Permit Number: DS11-07
Parcel: 11446227B

Review Status: Completed

Review Details: RESUBMITTAL - DEV. STDS. REVIEW

Permit Number - DS11-07
Review Name: RESUBMITTAL - DEV. STDS. REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/12/2011 LEERAY HANLY ZONING HC REVIEW Approved
07/12/2011 DAVID MANN COT NON-DSD FIRE Approved
07/15/2011 DAVID RIVERA ZONING REVIEW Approved Approved per PDSD Director's direction.
07/15/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Approved Review conducted by Zelin Canchola

No adverse comments approved as shown.
07/18/2011 J.HERSHENHORN COT NON-DSD URBAN PLANNING & DESIGN Approv-Cond The plans are approved subject to approval from the Planning and Development Service's (PDS) Zoning Review Section, and the Enivronmental Services Department. A resubmittal to the PDS Community Planning Secton is not needed.

J. Hershenhorn, 7/18/11
07/19/2011 ELEIBOL1 ENGINEERING REVIEW Approved Subject: 2495 N. Desert links Drive, DS11-07 Dev. Std. Mod. Request Resubmittal

1. DS 2-08.4.1 (sidewalk Separation) - The sidewalk separation or striped sections within the vehicular use areas (between parking spaces) that have been identified on the DSMR plan sheets can be supported with the exception of three locations. The locations are noted as the striped area adjacent or next to lot 44, the striped space between lot 11 and lot 13, the striped area between lot 20 and lot 22. In the case of the area between lot 20 and 22 the sidewalk can be extended to connect the two sidewalks. These three areas must be constructed with concrete in order to connect to the concrete sidewalks.
2. DS 2-08.5.1.C (Sidewalk Composition) - The DSMR request is supported in the revised areas that are within areas that are not designated or required for accessibility routes or ADA compliance.
3. DS 3-01.4.1.1.b - (Width of the sidewalk within the Tanque Verde Right of Way) - The eng. div. has no objection to the DSMR request.
4. DS 6-01.4.2 - (Enclosure and Bin Construction) - The eng. div. has no objection to the DSMR request, provided Environmental Services has no objections.
5. DS 10-01.11.2.2 - (Threshold Retention) - The eng. div. has no objection to the DSMR request.


If you have any questions, contact Elizabeth Leibold at 837-4934 / Elizabeth.leibold@tucsonaz.gov, or Paul Machado or 837-4932 / Paul.Machado@tucsonaz.gov

City of Tucson - Planning and Development Services Department
Engineering Division
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
07/20/2011 JWILLIA4 ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

07/20/2011


Nick Westphal
DOWL HKM
166 W. Alameda St.
Tucson, Arizona 85701


Re: DSMR DS11-07; 2495 N. Desert Links Dr.; (D11-0012) REVISION



Request: DS 2-08.4.1 - Modify the development standard to waive sidewalk separation location requirements.

DS 2-08.5.1.C - Modify the development standard to allow for an alternative surface composition on sidewalks.

DS 3-01.4.1.A.1.b - Modify the development standard to waive sidewalk width requirements on existing sidewalks.

DS 6-01.4.2 - Modify the development standard on required Enclosure and Bin Construction.

DS 10-01.II.2.2 - Modify the development standard to eliminate Threshold Retention.


The Development Standard Modification Request (DSMR) for DS 2-08.4.1 listed above has been Approved with the following exceptions:

1. The following three locations are excluded from the DSMR Approval.
a. Striped area adjacent or next to lot 44.
b. Striped area between lot 11 and lot 13.
c. Striped area between lot 20 and lot 22.

The Development Standard Modification Request (DSMR) for DS 2-08.5.1.C listed above has been Approved with the following exceptions.

