| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 07/11/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Provide infiltration test results showing the infiltration rate will not clear the basin within 12 hours. 2. Results must show test locations, provide data for tests and describe the test procedure. 3. Clearly indicate which basin or basins the request is for. The site plan with the application only indicates the low flow pipe for the northern basin. 4. Provide a discussion of the boring logs and whether an engineered basin can be used instead of the low flow pipe. |
| 07/13/2018 | KELLY LEE | ZONING-DECISION LETTER | WRITE DECISION LETTER | Reqs Change | Plan Returned for Corrections Notice: ds18-13 This review has been completed and resubmittal is required. Please resubmit the following items to PDSD Filedrop https://www.tucsonaz.gov/file-upload-pdsd 1) Revised Plan Set 2) All items requested by review staff 3) All items needed to approve these plans Please remember to name your files appropriately, for example: Example 2 (second submittal): 2_plan_set.pdf 2_soils_report.pdf |