600 W 25TH ST

Review Status: Completed

Review Details: DEV STDS MODIFICATION REVIEW

Permit Number - DS16-02
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2016 PGEHLEN1 START PLANS SUBMITTED Completed
01/15/2016 DAVID RIVERA H/C SITE REVIEW Approv-Cond See comments in the zoning folder.
01/19/2016 DAVID RIVERA ZONING REVIEW Completed CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
Principal Planner

PROJECT: DS 16-02
600 W 25th Street
TSMR - 7-01.4.1.B, request to use paved area with striping to provide the required circulation path.

TRANSMITTAL DATE: January 15, 2016

DUE DATE: January 21, 2016

COMMENTS: Conditionally approved.

01. Zoning conditionally approves the TSMR request with the condition that the path from the front door to the street sidewalk is ADA compliant. Cross and running slopes must comply with the minimum slope requirements listed in the ANSI Chapter Four - Accessible Routes.

02. The running slopes may not exceed a 1 in 12 (8.33%) slope and the cross slopes may not exceed 2%.

03. The plans must include the grades depicting the slopes along the striped path from the front door location to the connection made at the new sidewalk.

04. The drawing must also include two detailed drawings with slope information for the following locations; the connection from the striped area to the north section of the new sidewalk and the sidewalk connection to existing sidewalk along the street right of way.

05. Revisions to the DP plan sheets must be made for zoning approval.

06. List the TSMR case number in the lower right corner of the plans sheets. List the TSMR case number as a general note along with the date of approval and conditions of approval.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
01/19/2016 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond See zoning comments.

TSMR approved-conditionally on 1/19/2016