1. The Revised areas are not designated or required for accessibility routes or ADA compliance.


The Development Standard Modification Request (DSMR) for DS 3-01.4.1.A.1.b listed above has been Approved with the following conditions:

1. None

The Development Standard Modification Request (DSMR) for DS 6-01.4.2 listed above has been Approved with the following conditions:

1. The plans must include recycle containers and must be shown and labeled on the site plan.
2. All containers will require masonry enclosures with gates, and a detail of the enclosures must be shown and dimensioned on the plans in accordance with development standard 6-01.0.

The Development Standard Modification Request (DSMR) for DS 10-01.II.2.2 listed above has been Approved with the following conditions:

1. None




PLEASE NOTE THAT A GENERAL NOTE MUST BE ADDED TO THE PLAN WHICH STATES THE DSMR CASE NUMBER, DATE OF APPROVAL, MODIFICATIONS GRANTED, AND CONDITIONS IMPOSED. IN ADDITION, THE CASE NUMBER MUST BE ADDED TO EACH SHEET OF THE PLAN IN THE LOWER RIGHT CORNER NEAR THE TITLE BLOCK.

If you have any additional questions, please contact me at 837-4893.

Sincerely,






John Williams
Planning Technician
Planning & Development Services Department

Attachments: 1

XC: File
Records

Fax (520) 624-0384
07/20/2011 FRODRIG2 ENV SVCS REVIEW Approved Date Case Number Project Address
July 19, 2011 DS11-07 Tanque Verde At Wrightstown Casitas
2495 N. Desert Links Drive
Comments:
The DSMR submitted for Case No. DS11-07, Tanque Verde At Wrightstown Casitas Site Located at 2495 N. Desert Links Drive Is here by APPROVED by Environmental Service.



Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
07/20/2011 JWILLIA4 ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES
*** REVISION ***
07/20/2011


Nick Westphal
DOWL HKM
166 W. Alameda St.
Tucson, Arizona 85701


Re: DSMR DS11-07; 2495 N. Desert Links Dr.; (D11-0012) REVISION



Request: DS 2-08.4.1 - Modify the development standard to waive sidewalk separation location requirements.

DS 2-08.5.1.C - Modify the development standard to allow for an alternative surface composition on sidewalks.

DS 3-01.4.1.A.1.b - Modify the development standard to waive sidewalk width requirements on existing sidewalks.

DS 6-01.4.2 - Modify the development standard on required Enclosure and Bin Construction.

DS 10-01.II.2.2 - Modify the development standard to eliminate Threshold Retention.


The Development Standard Modification Request (DSMR) for DS 2-08.4.1 listed above has been Approved with the following exceptions:

1. The following three locations are excluded from the DSMR Approval.
a. Striped area adjacent or next to lot 44.
b. Striped area between lot 11 and lot 13.
c. Striped area between lot 20 and lot 22.

The Development Standard Modification Request (DSMR) for DS 2-08.5.1.C listed above has been Approved with the following exceptions.

1. The Revised areas are not designated or required for accessibility routes or ADA compliance.


The Development Standard Modification Request (DSMR) for DS 3-01.4.1.A.1.b listed above has been Approved with the following conditions:

1. None

The Development Standard Modification Request (DSMR) for DS 6-01.4.2 listed above has been Approved with the following conditions:

1. None


The Development Standard Modification Request (DSMR) for DS 10-01.II.2.2 listed above has been Approved with the following conditions:

1. None




PLEASE NOTE THAT A GENERAL NOTE MUST BE ADDED TO THE PLAN WHICH STATES THE DSMR CASE NUMBER, DATE OF APPROVAL, MODIFICATIONS GRANTED, AND CONDITIONS IMPOSED. IN ADDITION, THE CASE NUMBER MUST BE ADDED TO EACH SHEET OF THE PLAN IN THE LOWER RIGHT CORNER NEAR THE TITLE BLOCK.

If you have any additional questions, please contact me at 837-4893.

Sincerely,






John Williams
Planning Technician
Planning & Development Services Department

Attachments: 1

XC: File
Records

Fax (520) 624-0384