordingly, for example: 2_Plan_Set

HOLIDAY SCHEDULE: All Plan Review counters will be closed during Christmas week, Dec. 23-27. However, the Permit counter will be closed only on Dec. 25, and open the rest of the week from 8am-2pm, phone (520) 791-5550 press “O” for an operator

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 3rd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov
12/16/2019 LOREN MAKUS ENGINEERING REVIEW Approved
12/16/2019 SBEASLE1 ENV SVCS REVIEW Reqs Change Please find our comments for consideration:

Provide dimensions of turnaround, refer to Section 8 of TSM, page 8, Turnaround for Service Vehicles. If turnaround meets these minimum requirements, EGSD would approve as shown.

Thanks,
Andy Vera
City of Tucson Environmental Services
Accounts Representative Supervisor
Office (520) 837-3798, Fax (520) 791-4156
e-mail: Andy.Vera@tucsonaz.gov
12/16/2019 STEVE SHIELDS ZONING REVIEW Approved