Permit Number: DS11-11
Parcel: 12510025E

Review Status: Completed

Review Details: DEV STDS MODIFICATION REVIEW

Permit Number - DS11-11
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/16/2011 RONALD BROWN H/C SITE REVIEW Approved
08/17/2011 DAVE MANN FIRE REVIEW Approved
08/19/2011 FRODRIG2 ENV SVCS REVIEW Approved Date of Comments Case Number Project Address
August 18, 2011 DS11-11 Quebedeaux BUCK-GMC
Development Plan


Comments: The DSMR submitted for Case No. DS11-11, for the Quedebeaux BUCK-GMC,
located at 3566 E Speedway Boulevard. Is acceptable to Environmental Services for
solid waste and recycle materials and is hereby APPROVED.
.


Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
08/22/2011 JOSE ORTIZ TRAFFIC TRAFFIC Approved Approved no Traffic Engineering TDOT issues.

Review conducted by Zelin Canchola
08/23/2011 JOHN BEALL COMMUNITY PLANNING REVIEW Passed
08/23/2011 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

FROM: David Rivera
Principal Planner
DSD Zoning Review Section

PROJECT: DSMR-11-11
3566 E. Speedway Boulevard
Quebedeaux Buick-GMC
Development Standard Modification Request

Transmittal date: August 23, 2011

COMMENTS: Approved with conditions

1. After discussing the DSMR request(s) with the Zoning Administrator (due to unusual circumstances) the following is approved and approved with conditions.

DS 2-08.3.1 - pedestrian circulation and accessible circulation, and accessible route surface: All circulation as proposed on the DSMR plan sheet is acceptable to Zoning with the following conditions and changes. 1. The pedestrian surface in front and corners of Building Two must be concrete.
2. Barriers such as wheel stops or bollards at a minimum of 5 feet on center must be provided for the sidewalk in front of Building 2 and the path from Building One to Building Two except where the vehicle crossing occurs. The alternative is to provide raised concrete sidewalks at these locations.

2. DS 6-01.4.1.A - Zoning supports this DSMR request contingent upon Environmental Services supports and approves the request as well TDOT approval due to right of way concerns.



If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
08/24/2011 MATT FLICK ENGINEERING REVIEW Approved Revise General Note #6 on the Development Plan to reflect the Development Standard Modification Request. List the case number, date of approval, what was approved, and conditions of approval, if applicable.
08/25/2011 JOHN WILLIAMS ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES


July 7, 2011

Richard Cordova
DOWL HKM
406 N. Church Ave.
Tucson, Arizona 85701


Re: DSMR DS11-11 (3566 E. Speedway Blvd.) (D11-0013)

Request: DS 2-08.3.1 – Modify the Development Standard to waive pedestrian circulation path requirements.

DS 6-01.4.1.A – Modify the Development Standard to waive access and placement of trash containers.

The Development Standard Modification Request (DSMR) for DS 2-05.2.4.K listed above has been APPROVED with the following conditions:

1. The pedestrian surface in front and corners of building (2) two must be concrete.
2. Barriers such as wheel stops or bollards at a minimum of (5) five feet on center must be provided for the sidewalk in front of building (2) two and the path from building (1) one to building two except where the vehicle crossing occurs. The alternative is to provide raised concrete sidewalks at these locations.


The Development Standard Modification Request (DSMR) for DS 6-01.4.1.A listed above has been APPROVED with the following conditions:

1. N/A

PLEASE NOTE THAT A GENERAL NOTE MUST BE ADDED TO THE DEVELOPMENT PACKAGE WHICH STATES THE DSMR CASE NUMBER, DATE OF APPROVAL, MODIFICATIONS GRANTED, AND CONDITIONS IMPOSED. IN ADDITION, THE CASE NUMBER MUST BE ADDED TO EACH SHEET OF THE DEVELOPMENT PACKAGE, IN THE LOWER RIGHT CORNER NEAR THE TITLE BLOCK.


If you have any additional questions, please contact me at 837-4893.

Sincerely,




John Williams
Planning Technician
Planning & Development Services Department

Attachments: 1

XC: File